Step1
Step2 Step2
CAUTION
CAUTION
Precautions for Safe Use
H5CC-A/AD
H5CC-A11S/A11SD
H5CC-L8S/L8SD H5CC-L8E/L8ED/L8EF
H5CC-L8/L8D
H5CC-AU/AUD H5CC-A11/A11D/A11F
H5CC-AS/ASD
*1 The set values for the time range are as follows:
Self-diagnostic Functions
Terminals 2 and 3 of the H5CC-A11F
are connected internally.
*: NPN output PNP output With Inductive Load
Conformance to EN/IEC Standards
H5CC
Digital Timer
OMRON Corporation
©All Rights Reserved
For details, refer to the latest datasheet (L220-E1).
SAFETY PRECAUTIONS
Keys to Warning Symbols
Indicates a potentially hazardous situation which, if not
avoided, is likely to result in minor or moderate injury or in
property damage.
Do not disassemble, modify, or repair the Timer or touch internal components.
Minor electric shock, fire, or malfunction may occasionally occur.
The life expectancy of the output relay varies considerably according to its
usage. Use the output relay within its rated load and electrical life expectancy.
If the output relay is used beyond its life expectancy, its contacts may become
fused or there may be a risk of fire. Also, be sure that the load current does not
exceed the rated load current and when using a heater, be sure to use a
thermal switch in the load circuit.
Do not touch any of the terminals while power is being supplied. Be sure to
mount the terminal cover after wiring. Minor injury due to electric shock may
occasionally occur.
Fire may occasionally occur. Tighten the terminal screws to the rated torque.
H5CC terminals and P3GA-11/P3G-08 Socket terminals: 6.55 to 7.97 lb-in (0.74
to 0.90 N·m)
P2CF Socket terminals: 4.4 lb-in (0.5 N·m)
Do not use the Timer where subject to flammable or explosive gas. Minor
injury due to explosion may occasionally occur.
Do not allow pieces of metal, wire clippings, or fine metallic shavings or fillings
from installation to enter the product. Doing so may occasionally result in
electric shock, fire, or malfunction.
4)
Use the Timer within the specified ranges for the ambient operating temperature and humidity.
5) Do not use or store the product in the following locations:
• Locations subject to sudden or extreme changes in temperature.
• Locations where high humidity may result in condensation.
• Locations with excessive vibration or shock.
• Locations subject to water.
• Locations subject to oil.
• Locations prone to icing.
• Locations subject to exposure chemicals.
• Locations subject to bugs and small animals.
6) Do not use this Timer in dusty environments, in locations where corrosive gasses are
present, or in locations subject to direct sunlight.
7) Install the Timer well away from any sources of static electricity, such as pipes
transporting molding materials, powders, or liquids.
8) Internal elements may be destroyed if a voltage outside the rated voltage range is applied.
9) Be sure that polarity is correct when wiring the terminals.
10) Separate the Timer from sources of noise, such as devices with input signals from power
lines carrying noise, and wiring for I/O signals.
11) Do not connect more than two crimp terminals to the same terminal.
12) Up to two wires of the same size and type can be inserted into a single terminals.
13) Use the specified wires for wiring.
Applicable Wires: AWG 18 to AWG 22, solid or twisted, copper
Wiring stripping length: 5 to 6 mm (recommended)
14) Install a switch or circuit breaker that allows the operator to immediately turn OFF the
power, and label it to clearly indicate its function.
15) When the Timer other than H5CC-A11F is operated with no-voltage input (NPN input),
approximately 14 V is output from the input terminals. Use a sensor that contains a diode.
16)
Use a switch, relay, or other contact so that the rated power supply voltage will be reached
within 0.1 second. If the power supply voltage is not reached quickly enough, the Timer may
malfunction or outputs may be unstable. Use a switch, relay, or other contact so that the
rated power supply voltage will be reached within 0.1 second. If the power supply voltage is
not reached quickly enough, the Timer may malfunction or outputs may be unstable.
17) Use a switch, relay, or other contact to turn the power supply OFF instantaneously.
Outputs may malfunction and memory errors may occur if the power supply voltage is
decreased gradually.
18) If the set value is changed as follows during a timing operation, the output will turn ON because
of the use of a constant read-in system:
Elapsed time (UP) mode: Present value ≥ Set value
Remaining time (DOWN) mode: Elapsed time ≥ Set value (The present value is set to 0.)
