Notifier XP6-MA User manual

BEFORE INSTALLING
If the modules will be installed in an existing operational system,
inform the operator and local authority that the system will be tem-
porarily out of service. Disconnect the power to the control panel
before installing the modules. This system contains static sensitive
components. Always ground yourself with a proper wrist strap be-
fore handling any circuits so that static charges are removed from the
body. The module housing should also be grounded.
NOTICE: This manual should be left with the owner/user
of this equipment.
GENERAL DESCRIPTION
The XP6-MA Six Zone Interface Module is intended for use in an
intelligent alarm system. Each module provides an interface be-
N500-80-00 1 I56-1806-006
Notifier, 12 Clintonville Rd., Northford, CT 06472-1653 Phone: (203)484-7161
XP6-MA Six Zone Interface Module
Installation And Maintenance Instructions
SPECIFICATIONS
Normal Operating Voltage: 15-32VDC
Stand-By Current: 2 mA
Alarm Current: 40 mA (assumes all six LEDs solid on)
Temperature Range: 32ºF to 120ºF ( 0ºC to 49ºC)
Humidity: 10 to 93% Non-condensing
Dimensions: 6.8˝H x 5.8˝W x 1.0˝D
Accessories: CHS-6 Chassis; BB-25 Cabinet; BB-XP Cabinet; CAB-4 Series Cabinets; CAB-3 Series Cabinets
Wire Gauge: 12-18 AWG
Maximum IDC Wiring Resistance: 25 Ohms
External Power Supply Voltage: Regulated 24VDC
Ripple Voltage: 0.1 volts RMS maximum
IDC (supervised and power limited)
DC Voltage: 18-28 volts power limited
Frequency: DC
Current: 90mA per circuit
DET. DETECTOR
MODEL COMP. ID MANUFACTURER BASE MODEL MAX DET.
1151 A SYSTEM SENSOR B110LP, B401 20
1451 A SYSTEM SENSOR B401, B401B 20
1451DH A SYSTEM SENSOR DH400 20
2151 A SYSTEM SENSOR B110LP, B401 20
2451 A SYSTEM SENSOR DH400, B401B, B401 20
2451TH A SYSTEM SENSOR B401, B401B 20
5451 A SYSTEM SENSOR B401 20
1100 A SYSTEM SENSOR N/A 20
1400 A SYSTEM SENSOR N/A 20
**2100AT A SYSTEM SENSOR N/A 20
2100B A SYSTEM SENSOR N/A 20
2100D A SYSTEM SENSOR N/A 20
2100S A SYSTEM SENSOR N/A 20
2100TB A SYSTEM SENSOR N/A 20
2100TD A SYSTEM SENSOR N/A 20
2100TS A SYSTEM SENSOR N/A 20
2300B A SYSTEM SENSOR N/A 20
2300TB A SYSTEM SENSOR N/A 20
2400 A SYSTEM SENSOR N/A 20
2400TH A SYSTEM SENSOR N/A 20
* 2W-B A SYSTEM SENSOR N/A 20
* 2W-TB A SYSTEM SENSOR N/A 20
DH100LP A SYSTEM SENSOR N/A 20
* Class B, Style B only
** No Accessory will be supported by 2100AT
tween the intelligent alarm system and a conventional alarm sys-
tem loop. A common SLC input is used for all modules, and the
initiating device loops share a common supervisory supply and
ground. Otherwise, each monitor operates independently from the
others. Each module has its own unique address.
A pair of rotary code switches is used to set the address of the first
module from 01 to 154. The remaining modules are automatically
assigned to the next five higher addresses. Provisions are included
for disabling a maximum of two unused modules to release the
addresses to be used elsewhere. Each module also has panel con-
trolled bicolor LED indicators. The panel can cause the LEDs to
blink, latch on, or latch off.
Compatible Two-wire System Sensor Smoke Detectors for use with XP6-MA with Zone Identifier A
I56-1806-006

