Nabco GT 300 Operation manual

NABCO ENTRANCES, INC., S82 W18717 Gemini Drive, Muskego WI 53150, (877) 622-2694, (888) 679-3319 fax Rev 10/13
Models GT300 & GT8300
HEAVY DUTY - SWING DOOR OPERATOR - OVERHEAD CONCEALED
DIVISION 08 – OPENINGS
SECTION 08 42 29.33 SWINGING AUTOMATIC ENTRANCES
Note to Specifier: Articles and paragraphs below may be edited or modified to suit specific project requirements.
Add section numbers and titles per CSI “MasterFormat” and specifier’s standard practice. Contact manufacturer’s
representative to discuss specification modifications, performance requirements, accessories and/or related equipment
that may be applicable to this project.
Part 1 - GENERAL
1.01 DESCRIPTION
A. Furnish and install automatic swing door equipment as indicated on drawings and specifications.
B. Related work specified elsewhere.
(See note to Specifier*)
1. Electrical Supply:
Section________
1.02 REFERENCES
A. American Association of Automatic Door Manufacturers (AAADM) - www.aaadm.com
B. American National Standards Institute (ANSI) - www.ansi.org
C. Builders’ Hardware Manufacturers Association (BHMA) - www.buildershardware.com
D. Underwriters Laboratory, Inc. (UL) - www.ul.com
E. Canadian Standards Association (CSA) - www.csa.ca
F. National Fire Protection Association (NFPA) - www.nfpa.org
G. International Code Council (ICC) - www.iccsafe.org
1.03 QUALITY ASSURANCE
A. Manufacturer’s Qualifications: Manufacturer to have at least (5) five years experience in the fabrication of automatic
entrance systems.
B. Installer’s Qualifications: Products specified shall be represented by a factory authorized and trained distributor.
Distributor shall be AAADM Certified, maintain a parts inventory and have trained service personnel with experience
installing and maintaining units indicated for this project.
C. All automatic equipment to comply with UL325 (USA and Canada).
D. All automatic equipment to comply with ANSI A156.10.
1.04 SUBMITTALS
A. Product Data: Submit manufacturer’s product and complete installation data for all materials covered in this section.
B. Shop Drawings: Submit complete elevations, details and methods of anchorage to location; installation of hardware; size,
shape, joints and connections; and details of joining with other construction.
C. Templates and Diagrams: As needed shall be furnished to fabricators and installers of related work for coordination of
swinging door system with concrete work, electrical work, and other related work.
D. A copy of appropriate manuals shall be provided to owner / contractor upon completion of installation.
1.05 SUBSTITUTIONS
GT SYSTEM 300 & 8300 OVERHEAD
CONCEALED (OHC)
SUGGESTED ARCHITECTURAL SPECIFICATIONS
SECTION 8
AUTOMATIC ENTRANCE SYSTEMS

