2TM-4 Instructions P/N 51490, Rev A 7/02/01
Specifications
TM-4 Power Requirements
24 VDC, 175 mA
Three (3) isolated reverse polarity outputs
Maximum current per output: 15mA
Reverse polarity voltage: 24 VDC nominal
Fire Municipal Box trip
Supervisory current: 250 µA
Trip current: 0.35 A
Coil voltage: 3.65 VDC
Coil resistance: 14.6 ohms
Wire resistance: 3.0 ohms maximum
Indicators
LED 1 - ACS Receive - Blinks green when Annunciator Control System (ACS) data is received.
LED 2 - ACS Transmit - Blinks green when ACS data is transmitted.
LED 3 - Trouble - Lights yellow when an ACS trouble occurs, or the Disable All Outputs switch (SW4) is on.
LED 4 - Power - Lights when 5 V of power is present on the TM-4 board.
Switches
SW1 - EOL resistor switch - Must be set to ON when the TM-4 is the last device on the ACS circuit.
SW2 - Address switch, tens position. Turn the dial until the arrow points to the number in the tens position of the ACS address.
SW3 - Address switch, ones position. Turn the dial until the arrow points to the number in the ones position of the ACS
address.
SW4 - Disable All Outputs switch - disables all outputs except Remote Station Trouble when turned ON, for ease in
maintenance.
Note: When this switch is ON, a trouble message is displayed at the FACP.
SW5 - Set of four DIP switches that function as follows:
SW5.1, SW5.2 - Not used.
SW5.3 - When set to ON: If the Signal Silence button at the panel is pushed after an alarm has been initiated, the
Remote Station or Municipal Box output will deactivate. A subsequent alarm will reactivate the output.
Note: This function is not valid for the AM2020/AFP1010 or INA.
SW5.4 - When set to ON Alarm and Trouble signals are combined onto one output (REMOTE STATION ALARM).
SW6 - Isolator switch - isolates or non-isolates the Municipal Box output.
Installation
The TM-4 is designed to mount in the NFS-640, CHS-4N, or
CHS-4L chassis, on a BMP-1 blank plate for dress panel
mounting, or in the ABS-8R cabinet.
The TM-4 comes with four Phillips-head screws (3/8” [9.5
mm] 4-46 screws, included) to be used in the locations indi-
cated at left.
Screw hole locations
Tab
TM-4
TM4cad.cdr
Screw hole locations