MYERS LVM-125 User manual

SAVE THESE INSTRUCTIONS
LVM-125/250
(LVS Catalog #: CEPS-125/250)INSTRUCTION MANUAL
EMERGENCY POWER EQUIPMENT
UNIVERSAL MICRO INVERTER
PURE SINUSOIDAL AC OUTPUT
OUTPUT VOLTAGE AUTO SETTING EQUAL TO INPUT VOLTAGE
AUTO DIMMING (0-10V) OF CONNECTED LOAD
IMPORTANT SAFEGUARDS
WHEN USING ELECTRICAL EQUIPMENT, BASIC SAFETY PRECAUTIONS SHOULD ALWAYS BE FOLLOWED,
INCLUDING THE FOLLOWING
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
1. To prevent electric shock, switch off the mains power until installation is complete and
AC input power is supplied to this product.
2. This product requires an unswitched AC power supply of 120-277V, 50/60Hz.
3. Ensure all connections are in accordance with National Electrical Code or Canadian
Electrical Code and all local regulations.
4. To reduce the risk of electrical shock, disconnect both normal power, emergency power
supplies and unit connector of this product before servicing.
5. For emergency operation of LED, incandescent, fluorescent fixtures and screw-base
lamps.
6. The product has a metallic housing and is suitable for installation in air handling/plenum
spaces in accordance with the National Electric Code.
7. Use this product in 0°C minimum, 50°C maximum ambient temperatures (Ta). To ensure
the emergency operating time over 90 minutes, the output emergency power of LVM-125
/250 should be maximum of 125W for the LVM-125 and 250W for the LVM-250.
8. Use with grounded, Listed, dry or damp location rated fixtures and the case should be
grounded.
9. Do not use outdoors. Do not mount near gas or electric heaters.
10. The use of accessory equipment not recommended by the manufacturer may cause an
unsafe condition and void warranty.
11. Do not use this product for other than intended use.
12. Installation and service should be performed by qualified service personnel.
13. This product should be mounted in locations and at heights where it will not readily be
subjected to tampering by unauthorized personnel.
10E22
44 South Commerce Way, Bethlehem, PA 18017 Technical Support:610-868-5400
THIS PRODUCT CONTAINS A RECHARGEABLE LITHIUM IRON PHOSPHATE BATTERY.
THE BATTERY MUST BE RECYCLED OR DISPOSED OF PROPERLY.
WWW.MYERSEPS.COM
WWW.LVSCONTROLS.COM
E95719
3KLH
INSTALLATION MANUAL
LFP

INSTALLATION
2/5
2. INSTALLING THE LVM-125/250
CAUTION: MAKE CERTAIN THE AC POWER IS OFFAND THELVM-125/250 BATTERY SWITCH IS
DISCONNECTED UNTIL THE INSTALLATION IS COMPLETE.
WWW.MYERSEPS.COM
WWW.LVSCONTROLS.COM
44 South Commerce Way, Bethlehem, PA 18017 Technical Support:610-868-5400
1. SPECIFICATION OF LVM-125/250
LVM-125 LVM-250
Output
Output Power
Voltage
Input
230V 50Hz
120V 60Hz
125W 250W
230V 50Hz
120V 60Hz
277V 60Hz 277V 60Hz
12
3
4
9
10
5
6
7ON
8

INSTALLATION
3/5
WWW.MYERSEPS.COM
WWW.LVSCONTROLS.COM
44 South Commerce Way, Bethlehem, PA 18017 Technical Support:610-868-5400
M2
L
L-37 [-1.46]
85 [3.35] 175 [6.89]
4.2 [0.17]
45 [1.77] 45 [1.77]
LVM-125
LVM-250
Item No. W
mm [inch]
H
mm [inch]
L
mm [inch]
292 [11.50]
398 [15.67]
M2 (Mounting)
mm [inch]
282 [11.10]
388 [15.28]
175 [6.89] 85 [3.35]
175 [6.89] 85 [3.35]
Dimension unit: mm [inch]
Weight
kg [lb]
4.2 [9.24]
7.0 [15.4]
M1 (Hanging)
mm [inch]
252 [9.92]
358 [14.09]
SURFACE MOUNTING
OPTIONAL MOUNTING ACCESSORIES AVAILABLE, CONSULT FACTORY FOR DETAILS:
WALL MOUNT ADAPTOR
CEILING-GRID MOUNT ADAPTOR

