manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Omron
  6. •
  7. Touch Terminal
  8. •
  9. Omron NS10-TV Series User manual

Omron NS10-TV Series User manual

Cat. No. V098-E1-05
Programmable Terminals
Host Connection Manual:
Host Link
NS15-TX_, NS12-TS_,
NS10-TV_, NS8-TV_,
NS5-SQ_, NS5-TQ_, NS5-MQ_
OPERATION MANUAL
1
Introduction
This manual describes the configuration and settings required for communicating with the
host devices used by NS-series Programmable Terminals for Host Link communications.
First familiarize yourself with the contents of the manuals related to NS-series
Programmable Terminals (the NS-series Setup Manual, NS-series Programming Manual,
and the CX-Designer online help), and then use this manual for Host Link communications.
2
1-1 Overview
This section provides an overview of connecting an NS-V1/V2 PT to an OMRON
Programmable Controller that supports Host Link communications.
The NS-V1/V2 PT is connected 1:1 to the CPU Unit or a Host Link Unit of an OMRON PLC.
Host Link communications are used to read and display or write the words and settings in the
host PLC.
NS-V1/V2 PT serial ports A and B can both be connected to a host by means of the Host
Link protocol.
Reference
When an NS-V1/V2 PT and a PLC are connected by
Host Link, it is not possible to change to RUN Mode.
If the PLC is set for RUN Mode, it is automatically
switched to Monitor Mode. For example, if a
compatible Programming Console is connected to
the PLC and the PLC operating mode is switched to
RUN mode, the password display for the Monitor
Mode will be displayed at the Programming Console.
3
1-2 Connection Configuration
This section describes the system configuration required for connecting to the host by Host
Link communications.
1-2-1 NS-V1/V2 Configuration Required for Connection
 NS-V1/V2 Models
One of the following NS-V1/V2 PTs is required to connect with the host by Host Link
communications.
Model
NS15-TX01@-V2
NS12-TS0@(B)-V1/-V2
NS10-TV0@(B)-V1/-V2
NS8-TV0@(B)-V1/-V2
NS8-TV1@(B)-V1
NS5-SQ@@ (B)-V1/-V2
NS5-TQ@@ (B)-V2
NS5-MQ@@ (B)-V2
Reference
NS-series PTs without the -V1 or -V2 suffix do not
support Host Link communications. One of the above
NS-V1/V2 models must be used.
 NS-V1/V2 System Program
To connect to the host by means of Host Link communications, system program version 6 or
later must be installed in the NS-V1/V2 PT.
System program
Ver. 6 or later
4
 Communications Ports
Communications
port
Applicable communications method
Serial port A Host Link
1:1 NT link
1:N NT link
Memory link
(Bar-code reader input)
(Temperature controller connection)
(CX-Designer connection)
Serial port B Host Link
1:1 NT link
1:N NT link
Memory link
(Bar-code reader input)
(Temperature controller connection)
(CX-Designer connection)
The following table shows the communications methods that can be used in combination
when serial ports A and B are used at the same time.
Serial port B
Host Link
1:1 NT Link
1:N NT Link
Memory link
Bar-code
reader
Temperature
controller
CX-Designer
connection
Host Link YES YES YES YES YES YES YES
1:1 NT link YES YES YES YES YES YES YES
1:N NT Link YES YES YES YES YES YES YES
Memory link YES YES YES No YES YES YES
Bar-code reader YES YES YES YES No YES YES