Cabinets
A BB-25, CAB-3 or CAB-4 Series cabinet will house the CHS-6
chassis with up to six XP6-MA modules installed on it. Refer to
cabinet installation documents for dimensions.
The BB-XP cabinet houses one or two XP6-MA modules on the
internal chassis that is part of the cabinet. Refer to cabinet instal-
lation documents for dimensions.
INSTALLATION STEPS
1. Cabinet Mounting
In a clean, dry area, mount the backbox using the four holes
provided in the back surface of the cabinet (Figure 3).
2. Chassis Installation
The CHS-6 chassis is mounted in the BB-25, CAB-3 or CAB-4
Series cabinet. It is shipped with two self-threading screws,
which are used to fasten the chassis to the back wall of the
cabinet (Figure 4).
Figure 3. Typical mounting hole locations:
Backbox
Mounting
Holes
C0235-00
Figure 4: Mounting the CHS-6 chassis
Mount with self-threading screws
to back of cabinet
C0236-00
The BB-XP cabinet comes with the chassis already installed, so
no mounting is necessary.
3. Module Installation
There are two methods for installing a module in the rear
position of a chassis. Method one is for installation of a rear
module only, when no module will be installed in front of it.
Refer to Figure 5 for instructions. Method two is for installation
of a rear module when another module will be installed in the
chassis position in front of it. Refer to Figures 6a and 6b for
method two. All necessary screws and standoffs are supplied
with the modules.
Figure 5. Installation of rear module only, method one:
23
1
C0237-00
Included:
(5) 1 x 4 Terminal Blocks (2) 11/4″Stand offs (3) Shunts
(4) Machine Screws (1) Long Power Supply Jumper
(6) 3.9k Ohm
End of Line Resistors
Shipped on Board:
(2) Shunts in Class A/B position
(Shipped in Class B position, remove shunts for Class A)
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected to a com-
patible Notifier system control panel (list available from Notifier).
COMPONENTS
Following are descriptions of the XP6-MA mounting frameworks.
There are two mounting options for XP6-MA modules:
Up to six XP6-MA modules can be installed on a CHS-6 in a
CAB-3 Series, CAB-4 Series or BB-25 cabinet
One or two XP6-MA modules can be installed in a BB-XP cabinet
Chassis
The CHS-6 chassis is used to mount XP6-MA modules in a BB-25,
CAB-3 or CAB-4 Series cabinet. It accommodates up to six XP6-
MA modules in a single cabinet row three modules wide and two
modules deep.
Figure 1. CHS-6 Chassis:
C0206-00
The BB-XP cabinet has a built-in chassis that will accommodate
one or two XP6-MA modules.
Figure 2. BB-XP Cabinet:
0
1
2
3
456789
0
78
6
5
4
3
21
910
11
12
13
14
15
BASEADDRESS
ADDRESS
DISABLE
NONE
ONE
TWO
THREE
0
1
2
3
456789
0
78
6
5
4
3
21
910
11
12
13
14
15
BASEADDRESS
ADDRESS
DISABLE
NONE
ONE
TWO
THREE
C0234-00
The front XP6-MA module positions of each chassis are offset
below the rear XP6-MA module positions so that all of the status
indicators are visible.
•
•
N500-80-00 2 I56-1806-006
(2) Nuts