In the remaining time mode, the amount the set value is changed is added to or subtracted from
the present value.
The operation under the set value 0 depends on the set output mode.
19)
Do not use organic solvents (such as paint thinners or benzine), strong alkali, or strong acids.
20) Confirm that indications are working normally, including the backlight LEDs, and LCD. The
indicator LEDs, LCD, and resin parts may deteriorate more quickly depending on the
application environment, preventing normal indications. Periodic inspection and
replacement are required.
21) The waterproof packing may deteriorate, shrink, or harden depending on the application
environment. Periodic inspection and replacement are required.
1) When mounting the Timer to a panel, tighten the two mounting screws alternately, a little
at a time, so as to keep them at an equal tightness. If the panel screws are tightened
unequally, water may enter the panel.
2) Store the Timer at the specified temperature. If the Timer has been stored at a
temperature of less than -10°C, allow the Timer to stand at room temperature for at least
3 hours before use.
3) Mounting the Timer side-by-side may reduce the life expectancies of internal components.
1) Read this manual carefully before using the product.
2) An inrush current of approx. 14 A will flow for a short time when the power supply
is turned ON. If the capacity of the power supply is not sufficient, the Timer may
not start. Be sure to use a power supply with sufficient capacity.
3) Make sure the power supply voltage and loads are within the specifications and
ratings for the product.
4) Take caution that signal reception is possible, impossible, or indefinite during the
following periods after power ON/OFF. To allow for the startup time of peripheral
devices (sensors, etc.), the Timer starts timing operation between 200 to 250 ms
after power is turned ON. For this reason, if the set value is 249 ms or less in
operations where timing starts from power ON, the time until output turns ON will
be a fixed value between 200 and 250. The present value display will start from
250 ms. (Normal operation is possible for set values of 250 ms or more.) In
applications where a set value of 249 ms or less is required, use start timing with
signal input.
5) No input signals will be accepted from 5 to 505 ms for H5CC-A/L8, from 5 to
105 ms for H5CC-A11F, and from 5 to 1005 ms for H5CC-AUafter the power is
turned OFF.
6) Inrush current generated by turning ON or OFF the power supply may deteriorate
contacts on the power supply circuit. Turn ON or OFF to a device with the rated
current of more than 14 A.
7) Make sure that all settings are appropriate for the application. Unexpected
operation resulting in property damage or accidents may occur if the settings are
not appropriate.
8) Do not leave the Timer for long periods at a high temperature with output current
in the ON state. Doing so may result in the premature deterioration of internal
components (e.g., electrolytic capacitors). Do not install the product close
contact with the heating element.
9) Non-volatile memory is used as backup memory when the power is interrupted.
The write life of the non-volatile memory is 100,000 writes. The non-volatile
memory is written when the power is turned OFF or when switching from function
setting mode or configuration selection mode to run mode.
10) Dispose of the product according to local ordinances as they apply.
11) Do not use because it may be damaged inside the product when the product fall
by mistake.
12) Confirm the wiring the input and output terminals correctly before power is
supplied.
13) Do not use the product near radio wave receivers. Doing so may cause incoming
radio wave interference.
14) Install product so that the load doesn't span the product body.
15) H5CC models with a 24 to 240 VAC/DC power supply use a transformer-free
power supply method in which the power supply terminals are not isolated from
the signal input terminals. In such cases, unwanted current paths may
occasionally burn or destroy internal components depending on the wiring.
Always check the wiring sufficiently before use.
16) Do not wire the terminals that are not used.
17) If there is a transformer or other device with a large inductance component on the
power supply line, the inductance will cause a reverse voltage. If that occurs,
insert a CR filter in the power supply line to reduce
the reverse voltage.
18) Do not use in a circuit with the waveform is
distorted. The error will increase due to the
influence of the distorted waveform.
19) The capacity of the external power supply is 100 mA
at 12 V. When using H5CC-AUD with the DC power
supply, however, reduce the load with the power
supply voltage, as shown in the diagram on the
right.