Temperature controller YES YES YES YES YES YES YES
Serial port A
CX-Designer connection YES YES YES YES YES YES No
5
 Communications Setup
The following table shows the communications settings required at the NS-V1/V2 PT and the
host to connect to the host by means of Host Link communications.
Setup
location
Settings (See note 2.)
NS-V1/V2 PT Baud rate: 9,600 or 19,200 bps (See note 1.)
Host Start bits: 1 bit
Data: 7 bits
Stop bits: 2 bits
Parity: Even
Host Link unit number: 0
Baud rate: 9,600 or 19,200 bps (See note 1.)
Note 1: The baud rate settings must be the same for both the NS-V1/V2 PT and the host.
2: Use the 1:N protocol setting.
1-2-2 Applicable PLCs
The OMRON PLCs listed below can be connected as hosts using Host Link communications.
The connection can be made either directly to the built-in serial port on the CPU Unit or to a
Host Link Unit mounted to the PLC.
C Series
C200HS, C200HX/HG/HE(-Z), CQM1, CQM1H, CPM2A/CPM2C, CPM1/CPM1A, C500,
C1000H, C2000H
CV Series
CV500, CV1000, CV2000, CVM1
CS/CJ Series
CS1G/CS1H, CS1G-H/CS1H-H, CJ1G, CJ1G-H/CJ1H-H, CJ1M, CP1H/CP1L, CJ2H,
CJ2M
6
1-3 Connecting to the Host
The types of host that can be connected to a PT by using the serial ports on the NS-series
PT and connecting to an RS-232C port at the host are described here.
1-3-1 Connecting to an RS-232C Port at the Host
 Compatible Host Units
Some models and series of OMRON PLCs have the host link function built in.
In the CS-series or CQM1H PLCs, the host link method can be used by installing a Serial
Communications Board. In addition, some C200HX/HG/HE(-Z)E have an integral CPU Unit
that can be connected in the host link method by installing a Communications Board.
Check the model and series of the PLC, the type of installed Serial Communications Board
or Serial Communications Unit before making a connection.
The PLC Units/Boards that can be connected to an NS-series PT through a Host Link
connection using RS-232C ports on both the PLC Unit/Board and PT are listed in the
following table.
PLC Series CPU Units with Built-in Host Link
Function
CPU Units Connectable with Host
Link Units or Expansion
Communications Board
Host Link Unit/
Communications
Board
CS1G-CPU42/43/44/45-EV1
CS1H-CPU63/64/65/66/67-EV1
CS1G-CPU42/43/44/45-EV1
CS1H-CPU63/64/65/66/67-EV1
CS Series
CS1G-CPU42H/43H/44H/45H
CS1H-CPU63H/64H/65H/66H/67H
CS1G-CPU42H/43H/44H/45H
CS1H-CPU63H/64H/65H/66H/67H
CS1W-SCU21-V1
CS1W-SCB21-V1
CS1W-SCB41-V1
CJ1G-CPU44/CPU45 CJ1G-CPU44/CPU45
CJ1G-CPU42H/43H/44H/45H
CJ1H-CPU65H/66H/67H
CJ1H-CPU65H/66H/67H-R
CJ2H-CPU64/65/66/67/68(-EIP)
CJ1G-CPU42H/43H/44H/45H
CJ1H-CPU65H/66H/67H
CJ1H-CPU65H/66H/67H-R
CJ2H-CPU64/65/66/67/68(-EIP)
CJ1M-CPU11/12/13/21/22/23
CJ2M-CPU11/12/13/14/15
CJ1M-CPU11/12/13/21/22/23
CJ2M-CPU11/12/13/14/15
/31/32/33/34/35
CJ1W-SCU21/41-V1
CP1H-XA40DR-A/XA40DT-D/XA40D
T1-D/X40DR-A/X40DT-D/X40DT1-D/
Y20DT-D
CJ Series
CP1L-L14DR-A/L14DR-D/L14DT-D/L
14DT1-D/L20DR-A/L20DR-D/L20DT-
D/L20DT1-D/M30DR-A/M30DR-D/M3
0DT-D/M30DT1-D/M40DR-A/M40DR-
D/M40DT-D/M40DT1-D
CP1W-CIF01
C1000H-CPU01-EV1
C2000H-CPU01-EV1
C120-LK201-EV1
C200HS-CPU01/03/21/23/31/33-E
C200HE-CPU11/32/42-E
C200HE-CPU11/32/42-ZE
C200HG-CPU33/43/53/63-E
C200HG-CPU33/43/53/63-ZE
C200HX-CPU34/44/54/64-E
C200HX-CPU34/44/54/64/65/85-ZE
C200H-LK201-EV1
