Model S4100C
i
Warranty Statement
General Monitors warrants the Model S4100C to be free from defects in workmanship
or material under normal use and service within two (2) years from the date of
shipment. General Monitors will repair or replace without charge any equipment
found to be defective during the warranty period. Full determination of the nature of,
and responsibility for, defective or damaged equipment will be made by General
Monitors’ personnel. Defective or damaged equipment must be shipped prepaid to
General Monitors’ plant or the representative from which shipment was made. In all
cases this warranty is limited to the cost of the equipment supplied by General
Monitors. The customer will assume all liability for the misuse of this equipment by its
employees or other personnel. All warranties are contingent upon proper use in the
application for which the product was intended and do not cover products which have
been modified or repaired without General Monitors’ approval or which have been
subjected to neglect, accident, improper installation or application, or on which the
original identification marks have been removed or altered. Except for the express
warranty stated above, General Monitors disclaims all warranties with regard to the
products sold, including all implied warranties of merchantability and fitness and the
express warranties stated herein are in lieu of all obligations or liabilities on the part of
General Monitors for damages including, but not limited to, consequential damages
arising out of/or in connection with the use or performance of the product.
Warnings
High off scale readings may indicate an explosive concentration of gas at the sensor.
A subsequent fall in indicated gas concentration does not imply that safe working
conditions have been restored.
Install and maintain all hazardous area equipment in accordance with the relevant
regulations and practices of the country concerned. See Section 3 Installation and
Section 5 Maintenance.
The S4100C must be protected by in-line 1A PC> 1500A Char “T” fuse (required if
voltage at unit is between 10VDC and 35VDC) or a 500mA fuse (required if voltage at
unit is between 18VDC and 35VDC) in the 24 VDC supply line. This is necessary to
fully comply with approval requirements and good installation practices.
NOTE: General Monitors series of Trip Amplifiers have the 500mA fuse as standard.
Where application requires 1A fuse, then this must be replaced at time of installation.
The S4100C must be protected by an in-line 63mA; PC> 1500A Char “F” fuse in the
analogue output line. This is necessary to fully comply with approval requirements and
good installation practices.
WARNING - Installation and Maintenance must be carried out by suitably skilled and
competent personnel only.