Precautions for Correct Use
Panel-cutout Dimensions
Diagram (Unit: mm)
Standard panel cutout is shown in the
following diagram. (conforms to DIN 43700)
A space of 15 mm or greater (a panel cut-out
distance of 60 mm or greater) is
recommended towards the Adapter's hook
side to enable easier mounting work.
1. The thickness of a mounting panel
should be 1 to 5 mm.
2. It is possible to mount Timers
side-by-side. (But only towards the
non-hook side.)
Mounting and Panel-cutout Dimensions Diagram
Mounting Dimensions (Unit: mm)
Front panel dimensions
are the same for all
models.
Flush Mounting
Surface Mounting
H5CC-A11/-L8
H5CC-A/AS/AU
3. If the products are mounted side by
side, water resistance will be lost.
Package Contents
• Digital Timer
• Instruction manual (this document)
• Mounting Adapter, Waterproof
Packing, Terminal Cover (except
H5CC-A11/L8)
Ratings (Specifications)
Power supply voltage 100 to 240 VAC, 50/60 Hz
12 to 48 VDC/24 VAC, 50/60 Hz
24 to 240 VDC/24 to 240 VAC, 50/60 Hz
Allowable voltage fluctuation range
85% to 110% of rated supply voltage (12 to 48
VDC: 90% to 110%)
Power consumption Approx. 6.5 VA at 100 to 240 VAC
Approx. 5.4 VA/3.2 W at 24 VAC/12 to 48 VDC
Approx. 5.6 VA/2.7 W at 24 to 240 VAC/24 to 240
VDC
Operating temperature range -10 to 55°C (-10 to 50°C if Timers are mounted
side by side) (with no icing or condensation)
Storage temperature range -25 to 70°C (with no icing or condensation)
Operating humidity range 25% to 85%
Altitude 2,000 m max.
Recommended fuse
Relay output: 0216005, Transistor output:0216.100
Weight Approx. 115 g (main unit only)
Installation environment Over-voltage category Ⅲ, pollution degree 2,
indoor use only (IEC 61812-1)
Input method
No-voltage input ON impedance: 1 kΩmax. (Leakage current: 12
mA when 0 Ω),
ON residual voltage: 3 V max., OFF impedance:
100 kΩmin.
Voltage input High (logic) level: 4.5 to 30 VDC, Low (logic) level:
0 to 2 VDC (Input resistance: approx. 4.7 kΩ)
No-voltage (NPN) input/voltage (PNP) input
(switchable) (H5CC-A11F/H5CC-L8□supports
no-voltage input only)
Control output
Contact output 250 VAC/30 VDC 5A (resistive load)
Solid state output Open collector 30 VDC max., 100 mA max.
Residual voltage 1.5 VDC max. (Effective value:
Approx. 1 VDC)
Leakage current 0.1 mA max.
Electrical life of relay 100,000 operations (at an ambient temperature
of 23°C)
Mechanical life of relay 10,000,000 operations (at an ambient
temperature of 23°C)
External power supply 12 VDC 100 mA (H5CC-AU□only)
Degree of protection IEC IP66
* Individual mounting: Degree of protection on the front panel of the Timer
conforms when all of the following conditions are satisfied:
• The Y92S-P6 waterproof packing and Y92F-30 mounting adapter are used with
the Timer. Use only these parts for replacement.
Terminal Arrangement
• Wire properly after checking the specifications of the power supply voltage.
• Do not wire the terminals that are not used.
Nomenclature
Operating Procedures
Change from RUN Mode to Function Setting Mode.
Set the parameters using the UP Key or
DOWN Key.
The characters displayed in reverse video are the default
settings.
Press UP1+UP3 keys once to move to the previous parameter.
Press DW1+DW3 keys once to move to the next parameter.
Change from RUN Mode to Function Setting Mode.
Display in RUN mode
(other than Z mode).
Set the parameters using the UP Key or DOWN Key.
The characters displayed in reverse video are the default settings.
Press UP1+UP3 keys once to move to the previous parameter.
Press DW1+DW3 keys once to move to the next parameter.
Timer
Twin timer
Function
Display
tim
twn
Table 1 Configuration Selection
Mode Settings
Select the function from Table 1
using the UP1 or DW1 Key.
Operation as a Twin timerOperation as a Timer
*1 The set values for the time range are the same as for Timer operation.
* These dimensions vary with
the type of DIN track
(reference value).