C200HS-CPU21/22/31/33-E
C200HE-CPU42-E
C200HE-CPU42-ZE
C200HE-CPU32/42-E
C200HE-CPU32/42-ZE
C200HG-CPU43/63-E
C200HG-CPU43/63-ZE
C200HG-CPU33/43/53/63-E
C200HG-CPU33/43/53/63-ZE
C Series
C200HX-CPU44/64-E
C200HX-CPU44/64/65/85-ZE
C200HX-CPU34/44/54/64-E
C200HX-CPU34/44/54/64/65/85-ZE
C200HW-COM02/04/
05/06-EV1
7
PLC Series CPU Units with Built-in Host Link
Function
CPU Units Connectable with Host
Link Units or Expansion
Communications Board
Host Link Unit/
Communications
Board
C1000H-CPU01-EV1
C2000H-CPU01-EV1
C500-LK201-EV1
C1000H-CPU01-EV1
C1000HF-CPUA1-EV1
C2000H-CPU01-EV1
C500-LK203
CPM1-10/20/30CDR-@+CPM1-CIF01
CPM1A-10/20/30/40CD@-@+CPM1-
CIF01
CPM2A-30/40/60CD@@-@+CPM1-
CIF01 (Peripheral port connection)
CPM2C-10/20@@@@@@-@
(See note 1.)
CQM1-CPU21-E
CQM1-CPU41/42/43/44-EV1
C Series
CQM1H-CPU11/21/51/61 (See note 2.) CQM1H-CPU51/61 CQM1H-SCB41
CV500-CPU01-EV1 CV500-CPU01-EV1 CV500-LK201
CV1000-CPU01-EV1 CV1000-CPU01-EV1
CV Series
(See note 3.)
CV2000-CPU01-EV1 CV2000-CPU01-EV1
CVM1 Series
(See note 3.)
CVM1-CPU01-EV2
CVM1-CPU11-EV2
CVM1-CPU21-EV2
CVM1-CPU01-EV2
CVM1-CPU11-EV2
CVM1-CPU21-EV2
CV500-LK201
CompoBus/S
master control
unit
SRM1-C02-V2
Note 1: Use a CPM2C-CN111 or CS1W-CN114/118 Connecting Cable, CPM1-CIF01
RS-232C Adapter, or CPM1-CIF11 RS-422A Adapter to connect.
2: The CQM1H-CPU11 does not have a built-in RS-232C port, so connect to the
peripheral port to the PT with a CS1W-CN118 Connecting Cable.
3: CPU Units of CVM1/CV-series PLCs without the suffix –EV@cannot be connected.
 Settings at the Host
When using the host link method, the settings shown below must be made at the host
(depending on the unit, some of these settings may not be necessary, or settings not shown
here may be necessary).
Item Switch Setting
I/O port RS-232C
Communications speed Set the same baud rate as set at the NS-series PT (See note 1.)
Transfer code ASCII, 7 data bits, 2 stop bits
Parity Even
1-to-1/1-to-N 1-to-N (See note 2.)
Command level Level 1, 2, 3
Unit # 00
Note 1: Set the Host Link communications speed (baud rate) to 9600 bps or 19200 bps with
the Communications Setting menu item in the CX-Designer and the System Menu
for the NS-series PT. For details, refer to 1-4 Settings for Host Link.
2: The 1-to-N setting enables using a BCC (Block Check Character). It is not actually
possible to connect more than one NS-series PT in a single Host Link.
The setting methods for each type of unit are described in the following.
8
Connecting to a C-series Host Link Unit
C200H/C200HS/C200HE(-Z)E/C200HG(-Z)E/C200HX(-Z)E Rack-mounted type: C200H-LK201-V1
Setting the Front Switches
Set each switch with a flat blade screwdriver so that the values or symbols in the setting
value window agree with the following.
•Unit # (SW1, SW2)
Set these switches to 0.
•Command level, parity, and transfer code (SW4)
Set this switch to 2.
•Communications speed (SW3)
Set this switch to 5 to select 9600 bps.
Set this switch to 6 to select 19200 bps.
Setting the Rear Switches
•1-to-1/1-to-N selection (DIP switch)
Set #3 to ON.
•CTS selection (selector switch)
Set this always to 0 V (ON).
CTS selector switch
External
0 V (ON)
C1000H/C2000H Rack-mounted type: C500-LK201-EV1
Setting the Front Switches
•Mode control (key switch)
Set this to host link.
