Getting Started with the NI 9502 and AKM Motors 12 ni.com
Complete the following steps to connect the NI 9502 to the NI AKM motor.
1. Connect the motor connector on the cable to the NI AKM motor connector.
2. Connect the motor Phase U, Phase V, and Phase W, and COM wires to the NI 9502.
3. Connect the feedback connector on the cable to the NI AKM feedback connector.
4. Connect the Hall 1, Hall 2, Hall 3, and COM wires from the Halls portion of the cable to the
NI 9502.
5. Connect the +5 V and COM wires from the encoder portion of the cable to a 5 V power supply.
6. Connect the COM from the 5 V power supply to the NI 9502 COM, to provide a common reference.
Software Installation and Configuration
This section covers installing and configuring the software for the NI 9502 servo drive module. It
assumes that all required software from the What You Need to Get Started section is installed.
Step 1: Install Software on and Configure the NI RT Controller
Complete the following steps to configure the controller and install software on it.
1. Launch Measurement & Automation Explorer (MAX) on the development computer by clicking
the MAX icon on the desktop, or by selecting Start»All Programs»National Instruments»
Measurement & Automation.
2. Select the controller under Remote Systems in the Configuration pane. If you do not see the
controller, you may need to disable the firewall on the development computer.
3. Verify that the Serial Number in the Identification section matches the serial number on the
device.
4. If you do not want to format the disk on the controller, eliminating all installed software and files,
power on the controller and skip to step 12.
5. Set the Safe Mode switch on the controller to the On position.
6. Power on the controller. If it is already powered on, press the Reset button on the controller to
reboot it.
7. Right-click the controller under Remote Systems in the Configuration pane and select Format
Disk. Click Yes on the dialog box that appears.
8. When MAX finishes formatting the disk, set the Safe Mode switch to the Off position and press
the Reset button on the controller to reboot it.
9. Select the System Settings tab and type a descriptive name for the system in the Name field.
10. (Optional) Complete this step only if the target has an empty IP address (0.0.0.0). Select the
Network Settings tab and select DHCP or Link Local from the Configure IPv4 Address list to
assign an IP address or select the Static to specify a static IP address in the IPv4 Address section.
11. Click Save on the toolbar and let MAX reboot the system.
12. When the new system name appears under Remote Systems, expand the controller item in the tree,
right-click Software, and select Add/Remove Software.
13. Select a recommended software set that includes NI-RIO 4.0 or later.
14. Click Next.
15. (Optional) Select LabVIEW NI SoftMotion Module 11.0.1 or later from the add-ons list.
16. Click Next to install the selected software on the controller. Click Help if you need information
about installing recommended software sets.
17. Close MAX.