
Page 5
Cause: Problem with contacts on main contactor or circuit breaker.
Solution: Verify all three phases are on the load terminals of the contactor and
breaker. Replace contactor/breaker if required.
Cause: Phase imbalance or loss of one of the incoming three phase lines.
Solution: Correct the phase imbalance/loss problem.
•Fan Current Fault: Activated if the IGBT heatsink fan current is less than .5 amp
or greater than 1.5 amp for 480 VAC fans and less than 1 amp or greater than 4
amp for 120 VAC fans (used on 21 kW and smaller units). If the tank fan
experiences a current fault, the alarm will be annunciated, but the unit will not
trip. The control will monitor the fluid temperature and go into a Temperature
Limit or Overtemp trip condition.
Cause: Problem with contacts on fan contactor
Solution: Verify all three phases are on the load terminals of the fan contactor.
Replace contactor if required.
Cause: Open or short circuit of the fan motor winding.
Solution: The winding of the fan motor are thermally protected with an internal
temperature cutout. If the motor is hot, allow it to cool and see if it can
be re-energized. If not replace motor. If it can be re-energized,
determine cause of overheating.
•Main Contactor Fault: Activated if the main contactor fails to energize based on
the status of the auxiliary contact. Since this alarm may have been caused by a
low incoming line voltage, the PowerPlus will continue to monitor the line
voltage for an additional 10 seconds after it trips. If the line voltage returns to
within the acceptable range listed above, the unit will automatically re-energize
the high voltage. If it again experiences the V Bus Low condition during ramp
up, or if a second alarm occurs within 5 minutes, the unit will trip and stay off
until the alarm is manually cleared.
Cause: Main contactor not energizing.
Solution: Check for 120 VAC at contactor coil. Check the small cylindrical fuse,
F2, located on the D25166-01 I/O board of the control module. Verify
that 120 VAC is present at the Aux. Main input on the control board.
Repair any faulty connections or replace contactor or control board if
required.
•Step Start Contactor Fault: Activated if the step start contactor fails to energize
(based on the status of the auxiliary contact).
Cause: Step start contactor not energizing.
Solution: Check for 120 VAC at contactor coil. Check the small cylindrical fuse,
F1, located on the D25166-01 I/O board of the control module. Verify