9
Setting the Rear Switches
•I/O port selection (selector switch)
Set this to RS-232C.
•Unit # (DIP SW1)
Set SW1-1 to SW1-5 to OFF (0).
•Synchronization (selector switch)
Set this to Internal.
•Communications speed
(DIP SW2-1 to SW2-4)
Set these switches to 0010 to select
19,200 bps.
Set these switches to 1010 to select
9,600 bps.
(0: OFF 1: ON)
•1-to-1/1-to-N selection (DIP SW2-6)
Set SW2-6 to OFF (0) (1-to-N).
•Command level (DIP SW2-7, SW2-8)
Set these switches to ON (1).
(
Levels 1
,
2
,
and 3 are enabled.
)
•CTS selection (selector switch)
Set this always to 0 V (ON).
I/O
p
ort
S
y
nchronization
Terminato
r
0 V
C1000H(F)/C2000H Rack-mounted type: C500-LK203
Setting the Rear Switches
•I/O port selection (selector switch)
Set this to RS-232C.
•Unit #, parity, and transfer code
(DIP SW1-1 to SW1-7)
Set SW1-1 to SW1-7 to OFF (0).
•Synchronization (selector switch)
Set this to Internal.
•Communications speed
(DIP SW2-1 to SW2-4)
Set these switches to 0010 to select
19,200 bps.
Set these switches to 1010 to select
9,600 bps.
(0: OFF 1: ON)
•1-to-1/1-to-N selection (DIP SW2-6)
Set SW2-6 to OFF (0) (1-to-N).
•Command level (DIP SW2-7, SW2-8)
Set these switches to ON (1).
(
Levels 1
,
2
,
and 3 are enabled.
)
•CTS selection (selector switch)
Set this always to 0 V (ON).
I/O
p
ort
S
y
nchronization
Terminator
5V su
pp
l
y
0
V
10
C200H/C1000H/C2000H CPU Unit-mounted Type: C120-LK201-EV
Setting the Rear Switches
•Unit #, parity, and transfer code
(DIP SW1-1 to SW1-5)
Set SW1-1 to SW1-5 to OFF (0).
* Parity is fixed at Even Parity. Transfer code
is fixed at ASCII 7 data bits and 2 stop bits.
•Communications speed (DIP SW2-1 to SW2-4)
Set these switches to 0010 to select 19200 bps.
Set these switches to 1010 to select 9600 bps.
(
0: OFF 1: ON
)
•1-to-1/1-to-N selection (DIP SW2-6)
Set SW2-6 to OFF (0) (1-to-N).
•Command level (DIP SW2-7, SW2-8)
Set these switches to ON (1).
(Levels 1, 2, and 3 are enabled.)
•CTS selection (DIP SW3-1 and SW3-2)
Set SW3-1 to ON (1), and SW3-2 to OFF (0).
(Set this always to 0V.)
•Synchronization (DIP SW3-3 to SW3-6)
Set SW3-3 and SW3-5 to ON (1), and
SW3-4 and SW3-6 to OFF (0). (Set these to Internal.)
Connecting to a CVM1/CV Series Host Link Unit
CVM1/CV-series Rack-mounted type: CV500-LK201
A CVM1/CV series host link unit (CV500-LK201) has two connectors (communications ports
1 and 2). Either of these ports can be used for connection to an NS-series PT by the
RS-232C method. However, since the connectors at these ports are of different types,
a cable that matches the connector must be prepared.
• Communications port 1
Communications port 1 is a 25-pin connector for RS-232C use only.
• Communications port 2
Communications port 2 is a 9-pin connector which allows selection of the RS-232C or
RS-422A method. When this port is used with the RS-232C method, the I/O port selector
switch on the front of the unit must be set to RS-232C (the upper position).
CPU Bus Unit Settings
When connecting to a CVM1/CV series host link unit, set the following communications
conditions for the CPU Bus Unit settings.
Item Setting at Host
Communications speed Set the same baud rate as set at the NS-series PT (See note 1.)
Transfer code ASCII, 7 data bits, 2 stop bits
Parity Even
