Installation and Maintenance XS Roof Fan Kits 50/60Hz
6.1.4 Supply / Extract Fan Operated via remote XS-MFC Control
6.1.5 Supply / Extract Fan Operated via remote XS-MFC Control
and Remote Sensor(s)
6.1.6 Supply / Extract Fan Operated via remote XS-MFC Control
and an Integral Sensor
Remote switch may be set: On/Off, Forward/Reverse, Economy/Std.
(variable speed), Auto/Manual.
Remote switch may be set: On/Off, Forward/Reverse, Economy/Std.
(variable speed), Auto/Manual.
One or more Remote Sensors may be wired in parallel to one XS-MFC
Control.
Humidity Sensor: XS-HR
Air Quality Sensor: XS-AQR
Passive Infra-Red Sensor: XS-PIRR
Remote switch may be set: On/Off, Forward/Reverse, Economy/Std.
(variable speed), Auto/Manual.
Maximum one Integral Sensor per fan, 6/9/12 denotes unit size identity.
Humidity Sensor: XS-H6/9/12
Air Quality Sensor: XS-AQ6/9/12
Passive Infra Red Sensor: XS-PIR6/9/12
Temperature Sensor: XS-TH6/9/12
Run on Timer: XS-TA6/9/12.
A single sensor will switch all fans if more than one fan is being
operated by a single XS-MFC controller.
NOTE: Multi-fan options:
Up to 5 fans (size 6"/9") can be controlled by one XS-MFC.
Up to 2 fans (size 12") can be controlled by one XS-MFC.
Do not mix different fan sizes on the same controller.
XS-MFC controller
L5
L4
L3
L2
L1
N
L4
L3
L2
L1
N
L1
N
Double
pole
isolator
Fuse
max.
3 amp
L
N
XS Fan unit
mains
supply
XS-MFC controller
L5
L4
L3
L2
L1
N
L4
L3
L2
L1
N
L1
N
Double
pole
isolator max.
Fuse
3 amp
L
N
XS Fan unit
Remote sensor
mains
L2 L1 N
supply
XS-MFC controller
L5
L4
L3
L2
L1
N
L4
L3
L2
L1
N
L1
N
Double
pole
isolator
Fuse
max.
3 amp
L
N
XS Fan unit with
integral sensor
Required if using
integral Timer
mains
supply
Model
Input Power
(W) Weight
(kg)
Max. Economy
XS6FR supply & extract 38 20 6.3
XS6PR supply & extract 38 20 6.3
XS9FR supply & extract 50 37 8.7
XS9PR supply & extract 50 37 9.1
XS12FR supply & extract 100 70 11.0
XS12PR supply & extract 100 70 11.8
6.2 Unit Consumption & Weight
6.3 Electrical Specification
230V ~ 50Hz / 220V ~ 60Hz Class I. Motor thermally protected by
overload device. Cable: 1mm max. or min. Fuse: 3 amp (if fan is supplied
from a 5A lighting circuit, no local fuse is required).
Note: If 2 x 12 inch fans or 3 x 6 or 9 inch fans are used in the same
operating mode in the same room they should all be controlled from
the same MFC speed control. This avoids the possibility of one fan (if
speed controlled at a lower flow rate) being stalled by the other fan(s).
Adequate make-up air provision sufficient to provide ventilation in
accordance with building regulations is required in all rooms. This
should be checked during commissioning with all fans in the same room
running together in all possible configurations.
The automatic shutters, motor bearings should be frequently inspected
and maintained to ensure they open fully/operate satisfactorily. Use
of an RCD and fused spur with 1A, Bussmann TDC180, BS1362, fuse
(Farnell order no: 1123029) for 1 fan or 2A, Bussmann TDC180, BS1362
fuse (Farnell order no: 1123032) for 2 or 3 fans is recommended.
Always confirm airflow direction before commissioning.
Note figures are for extract only at 50hz.