1/4˝ of insulation from the end of wire, sliding the bare end of
the wire under the clamping plate screw.
3. Set the address on the modules per the job drawing. Use the
rotary code switches to set the address of the first module (be-
tween 01 and 154).
In Class B operation, the remaining modules
are automatically assigned to the next five
higher addresses. For example, if the base ad-
dress switch is set to 28, the next five modules
will be addressed to 29, 30, 31, 32 and 33.
The module is shipped in Class B position,
remove shunts for Class A. When operating in
Class A, alternate modules are paired together
(+0/+1, +2/+3, +4/+5), resulting in a
total of three modules. For example, if the base address switch
is set to 28, then 30 and 32 will be automatically assigned to the
modules while 29, 31 and 33 are available to be used for other
modules on the SLC. For Class A and B operation, DO NOT set the
lowest address above 154, as the other modules will be assigned
to nonexistent addresses.
NOTE: The XP6-MA must have power cycled for shunt changes
to take effect.
NOTE: Some panels support extended addressing. In order to set
the module above address 99 on compatible systems, carefully
remove the stop on the upper rotary switch (see Figure 7). If the
panel does not support extended addressing, do not set the lowest
address above 94.
4. A shunt is provided to disable a maximum of two unused modules
in Class B operation and Class A operation. Modules are disabled
from the highest address and work downward. If two modules
are disabled, the lowest four addresses will be functional, while
the highest two will be disabled. For example, in Class B opera-
tion, if the shunt for Address Disable is placed on “two” and the
base switch is set to 28, the modules will be assigned to 28, 29,
30 and 31 while disabling the highest two positions.
NOTE: Place unused shunts on single pin to store on board for
future use.
NOTE: Power must not be applied to the unit when changing
functionality on the shunts.
WIRING NOTES
Power-limited circuits must employ type FPL, FPLR, or FPLP
cable as required by Article 760 of the NEC.
All wiring must be in accordance with the NEC, NFPA 72 and
all other applicable codes and standards. All external power
supplies must be power limited with battery back-up. All ex-
ternal power supplies and detectors must be UL listed for fire
protection signaling applications.
PROGRAMMING
The XP6-MA module operates with the following Fire Alarm
Control Panels:
• AM2020/AFP1010 • System 5000 with AIM-200
• AFP-200 • AFC-600
• AFP-300/AFP-400 • NFS-640 (ONYX™ Series System)
• NFS-3030
The modules are programmed as devices in each system according
to the programming instructions in the appropriate FACP manual.
•
•
N500-80-00 3 I56-1806-006
Step 1: Insert the bottom of the XP6-MA module down into a
rear slot on the chassis.
Step 2: Carefully swing the upper edge of the board back
towards the back of the chassis until it touches
the two standoffs.
Step 3: Align two 4-40 screws with the two standoffs and tighten.
Step 4: Address and wire the modules according to the instruc-
tions in this manual.
The steps in Figures 6a and 6b describe and illustrate module in-
stallation when the rear chassis position and the position in front
of it will be filled. Front position installation is possible only if
the rear position is filled with an XP module.
Figure 6a. Installation of XP6-MA module in a rear
chassis position, method two:
1
C0225-00
Step 1: Insert the bottom edge of the XP6-MA module down into
a rear slot of the chassis.
Step 2: Carefully swing the upper edge of the board towards the
back of the chassis until it touches the short standoff
attached to the chassis.
Step 3: Align the long standoff with the short standoff and tighten.
Figure 6b. Installation of XP6-MA module in front
chassis position:
2
3
1
C0226-00
Step 1: Insert the bottom edge of the XP6-MA module down
into a front slot of the chassis.
Step 2: Carefully swing the upper edge of the board
towards the back of the chassis until it touches the 1
1/4”
(31.75mm) standoffs installed on the rear module.
Step 3: Align two 4-40 screws with the two standoffs and tighten.
Step 4: Address and wire the modules according to the
instructions in this manual.
WIRING
NOTE: All wiring must conform to applicable local codes,
ordinances, and regulations.
1. Install module wiring in accordance with the job drawings and
appropriate wiring diagrams.
2. All wiring to the XP6-MA is done via terminal blocks. In order
to properly make electrical connections strip approximately
TENS
0
78
6
5
4
3
21
910
11
12
13
14
15
Figure 7.
C0227-00

0
1
2
3
456789
BASE ADDRESS
TO NEXT DEVICE
–
STATUS
INDICATORS
—
+
—
+
+0
+1
IDC
ADDRESS
—
+
—
+
+2
+3
IDC
ADDRESS
—
+
—
+
+4
+5
IDC
ADDRESS
SLC
—
+
—
+
+
–
+
FROM PANEL OR
PREVIOUS DEVICE
3.9K EOL
RESISTOR
(INCLUDED)
CONNECT MODULES TO
LISTED COMPATIBLE
NOTIFIER CONTROL
PANELS ONLY
SIGNAL LINE CIRCUIT 32 VDC MAX.
SEE PANEL INSTRUCTION MANUAL
FOR WIRE REQUIREMENTS.
CLASS B IDC (TYPICAL)
A/B SELECT
A/B SELECT
DISABLE 1
DISABLE 2
+
–
+
–
T6 T5
DETECTORS MUST BE UL LISTED COMPATIBLE WITH THE MODULE.
INSTALL DETECTORS PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.
(–)
(+)
IN
OUT
—
+
—
+
EXTERNAL SUPPLY
0
1
2
3
456789
POWER-LIMITED
AND SUPERVISED
POWER TO THE NEXT INTERFACE
MODULE MUST BE EXTERNALLY
SWITCHED TO RESET THE DETECTORS.
AN FRM-1 RELAY CONTROL MODULE CAN BE
USED TO SWITCH POWER FROM A
STANDARD POWER SUPPLY. SEE FIGUR 10.
1. To use a common power supply between multiple XP6-MA
modules, connect a long power supply jumper from T5 or T6
to T5 or T6 on the adjacent XP6-MA module.
1. To select Class A, remove the two shunts from the
“A/B select” positions.
2. To use a common power supply between multiple XP6-MA
modules, connect a long power supply jumper from T5 or T6
to T5 or T6 on the adjacent XP6-MA module.
0
1
2
3
456789
BASE ADDRESS
TO NEXT DEVICE
–
STATUS
INDICATORS
—
+
—
+
+0
+1
IDC
ADDRESS
—
+
—
+
+2
+3
IDC
ADDRESS
—
+
—
+
+4
+5
IDC
ADDRESS
SLC
—
+
—
+
+
–
+
FROM PANEL OR
PREVIOUS DEVICE
CONNECT MODULES TO LISTED COMPATIBLE
NOTIFIER CONTROL PANELS ONLY
SIGNAL LINE CIRCUIT 32 VDC MAX.
SEE PANEL INSTRUCTION MANUAL
FOR WIRE REQUIREMENTS.
CLASS A IDC (TYPICAL)
A/B SELECT
A/B SELECT
DISABLE 1
DISABLE 2
0
1
2
3
45678910
11
12
13
14
15
++
IDC 2
IDC 3
(–)
(+)
POWER TO THE NEXT INTERFACE
MODULE MUST BE EXTERNALLY
SWITCHED TO RESET THE DETECTORS.
AN FRM-1 RELAY CONTROL MODULE CAN BE
USED TO SWITCH POWER FROM A
STANDARD POWER SUPPLY. SEE FIGURE 10.
T6 T5
IN
OUT
—
+
—
+
EXTERNAL SUPPLY
POWER-LIMITED
AND SUPERVISED
––
Figure 8. Interface two-wire conventional detectors – Class B, Style B:
Figure 9. Interface two-wire conventional detectors – Class A, Style D:
N500-80-00 4 I56-1806-006
Detectors must be UL Listed compatible with the module. Install detectors
per manufacturer’s installation instructions.
C0154-02
C0160-01