Note 1: Set the Host Link communications speed (baud rate) to 9600 bps or 19200 bps with
the Communications Setting menu item in the CX-Designer and the System Menu
for the NS-series PT. For details, refer to 1-4 Settings for Host Link.
11
Set the CPU Bus Unit settings directly from a Programming Device (e.g. CX-Programmer).
For details on the CPU Bus Unit settings, refer to the SYSMAC CVM1/CV-series Host Link
Unit Operation Manual (W205-E1-@).
Setting The Front Switches
•Unit # (SW3, SW4)
When using communication port 2, set these
switches to 0.
•I/O port selection (selector switch)
Set this to RS-232C.
•CTS selection (DIP SW2 and SW3)
Set SW2 or SW3 to ON. (Set this always to 0V.)
To use communication port 1, set SW2. To use
communication port 2, set SW3.
•Communication condition setting (DIP SW1)
Set this switch to OFF.
Communication is executed in accordance with the
CPU bus unit system settings made at the PLC. The
initial values for the system settings are as follows.
- Communications speed: 9600 bps
- Parity: Even
- Xon/Xoff control: Not executed
- Communication method: Full duplex
- Stop bits: 2 stop bits
- Data length: 7 bits
Connecting to a CS-series Serial Communications Unit
CS-series Rack-mounted type: CS1W-SCU21(-V1)
Setting the Front Switches
Set the unit number of the Serial Communications Unit by using the rotary switch located on
the front panel. Set each switch with a flat blade screwdriver so that the values or symbols in
the setting value window agree with the following.
Set the unit number to 0 throu
g
h F so that it will
not overlap with the numbers used in other
units.
Allocation DM Area Settings in CPU Unit
Settings are written from the Programming Device (a Programming Console or
CX-Programmer) directly into the allocation DM area (system setting area) of the CPU Unit.
After the settings are written, they become effective by turning the power ON, restarting the
unit, restarting the communications port, or execution of the STUP command.
In the following, the words allocated in the DM area and the settings are shown.
12
m = DM 30000 + 100 × unit number (word address)
Allocation DM area word
Port 1 Port 2
Writing
Value
Settings
m m+10 8000 Host link mode, 2 stop bits, even parity, data length
7 bits
0000 Communications speed 9600 bps.m+1 m+11
0007 Communications speed 19200 bps.
m+2 m+12 0000 Transmit delay time 0 ms.
m+3 m+13 0000 No CTS control Unit No.0 for host link
Connecting to a CJ-series Serial Communications Unit
CJ-series Rack-mounted Type: CJ1W-SCU21/41-V1
Setting the Front Switches
Set the unit number for the Serial Communications Unit using the rotary switch on the front of
the Unit. Follow the procedure below use a flat-head screwdriver (−) to set the number and
sign in the setting display window.
Port 2 on the CJ1W-SCU41-V1 is an RS-232C port.
•Unit Number Setting
Set a number from 0 to
F that does not overlap
another unit.
•Port 1
RS-232C
•Port 2
RS-232C
CJ1W-SCU21-V1
•Unit Number Setting
Set a number from 0 to
F that does not overlap
another unit.
•Port 2
RS-232C
CJ1W-SCU41-V1
Setting CPU Unit Allocation DM Area Words
Settings can be directly written to the Allocation DM Area (System Setup Area) by using a
Programming Device, such as a Programming Console or the CX-Programmer. After the