• When conforming to EMC standards, refer to the information provided in this
Instruction Manual for cable selection and other conditions.
• This is a class A product. In residential areas it may cause radio interference, in which
case the user may be required to take adequate measures to reduce interference.
• Basic insulation is provided between power supply and input terminals. (There is no
insulation between power supply and input terminals for H5CC-A11.) Basic insulation
is provided between power supply and output terminals and between input and
output terminals.
• Basic insulation is provided between power supply and output terminals, and between
input and output terminals. When double insulation or reinforced insulation is
required, apply double insulation or reinforced insulation as defined in IEC 60664 that
is suitable for the maximum operating voltage with clearances or solid insulation.
• Connect the input and output terminals to devices that do not have any exposed
charged parts.
Note: Refer to the datasheet for detailed parameter settings. Note: Refer to the datasheet for detailed parameter settings.
Precautions for Compliance with
UL Standards and CSA Standards
No-voltage Inputs (NPN Inputs)
Input Connections
Voltage Inputs (PNP Inputs)
Open Collector
No-contact Input (NPN Transistor) No-contact Input (PNP Transistor)
Contact Input
Voltage Output Contact Input
SUITABILITY FOR USE
Power ON Function setting mode
Run mode
UP1+UP3 or DW1+DW3
(2 s min.)
UP1+UP3 or DW1+DW3
(2 s min.)
timr
timm
outm
otim
iflt
imod
otmd
sl-h
kypt
ot1i
ot2i
indc
on1a
on2a
on1c
on2c
ot-a
ot-c
ver
ot-i
indc
on-a
on-c
ot-a
ot-c
ver
Time range
UP/DOWN mode
Output mode
Output time
Input signal width
NPN/PNP input mode
Instantaneous/time-limit
Set value upper limit
Key protect level
Output 1 inversion
Output 2 inversion
Indicator display mode
Output 1 (OUT1) ON count alarm set value
Output 2 (OUT2) ON count alarm set value
Output 1 (OUT1) ON count monitor value
Output 2 (OUT2) ON count monitor value
Total run time alarm set value
Total run time monitor value
Software version
Output inversion
Indicator display mode
Output ON count alarm set value
Output ON count monitor value
Total run time alarm set value
Total run time monitor value
Software version
-
-
Only modes a-2, b, e, and zcan be selected for H5CC-L8E.
(If the output time is set to 0.00, hold is displayed.)
Displayed for modes a, a-1, a-2, a-3, b, b-1 and sonly. Unit: second
Displayed only for models other than H5CC-L8E□and H5CC-A11F.
Displayed only for models other than H5CC-L8□and H5CC-A11F.
Displayed only for the H5CC-L8E.
-
-
-
-
-
×1,000
×1,000
The monitor value is only displayed. It cannot be set. ×1,000
The monitor value is only displayed. It cannot be set. ×1,000
Unit: year
The Total run time monitor value is only displayed. It cannot be set.
The software version is only displayed. It cannot be set.
-
-
×1,000
The monitor value is only displayed. It cannot be set. ×1,000
Unit: year
The Total run time monitor value is only displayed. It cannot be set.
The software version is only displayed. It cannot be set.
※1
up, down
a, a-1, a-2, a-3, b, b-1, b-5, c, d, e, f, g, h, z, s
hold /0.01 ~99.99
20ms, 1ms
npn, pnp
1c1c, 2c
1~999999
kp-1, kp-2, kp-3, kp-4, kp-5, kp-6, kp-7
n-o, n-c
n-o, n-c
on, alof, allt
0~100 ~9999
0~100 ~9999
-
-
0.0 ~10.0 ~99.9
-
-
n-o, n-c
on, alof, allt
0~100 ~9999
-
0.0 ~10.0 ~99.9
-
-
Thank you for purchasing the OMRON Product.
To ensure the safe application of the Product, read this
manual carefully before using the Product and always
keep it close at hand when the Product is in use.
3616492-6 (Side-A)
H5CC-AU□and H5CC-L8E□
Models Other Than H5CC-AU□and H5CC-L8E□
Display Parameter name CommentsSet value
oftr
ontr
timm
totm
iflt
imod
otmd
sl1h
sl2h
OFF time range
ON time range
UP/DOWN mode
Twin Timer Output mode
Input signal width
NPN/PNP input mode
Instantaneous/time-limit
Set value upper limit 1
Set value upper limit 2
-
-
-
Only modes toff and ton can be selected for H5CC-L8E.