Figure 10. Relay control module used to disconnect a power supply:
N500-80-00 5 I56-1806-006
©2006 Notifier
9
8
7
6
54
3
2
1
0
ADDRESS
LOOP
RELAY
CONTROL
MODULE
(+)
(–)
FROM
PANEL OR
PREVIOUS
DEVICE
(+)
(–)
POWER LIMITED
DC POWER SUPPLY,
LISTED FOR FIRE
PROTECTION
WITH BATTERY
BACKUP
(+)
(–)
TO NEXT
(+)
(–)
DEVICE
CONNECT MODULES
TO LISTED COMPATIBLE
CONTROL PANELS ONLY.
TWISTED PAIR
IS RECOMMENDED
(+)
(–)
COMMUNICATION LINE
32 VDC MAX.
C0248-00
C0142-00
—
+
—
+
+0
+1
IDC
ADDRESS
—
+
—
+
+2
+3
IDC
ADDRESS
—
+
—
+
+4
+5
IDC
ADDRESS
SLC
—
+
—
+
A/B SELECT
A/B SELECT
DISABLE 1
DISABLE 2
T6 T5
—
+
—
+
+0
+1
IDC
ADDRESS
—
+
—
+
+2
+3
IDC
ADDRESS
—
+
—
+
+4
+5
IDC
ADDRESS
SLC
—
+
—
+
A/B SELECT
A/B SELECT
DISABLE 1
DISABLE 2
T6 T5
IN
OUT
—
+
—
+
EXTERNAL SUPPLY
IN
OUT
—
+
—
+
EXTERNAL SUPPLY
EXTERNAL
POWER
SUPPLY
—
+
PCB 1
PCB 2
VIEW A-A
0
1
2
3
456789
BASE ADDRESS
0
1
2
3
45678910
11
12
13
14
15
0
1
2
3
456789
BASE ADDRESS
0
1
2
3
45678910
11
12
13
14
15
Figure 11. Example of multiple boards sharing same external supply. Refer to figures 8 and 9 for typical wir-
ing. Make certain lip on long power supply jumper engages retaining tab on T5 or T6 as shown in View A-A:
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this
device must accept any interference received, including interference that may cause undesired operation.
Note: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to
provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not
installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not
occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off
and on, the user is encouraged to try to correct the interference by one or more of the following measures:
– Reorient or relocate the receiving antenna.
– Increase the separation between the equipment and receiver.
– Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
– Consult the dealer or an experienced radio/TV technician for help.
FCC Statement

Table of contents
Other Notifier Control Unit manuals

Notifier
Notifier FZM-1 User manual

Notifier
Notifier IDR-MD User manual

Notifier
Notifier FDM-1 User manual

Notifier
Notifier FMM-1 FlashScan User manual

Notifier
Notifier TM-4 Technical manual

Notifier
Notifier XP6-R User manual

Notifier
Notifier NAM-232 User manual

Notifier
Notifier FDM-1 User manual

Notifier
Notifier XP10-M User manual

Notifier
Notifier LDM-32 Assembly instructions
Popular Control Unit manuals by other brands

Victaulic
Victaulic Vic-300 MasterSeal 761 Series Installation and maintenance instructions

BFT
BFT Sirio TN1 Installation and user manual

TYAN
TYAN FT77D-B7109 Service engineer's manual

Elektrogas
Elektrogas VML Series Technical manual

Tektronix
Tektronix 80A05 user manual

enervent
enervent eWind User instructions