settings are written, the settings will become valid by performing any of the following: turning
on the power supply again, restarting the Unit, restarting the communications port, or
executing a STUP instruction.
13
The following table shows words allocated in the DM Area and setting details.
m = D30000 + 100 ×unit number (word address)
Allocation DM area word
Port 1 Port 2
Writing Value Setting details
m m+10 8000 Host link mode, 2 stop bits, even parity,
7-bit data length
0000 Baud rate: 9,600 bpsm+1 m+11
0007 Baud rate: 19,200 bps
m+2 m+12 0000 Transmission delay time: 0 ms
m+3 m+13 0000 No CTS control, Unit number 0 for host
link
Connecting to a CPU Unit
CV-series and CVM1/CV-series (-EV@) CPU Units
CV500-CPU01-EV1/CV1000-CPU01-EV1/CV2000-CPU01-EV1
CVM1-CPU01-EV2/CVM1-CPU11-EV2/CVM1-CPU21-EV2
PLC Setup
When connecting to a CVM1/CV series CPU Unit, set the following communications
conditions for the PLC Setup.
Item Setting at Host
Communications speed Set the same baud rate as set at the NS-series PT (See note.)
Stop bit 2 stop bits
Parity Even
Data length ASCII 7 bits
Unit # 00
Note: Set the Host Link communications speed (baud rate) to 9600 bps or 19200 bps with
the Communications Setting menu item in the CX-Designer and the System Menu for
the NS-series PT. For details, refer to 1-4 Settings for Host Link.
Either set PLC Setup directly from a Programming Device (e.g. CX-Programmer), or transmit
the PLC Setup made at a Programming Device to the CPU UNIT.
For details on the PLC Setup, refer to the SYSMAC CVM1/CV500/1000/2000 Operation
Manual: Ladder Diagrams (W202-E1-@).
14
Setting the Front Switches
•I/O port selection (selector switch)
Set this to RS-232C.
I/O port selector switch
•System setting (DIP SW4)
To effect the existing DIP switch
settings, set SW4 to ON.
To effect the existing PC Setup, set
SW4 to OFF.
Note
For CPUs manufactured before or
during June 1995 (lot No. @@65), the
existin
g
DIP switch settin
g
s differ from
the existing PC Setup as follows.
- DIP switch settings:
2,400 bps, 1 stop bit, even parity, 7
bit data length
- PC Setup:
9,600 bps, 2 stop bits, even parity, 7
bit data length
For CPUs manufactured from July 1995
onward (lot No. @@75), the stipulated
values in the DIP switch settings also
are 9,600 bps and 2 stop bits.
C-series C200HS, C200HX/HG/HE(-Z)E, CPM1, CPM2A, CPM2C, CQM1, CQM1H CPU Units, SRM1
The connection method depends upon the model of PLC being used, as shown in the
following table.
PLC model Connection method
C200HS, CQM1 Connect to the CPU Unit’s built-in RS-232C port.
C200HX/HG/HE(-Z)E • Connect to the CPU Unit’s built-in RS-232C port.
• Connect to one of the RS-232C ports (port A or port B) on a Serial
Communications Board.
CQM1H • Connect to the CPU Unit’s built-in RS-232C port.
• Connect to the peripheral port through a CS1W-CN118
Connecting Cable.
• Connect to the RS-232C port (port 1) on a Serial Communications
Board.
CPM1 Connect to the peripheral port through a CPM1-CIF01
RS-232C Adapter.
CPM2A, SRM1 • Connect to the CPU Unit’s built-in RS-232C port.
• Connect to the peripheral port through a CPM1-CIF01 RS-232C
Adapter.
CPM2C Connect to the CPU Unit’s RS-232C port or the peripheral
port through a Connecting Cable (CPM2C-CN111,