Displayed only for models other than H5CC-L8E□and H5CC-A11F.
Displayed only for models other than H5CC-L8□and H5CC-A11F.
Displayed only for the H5CC-L8E.
-
-
-
-
-
-
※1
※1
up, down
toff, ton, tof1, ton1
20ms, 1ms
npn, pnp
1c1c, 2c
1~999999
1~999999
kypt Key protect level kp-1, kp-2, kp-3, kp-4,
kp-5, kp-6, kp-7
ot1i
ot2i
indc
Output 1 inversion
Output 2 inversion
Indicator display mode
n-o, n-c
n-o, n-c
on, alof, allt
Unit: year
ot-a Total run time alarm set value 0.0 ~10.0 ~99.9
ot-c Total run time monitor
value -
ver Software version -
-
-
×1,000
The monitor value is only displayed. It cannot be set. ×1,000
Unit: year
ot-i
indc
on-a
on-c
ot-a
Output inversion
Indicator display mode
Output ON count alarm set value
Output ON count monitor value
Total run time alarm set value
n-o, n-c
on, alof, allt
0~100 ~9999
-
0.0 ~10.0 ~99.9
The software version is only displayed.
It cannot be set.
The software version is only displayed.
It cannot be set.
ver Software version -
The Total run time monitor value is only
displayed. It cannot be set.
The Total run time monitor value is only
displayed. It cannot be set.
ot-c Total run time monitor
value -
The monitor value is only displayed. It cannot be set.
×1,000
The monitor value is only displayed. It cannot be set.
×1,000
on1c Output 1 (OUT1)
ON count monitor value -
on2c Output 2 (OUT2)
ON count monitor value -
×1,000
on2a Output 2 (OUT2)
ON count alarm set value 0~100 ~9999
×1,000
on1a Output 1 (OUT1)
ON count alarm set value 0~100 ~9999
H5CC-AU□and H5CC-L8E□
Models Other Than H5CC-AU
□
and H5CC-L8E
□
Function setting mode
Display Parameter name CommentsSet value
Display in RUN mode. (Z mode)
Display in RUN mode.
Key-protect Switch Settings
* Changing mode to configuration selection mode or
function setting mode.
Level *Mode
change
Display switch
in the run mode
Reset
operation
UP/DOWN
Key
KP-1 (default setting)
KP-2
KP-3
KP-4
KP-5
KP-6
KP-7
Invalid
Invalid
Invalid
Invalid
Invalid
Invalid
Invalid
Valid
Valid
Valid
Valid
Invalid
Invalid
Invalid
Valid
Invalid
Valid
Invalid
Invalid
Valid
Invalid
Valid
Valid
Invalid
Invalid
Invalid
Valid
Valid
The following displays will appear if an error occurs.
e2 sum Memory error
(non-volatile memory) *1 OFF Reset operation Factory
setting
Rplc
*3 No
change
Total run time or Output
ON count has reached
the maintenance forecast.
No
change Reset operation *2 No change
e2 Not lit Memory error (RAM) OFF Turn ON the power
again. No change
e1 Not lit CPU error OFF Either perform Reset
operation or reset
the power supply. No change
Main
display
Sub-
display Description Output
status Correctionmethod Set value
after reset
INSTRUCTION MANUAL
EN
9. DOWN Keys (DW1 to DW6) (DW 1, 2, 3, 4, 5 and 6 from right to left)
10. Reset operation (UP6+DW6)
1.
Press RST keys (UP6+DW6) simultaneously for at least one second.
2.
LED on each key starts blinking. If not blink, that because the keys are not pressed
simultaneously. In this case, release the keys after pressing for at least 1 second,
and restart from 1. Do not release the keys until the LED starts blinking. Otherwise
the setting value may change.
3.
Press and hold until the LED turns off. If you release the keys while blinking, the
reset operation will be interrupted.
11. Mode operation (UP1+UP3 or DW1+DW3)
<Change of setting item>
1.
Press MODE keys (UP1+UP3 or DW1+DW3) simultaneously to switch setting items.
<Move to Function Setting Mode>
1.