4/5
WIRING
CAUTION: DO NOT TURN BATTERY SWITCH ON UNTIL INSTALLATION IS COMPLETE AND AC
POWER IS SUPPLIED.
WWW.MYERSEPS.COM
WWW.LVSCONTROLS.COM
1. The LVM-125/250 requires an unswitched AC power supply of 120-277 volt, 50/60Hz.
2. Refer to the wiring diagrams below.
3. Consult the factory for other wiring diagrams.
44 South Commerce Way, Bethlehem, PA 18017 Technical Support:610-868-5400
GROU N D
NEUT R A L
* The max. linkable luminaire
quantity for emergency will be
different due to different electrical
appliances, which needs to be
verified by end users.
LED
FLUORESCENT
INCANDESCENT
LUMINAIRE
FOR EMERGENCY
LED
FLUORESCENT
INCANDESCENT
LUMINAIRE
FOR EMERGENCY
LED
FLUORESCENT
INCANDESCENT
LUMINAIRE
LED
FLUORESCENT
INCANDESCENT
LUMINAIRE
0-10V
DIMMER
SWITCH
+
-
HOT
WIRING DIAGRAM FOR 0-10V DIMMABLE EMERGENCY LIGHTING SYSTEM
ANY QUANTITY
WIRING DIAGRAM FOR NON-DIMMABLE EMERGENCY LIGHTING SYSTEM
ANY QUANTITY
MAX. POWER = 125W (LVM-125)
= 250W (LVM-250)
MAX. DIMMABLE LOAD = 750W
GROU N D
LED
FLUORESCENT
INCANDESCENT
LUMINAIRE
FOR EMERGENCY
LED
FLUORESCENT
INCANDESCENT
LUMINAIRE
FOR EMERGENCY
LED
FLUORESCENT
INCANDESCENT
LUMINAIRE
LED
FLUORESCENT
INCANDESCENT
LUMINAIRE
HOT
120- 2 7 7 VA C
NEUT R A L
SWITCH
LDim out +
+
GND
N
Switched N-OUT
L-OUT Dim out - Dim in +Dim in -
LED Test Switch
-
Unswitched
L
FUSE
ON
Battery
Switch
LDim out +
+
GND
N
Switched N-OUT
L-OUT Dim out - Dim in +Dim in -
LED Test Switch
-
Unswitched
L
FUSE
ON
Battery
Switch

5/5
OPERATION / TESTING / MAINTENANCE
WWW.MYERSEPS.COM
WWW.LVSCONTROLS.COM
OPERATION
When AC power is applied, the LED test switch is illuminated, indicating that the batteries are being charged.
When AC power fails, the LVM-125/250 automatically switches to emergency power, operating the lighting load
at rated emergency power. During power failure, the LED test switch will be off. When the AC power is restored,
the LVM-125/250 switches the system back to normal mode of operation and resumesbattery charging.The
minimum emergencyoperation time is 90 minutes. A short term discharge test may be conducted after unit has
been charging for 1 hour. The charging time for the fulldischarged batteryof LVM-125 is 12 hours, of LVM-250
is 24 hours.
TESTING AND MAINTENANCE
The following Periodictesting is recommended to ensure the system is working correctly.
1. Visually inspect the LED test switch (LTS) monthly. Itshould be illuminated when ACpower is applied.
2. Conduct a 30-second discharge test by switching off theemergency breaker everymonth.TheLTS will be off.
3. Conducta90-minute dischargetestonce per year. The LTS will be off during thetest.
AUTO TEST
This LVM-125/250 has an Auto Test feature which saves cost by reducing theneed for manual testing.
1. Initial Auto Test
When the system is connected properly and powered on (make sure the load is switched on), the
LVM-125/250 will perform an InitialAuto Test. If any abnormalconditionsexist, the LTS willblink quickly. Once
the abnormalcondition is corrected, the LTS will function correctly. The Initial Auto Testwillbe restarted
automatically whenthe connected dimmable loads'maximum power increases.
2. Preprogrammed Scheduled Auto Test
a) The LVM-125/250 will conduct the firstMonthlyAutoTest after 24 hours and up to 7 days after initialpower on.
Then monthly tests will be performed every 30 days.
b) Annual Auto test will occur every 52 weeksafter initial power on.
- Monthly Auto Test
The Monthly Auto Test shall be executed every 30 days, and will test:
Normal to emergency transfer function, emergency, charging and discharging conditions are normal.
Monthly test time is approximately 60 seconds.
- Annual Auto Test
Annual Auto Testwill occur every 52 weeks after the initial 24 hoursfull charge, and will test:
Proper initialbatteryvoltage, 90-minute emergencyoperation and acceptable batteryvoltage at theend of the
full 90-minute test.
If the Auto Test is interrupted by a power failure, a full90-minute Auto Test will occur again 24 hours after the
power is restored.If the power failure causes the battery to fully discharge, the product will restart the Initial
Auto Test and Preprogrammed Scheduled Auto Test.
MANUALTEST
1. Press the LTS one time to simulate emergency mode for 10 seconds.
2. Pressthe LTS 2 times continuously within 3 seconds to force a 60-second monthly test. Afterthe test is
completed, the next (30-day) monthly test will countfrom this date.
3. Press the LTS 3 times continuously within 3 seconds to force a 90-minute annual test. After the testis
completed, the next (52-week) annual test will count from this date. Note: Prior to conducting annual test, the
LVM-125/250 must be charged for 24 hours.
4. In normal mode, press and hold the LTS for greater than 3 seconds to restart Initial Auto Test.
5. During any manual test, press and hold the LTS for greater than 3secondsto terminate a manual test. The
Preprogrammed Scheduled Auto Test time will not change.
LED TEST SWITCHCONDITIONS
LTS Slow Blinking: Normal Charging
LTS On:Battery Fully Charged - Normal Condition
LTS Off: Power Failure
LTS Gradual Change: In Testing Mode
LTS Quickly Blinking: Abnormal Condition - Corrective Action Required
44 South Commerce Way, Bethlehem, PA 18017 Technical Support:610-868-5400
This manual suits for next models
3
Table of contents
Other MYERS Inverter manuals
Popular Inverter manuals by other brands

Uniteck
Uniteck UNIFIX 20S manual

Black & Decker
Black & Decker PI100BB instruction manual

Sima
Sima SCG user manual

Industrial Scientific
Industrial Scientific Solar Power Supply quick start guide

Hoymiles
Hoymiles HMT-1800 Series Quick installation guide

Leroy-Somer
Leroy-Somer DIGIDRIVE Series Installation and commissioning