NABCO ENTRANCES, INC., S82 W18717 Gemini Drive, Muskego WI 53150, (877) 622-2694, (888) 679-3319 fax Rev 10/13
A. Gyro Tech equipment as manufactured by NABCO ENTRANCES, INC. has been specified and shall be quoted as the
base bid. Proposals for substitution products may be submitted by the bidding contractors a minimum of 10 days prior to
bid due date. The proposed substitution shall meet the quality and performance standards described in this specification.
1.06 JOB SITE CONDITIONS
A. Site Survey: Verify site conditions including, but not limited to the following: opening sizes, floor conditions, plumb and
level mounting surfaces (substrates shall be of proper dimension and material).
B. Coordinate installation with glass, glazing, hardware and electrical to avoid construction delays.
1.07 WARRANTY
A. Warranted materials shall be free of defects in material and workmanship for a period of one year from date of substantial
completion. During the warranty period the Owner shall request NABCO factory-trained technicians to perform service.
Warranty repairs are provided during normal business hours. Owner to receive warranty after completion of installation.
1.08 COMPLIANCE
A. A completed American Association of Automatic Door Manufacturers (AAADM) compliance form shall be submitted as
proof of compliance with ANSI A156.10 Standard for power operated pedestrian doors. Door(s) shall be inspected and a
form shall be signed by an AAADM certified inspector prior to placing door(s) in operation.
Part 2 - PRODUCTS
2.01 APPROVED MANUFACTURER
A. Automatic equipment and controls shall be manufactured by:
NABCO ENTRANCES INC.
S82 W18717 Gemini Drive
Muskego, WI 53150
Phone: (877) 622-2694
Fax: (888) 679-3319
2.02 AUTOMATIC OVERHEAD CONCEALED (OHC) SWING DOOR SYSTEM
A. Model GT300 Bottom Load or GT8300 Side Load Swing Door System as indicated on door schedule and details.
B. Mode of operation: Spring Close. Gyro Tech swing operator shall open door by energizing motor and shall stop door by
electrically reducing voltage and stalling motor against mechanical stop. Door shall close by means of spring energy, and
closing force shall be controlled by gear system and with motor being used as a dynamic brake without power. System
shall operate as a manual door control in event of power failure. Manual operation shall require less than 30 lbs. force
applied to door lockstile. Opening and closing speeds shall be adjustable. Hold open time shall be adjustable from 1-60
seconds. Door operation shall not require any fluids or gases under pressure to be used in opening and closing of door.
C. Components:
1. Operator Housing
2. Gyro Tech GT300 & GT8300 Swing Door Operator
3. Microprocessor Control
4. Connecting Hardware
5. Breakaway Door Stop – If required
1a) Operator Housing for the GT300 Bottom Load shall be, 5 1/2" (140mm) deep by 5" (127mm) high aluminum
extrusion with finished end caps and shall be prepared for mounting to new or existing door frames. All structural sections
shall have a minimum thickness of .146” (4mm) and shall be fabricated of 6063-T5 aluminum alloys. Housing cover shall
be removable to provide service access and shall be extruded from 6063-T5 aluminum alloys to a minimum thickness of
.093” (2mm). Plastic covers shall not be acceptable.
1b) Operator Housing for the GT8300 Side Load shall be, 5 1/2" (140mm) deep by 6" (152mm) high aluminum extrusion
with finished end caps and shall be prepared for mounting to new or existing door frames. All structural sections shall
have a minimum thickness of .166” (4mm) and shall be fabricated of 6063-T5 aluminum alloys. Hinged housing cover
shall be able to be raised and secured or removed to provide service access and shall be extruded from 6063-T5 aluminum
alloys to a minimum thickness of .100” (3mm). Plastic covers shall not be acceptable.
1c) Finish: Aluminum shall have a standard finish of AA-M12-C22-A31 (204R1, clear) or AA-M12-C22-A44 (dark
bronze). Black and special finishes available upon request.
2) Power Operator: Completely assembled and sealed unit which shall include helical gear-driven transmission,
mechanical spring and bearings all located in cast aluminum housing and filled with special lubricant for extreme