Press MODE key (UP1+UP3 or DW1+DW3) for at least 2 seconds simultaneously.
2.
LEDs on UP1 (DW1) and UP3 (DW3) key start blinking. If not blink, that because the
keys are not pressed simultaneously. In this case, release the keys after pressing
for at least one second, and restart from 1. Do not release the keys until the LEDs
start blinking. Otherwise the setting value may change.
3.
Press and hold until the LED turns off. If you release the keys during blinking, the
mode will not be moved to Function Setting Mode.
12. Status indicator
<When Run mode is selected.>
• When the indicator display mode is on, the LED indicator shows the percentage of
the present value from 0 to 100%.
• When the indicator display mode is all off or all lit, the LEDs are all off or all lit.
Note: When you press the UP key or the DOWN key, the indicator display or all-lit
display goes off, and the LED indicator of the pressed key lights up or blinks.
<When Function Setting Mode is selected>
• The LED indicators at the settable key positions will light.
Omron Companies shall not be responsible for conformity with any standards, codes
or regulations which apply to the combination of the Product in the Buyer's
application or use of the Product. At Buyer's request, Omron will provide applicable
third party certification documents identifying ratings and limitations of use which
apply to the Product. This information by itself is not sufficient for a complete
determination of the suitability of the Product in combination with the end product,
machine, system, or other application or use. Buyer shall be solely responsible for
determining appropriateness of the particular Product with respect to Buyer's
application, product or system. Buyer shall take application responsibility in all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS
RISK TO LIFE OR PROPERTY OR IN LARGE QUANTITIES WITHOUT
ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO
ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT(S) IS PROPERLY
RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL
EQUIPMENT OR SYSTEM.
The H5CC is a Timer that contains more than
one functional timer. Use the following chart to
enter configuration selection mode and then
refer to Table 1 and set the functions that are
suitable to the application.
Function setting mode
When the key-protect switch is ON,
ON (enable) individual key
operations can be disabled to
prevent setting errors according to
the key protect levels (KP-1 to
KP-7) shown in the following table.
Note: Key protect levels are set in
function setting mode.
*1. This includes times when the life of the
non-volatile memory has expired.
*2. This is displayed if the alarm set value for either
of the two outputs is exceeded if a model with
two outputs is used. The total ON count will not
be cleared by using Reset operation.
*3. The normal display and Rplc will appear
alternately. When Reset operation is performed,
Rplc will no longer be displayed even if the alarm
set value is exceeded. (Monitoring is possible,
however, because the Timer will continue without
clearing the total run time and the output ON
count.) If the power supply is turned OFF/ON
after the Rplc display is turned OFF by Reset
operation, Rplc will be displayed again. In order
to prevent the display even after the power supply
is turned OFF/ON, change the alarm set value to
equal to or greater than the count value, or
change the alarm set value to 0 to be invalid.
Display Section
1. Key Protect Indicator (yellow)
2. Control Output Indicator (yellow)
3. Reset Indicator (yellow) (Lit when the reset input or
Reset operation is ON.)
4. Present Value Display (Main Display) Character
height: 10 mm (white)
5. Time Unit Indicators (green) (If the time range is 0
min, 0.0 min, 0 h, 0.0 h, or 0 h 0 min, these indicators
flash to indicate timing operation.)
6. Set Value Display (Sub-display) Character height: 6
mm (green)
7. Set Value 1, 2 Indicator (green)
Operation Key
8. UP Keys (UP1 to UP6)
(UP 1, 2, 3, 4, 5 and 6 from right to left)
Power
ON Function
setting mode
Run
mode
UP1+UP3 or DW1+DW3
(2 s min.)
UP1+UP3 or DW1+DW3
(2 s min.)
* Each time the UP1+UP3 or DW1+DW3 Key are
pressed, the set value display (6) will switch
between OFF Set value and ON Set value.
* Each time the UP1+UP3 or DW1+DW3 Key are
pressed, the set value display (6) will switch
between ON duty and Cycle time.
Display Set value
----.-- s0.01s~9999.99s (default setting)
-----.- s0.1s~99999.9s
------ s1s~999999s
--:--:-- hms 0h0min01s~99h59min59s
-----.- m0.1min~99999.9min
------ m1min~999999min
----:-- hm 0h01min~9999h59min
-----.- h0.1h~99999.9h
------ h1h~999999h
---.--- s0.001s~999.999s
The diode connected to
the collector of the
output transistor is used
to absorb inverted
voltage that is generated
when an inductive load is
connected to the H5CC.
