K8AC-H
16
Burnout Alarm Set Value Setting Method
Setting Method
•Wire the K8AC-H, temperature controller (4 to 20 mA current output
type), and power regulator (phase control).
•Press the LKey on the K8AC-H for at least 3 s to change from
RUN mode to ADJ mode.
•AL-1 (CT1 burnout alarm set value) will be displayed when the
mode is changed to ADJ mode. Press the Skey once when AL-1
is displayed. Next, press the UKey once. The present heater
current value will be displayed on the main display, so note this as
the normal current value. Always have the temperature controller
output at 20.0 mA at this time. (See note 1.)
•Next, disconnect one heater and note the heater current in this
burnout state. Alternatively, use the current when one heater is
burned out (calculated earlier) as the current during malfunction. It
is recommended that the current at an actual burnout is confirmed.
•Set the K8AC-H burnout alarm set value based on the results. The
burnout alarm set value is set at the mid-point between the normal
current and the current at malfunction, taking errors and variations
in heater capacity into consideration.
•In this setting example, the set value for AL-2 (CT2 burnout alarm
setting) is the same as the set value for AL-1. (See note 2.)
Note: 1. The K8AC-H automatically adjusts burnout alarm setting
levels to compensate based on the temperature controller
current output. The burnout alarm set value must be set
when the temperature controller output is at 100% (20 mA),
so be sure to have the temperature controller at 20 mA
output.
2. If the heater capacity is unbalanced, the CT1 and CT2
burnout alarm levels may not be at the same value.
■Measurement Monitor Value Display Ranges and Functions
Other than measuring the heater current, the K8AC-H can measure the power supply voltage, maximum/minimum current, maximum/minimum
voltage, and other values. The measurement data can be monitored from a host using RS-485 communications. The measurement monitor value
names, display ranges, and functions are given in the following table.
Note: Each measurement monitor value can be individually reset. Refer to the K8AC-H Digital Heater Element Burnout Detector User’s Manual
(Cat. No. N132) for operating procedures.
Measurement monitor
value name
Display
characters
Display range Unit Function
Power supply voltage sce 0085 to 0264 V This is the K8AC-H control power supply voltage. When the voltage fluctuation
compensation function is enabled, the heater burnout determination based on this
voltage is automatically compensated.
Heater 1 maximum
current (See note.)
max1 0100 to 2300 A These hold the maximum and minimum values for each processing value.
•The maximum and minimum heater currents after the power is turned ON or
after a maximum or minimum reset are displayed.
•The values are not saved when power is interrupted.
•The current values are not refreshed when startup lock is in effect and when the
gate input is enabled but the gate input is OFF.
•Power supply voltages are always refreshed.
Heater 1 minimum current
(See note.)
min1 0100 to 2300 A
Heater 2 maximum
current (See note.)
max2 0100 to 2300 A
Heater 2 minimum current
(See note.)
min2 0100 to 2300 A
Maximum power supply
voltage (See note.)
maxs 0085 to 0264 V
Minimum power supply
voltage (See note.)
mins 0085 to 0264 V
Number of alarm outputs acnt 0000 to 9999 Outputs This value counts the total number of alarms output for heater burnout, SSR open
and short circuits, and heater overcurrent.
•The count is refreshed each time an alarm is output, and it is saved in non-
volatile memory.
•The value is saved when power is interrupted.
•The number of outputs is not counted for the test function.
Processing value for
alarm output
memo 0100 to 2300 A This holds the CT1 or CT2 processing value when a heater burnout alarm is output.
•This is the most recent processing value, and it is refreshed each time a heater
burnout alarm occurs.
•The value is not saved when power is interrupted.
Run time otim 0000 to 9999 × 10h This is the total run time value from when power is turned ON or the processing
value is reset until an alarm occurs.
•The total time is recorded in non-volatile memory approximately once per hour. If
power is interrupted within the hour, however, the data since the beginning of the
hour is lost and the total starts over from when the time was last saved.
•The total is stopped during heater burnout alarm output. When the alarm is
cleared, the total resumes from the time just before the alarm occurred.
Heater 1 input shift display
current
isc1 −999 to 999 A This is the shift value for displaying the CT1 heater current measurement set in
measurement parameter CT1.
•The value is saved when power is interrupted.
Heater 2 input shift display
current
isc2 −999 to 999 A This is the shift value for displaying the CT2 heater current measurement set in
measurement parameter CT2.
•The value is saved when power is interrupted.