NABCO ENTRANCES, INC., S82 W18717 Gemini Drive, Muskego WI 53150, (877) 622-2694, (888) 679-3319 fax Rev 10/13
temperature conditions. Attached to transmission system shall be a DC permanent magnet motor with sealed ball
bearings. Motor shall operate from 115-volt supply and require less than 3 amps at full power stall. Complete unit
shall be resilient mounted with provisions to easily adjust/replace the motor and gearbox without removing door from
pivots or frame.
3) Electrical Control: Shall be a solid-state microprocessor unit. The microprocessor control shall allow the opening
speed, closing speed, back check and latch check speed each to be adjusted separately and independently from each other
to meet specific site conditions. Adjustable opening and closing speeds shall be set in accordance with ANSI A156.10.
All adjustments shall be specific and reproducible.
4) Connecting Hardware: Connect overhead (OHC)-type power operator drive arm to door with a pin linkage rotating in
a self lubricated bearing, within a self adjusting slide block, traveling in an interconnected steel track and top door pivot
assembly. The (OHC) unit will independently support the door on heavy-duty steel top and bottom door pivots. To allow
for durability and easy serviceability, the door shall not pivot on shaft of operator.
5) Emergency breakaway doorstop shall mount directly to the underside of operator housing. It shall function as a stop
on all center pivoted in-swinging doors. A force of not more than 50 LBF applied at the lock stile shall cause the
breakaway stop to rotate, interrupt automatic operation and allow the door to swing open 180 degrees opposite its normal
travel. Swinging the door back into the normal mode of operation resets the breakaway doorstop and reengages the
operator for normal automated operation.
2.03 ACTIVATING DEVICES
A. Sensor Devices - Approach side. Nabco Entrances Acusensor or Optex Reaction Two
1.) The Acusensor as manufactured by NABCO ENTRANCES, INC. is a presence sensing active infrared sensor.
Sensing shall be provided in a rectangular shaped pattern with sensing immediately next to the door system. To provide
optimum coverage to meet specific site conditions the sensing pattern width and depth shall be adjustable while
remaining at a full power setting.
2.) The OPTEX Reaction Two microwave sensor is specially designed to increase efficiency on opening of automatic
doors. Uni-directional mode ignores traffic moving away from the door and assures the minimum door open time. The
OPTEX microwave provides fast detection for automatic door installations and particularly for applications with high
speed entries
B. Sensor Devices - Swing Side. The Optex OA Edge system shall be provided which includes two sensors mounted near
the top of the door to provide continuous sensing coverage on both sides of the door panel including during the opening
and closing operations.
C. Additional Specification Options for consideration - See product catalog
PART 3- EXECUTION
3.01 INSTALLATION
A. Automatic door equipment shall be installed by AAADM Certified, factory-trained installers in compliance with ANSI
A156.10, manufacturer’s recommendations and approved shop drawings.
3.01 CLEANING AND PROTECTION
A. After installation, clean framing members as recommended by the manufacturer. Aluminum surfaces in contact with
masonry, concrete or steel shall be protected from contact by use of neoprene gaskets, where indicated, or a coat of
bituminous paint to prevent galvanic or corrosive action. Advise general contractor to protect unit from damage during
subsequent construction activities.
* COVER NOTE TO SPECIFICATION WRITER
Indicate under appropriate Section the following work by others:
ELECTRICAL INSTALLER shall furnish and install all conduit and electrical wiring for activating devices and door
operators. A minimum of 5 amperes, 115 volts, A/C, 1-phase circuit shall be furnished for each door operator, terminate
and connect to operator control panel, in operator housing.
CONCRETE INSTALLER shall prepare floor at location of automatic entrance system to be level and smooth without
changes in elevation between foundation and associated walkways.
END OF SECTION
Other manuals for GT 300
2
This manual suits for next models
1
Table of contents
Other Nabco Gate Opener manuals
Popular Gate Opener manuals by other brands

GFA
GFA 10003600 10012 installation instructions

Nice
Nice Wingo 5024 Kit Instructions and warnings for installation and use

Beninca
Beninca CORE user manual

Bircher Reglomat
Bircher Reglomat InTra6 3 operating instructions

GBD
GBD KUDA 150 Instructions for installations

Chamberlain
Chamberlain WGO200 instructions

Gamatech
Gamatech PK300DC user manual

Roger
Roger MONOS4 INSTRUCTIONS AND RECOMMENDATIONS FOR THE INSTALLER

McConnel
McConnel 5 Wheel Backing Gate Drive owner's manual

tau
tau MASTER Maintenance manual

Maximum Controls
Maximum Controls MAX F18 Installation and owner's manual

Portamatik
Portamatik TOP500 User's and installer's manual