Notice to Users of the H5CC in the USA and Canada
Please use the following installation information instead of the general information in
the instruction manuals in order to use the product under certified conditions of UL and
CSA when the product is installed in the USA or Canada. These conditions are required
by NFPA 70, National Electrical Code in the USA and the Canadian Electrical Code, Part
I in Canada and may vary from information given in the product manuals or safety
precautions.
• Installation in a Panel
H5CC is normally installed on a flat surface in an operation panel. Use a Type 1
Enclosure for the operation panel.
• Environment
Surrounding Air Temperature: -10 to 40°C
• Accessories (Order Separately)
11-pin
11-pin, finger-safe type
8-pin
8-pin, finger-safe type
P2CF-11
P2CF-11-E
P2CF-08
P2CF-08-E
Track Mounting/
Front Connecting
Socket
0
20
10.8 15
100
Load
current
(mA)
Power supply voltage (VDC)
100.9
103.2
*
P2CF-08 (-E)/ P2CF-11(-E)
(order separately)
Front-connecting Socket
H5CC-A11/L8
(48)
57.57.5
Panel
Y92F-30 (provided)
Flush Mounting Adapter
Y92S-P6 (provided)
Waterproof Packing
(48)
7.5 89.9
P3GA-11/P3G-08 (order separately)
Back-connecting Socket
Panel
Y92F-30 (order separately)
Flush Mounting Adapter
Y92S-P6 (order separately)
Waterproof Packing
A
A (48n 2.5) 1
0
58
48
15 or greater
60 or greater
□45+0.6
ー0
n Units mounted
side-by-side
Run mode
Power ON
func
tim
Configuration selection mode
UP1+UP6 or DW1+DW6 (2 s min.)
UP1+UP6 or DW1+DW6 (2 s min.)
67
8
9
10
11
1
2
3
4
5
(+)(-)
Reset
Signal
Gate
0 V
Unused
Unused
Internal circuit
Contact
output
67
8
9
10
11
1
2
3
4
5
(+)(-)
Reset
Signal
Gate
0 V
Unused
Unused
Internal circuit
Solid state
output*
4
3
2
1 8
7
6
5
(+)(-)
0 V
Internal circuit
Signal
Reset
Contact
output
4
3
2
1 8
7
6
5
(+)(-)
0 V
Unused
Internal circuit
Signal
Reset
Solid state
output*
4
3
2
1 8
7
6
5
(+)(-)
Internal circuit
Time-limit
contact output
OUT2
Internal circuit
Instantaneous
contact output
OUT1
Power for load
+
Load
Power for load
+
Load
Power for load
+
Timer
Inductive
load
Note: Operate with relay ON
Note: Operate with transistor ON
Note: Operate with transistor ON
Note: Operate with transistor OFF Note: Operate with relay ON
Note: Operate with transistor ON
Present value
Set Value
ON (enable)
OFF (disable)
(Factory setting)
Key protect
indicator
Present value
OFF Set value
Present value
ON Set value
12.34
10.00
12.34
18.50
Present value
ON duty
Present value
Cycle time
12.34
10
1234
2000
12.34
18.50
6789
Contact output
(+)(-)
0 V
12345
Reset
Signal
Gate
6 7 8 9
Solid state output*
(+)(-)
1 2 3 4 5
0 V
Reset
Signal
Gate
6 7 8 9
11
12 VDC
(-)
(+)
External
power supply
0 V
12345
Sensor
(+)(-)
Solid state
output*
Contact output
12 13
Reset
Signal
Gate
0 V
PLC,
Sensor
Reset
Signal
Gate
Sensor
Reset
Signal
Gate
0 V
Reset
Signal
Gate
0 V
Sensor
0 V
Reset
Signal
Gate
Sensor
0 V
Reset
Signal
Gate
0 V
Reset
Signal
Gate
* UP1+UP3 or
DW1+DW3
* UP1+UP3 or
DW1+DW3
H5CC TIMER
1
7
9
26
12
8
11
10
4
5
3
48
48
H5CC TIMER