CS1W-CN118, or CS1W-CN114).
(The CPM2C-CN111 splits the Unit’s communications port into
an RS-232C port and a peripheral port. A CPM1-CIF01
RS-232C Adapter is also required to connect to this peripheral
port.)
PLC Setup Area Settings
When connecting to a C200HS, C200HX/HG/HE(-Z)E, CPM1, CPM2A, CPM2C, CQM1, or
CQM1H CPU Unit, or SRM1, set the following communications conditions for the PLC Setup
area.
Item Setting at Host
Communications mode Host link mode
Communications speed Set the same baud rate as set at the NS-series PT (See note.)
Stop bit 2 stop bits
15
Item Setting at Host
Parity Even
Data length ASCII 7 bits
Unit # 00
Note: Set the Host Link communications speed (baud rate) to 9600 bps or 19200 bps with
the Communications Setting menu item in the CX-Designer and the System Menu for
the NS-series PT. For details, refer to 1-4 Settings for Host Link.
Set the PLC Setup area settings directly from a Programming Device (e.g. CX-Programmer).
For details on operations relating to the PLC Setup area, refer to the manual for the PLC
which is used.
The PLC Setup area word numbers and settings to be made depending on the unit and port
to which the connection is made are shown below.
CPM2A, CPM2C, CQM1H, or SRM1: Peripheral port connection
Word Writing Value Settings
DM6650 0001 Host link mode, no CTS control, communications conditions
set by the contents of DM
0303 Data length 7 bits, 2 stop bits, even parity, communications
speed: 9600 bps
DM6651
0304 Data length 7 bits, 2 stop bits, even parity, communications
speed: 19200 bps
DM6653 0000 Unit # 00
C200HS, C200HX/HG/HE(-Z)E, CPM2A, CPM2C, CQM1, CQM1H (other than the CPU11),
or SRM1: Built-in RS-232C port connection
Word Writing Value Settings
DM6645 0001 Host link mode, no CTS control, communications conditions
set by the contents of DM
0303 Data length 7 bits, 2 stop bits, even parity, communications
speed: 9600 bps
DM6646
0304 Data length 7 bits, 2 stop bits, even parity, communications
speed: 19200 bps
DM6648 0000 Unit # 00
C200HX/HG/HE(-Z)E: Serial Communications Board port A, CQM1H: Serial
Communications Board port 1
Word Writing Value Settings
DM6555 0001 Host link mode, no CTS control, communications conditions
set by the contents of DM area
0303 Data length 7 bits, 2 stop bits, even parity, communications
speed: 9600 bps
DM6556
0304 Data length 7 bits, 2 stop bits, even parity, communications
speed: 19200 bps
DM6558 0000 Unit # 00

Other manuals for NS10-TV Series

2

This manual suits for next models

6

Other Omron Touch Terminal manuals

Omron NT2S-SF121B-E - User manual

Omron

Omron NT2S-SF121B-E - User manual

Omron PRT1-COM User manual

Omron

Omron PRT1-COM User manual

Omron NA-series Instructions for use

Omron

Omron NA-series Instructions for use

Omron NT20S User manual

Omron

Omron NT20S User manual

Omron NT31 Series User guide

Omron

Omron NT31 Series User guide

Omron NA-series User manual

Omron

Omron NA-series User manual

Omron NT2S-SF121B-E - Instruction manual

Omron

Omron NT2S-SF121B-E - Instruction manual

Omron NT-series User manual

Omron

Omron NT-series User manual

Omron NT4S User manual

Omron

Omron NT4S User manual

Omron NT31 Series User guide

Omron

Omron NT31 Series User guide

Omron NT21 User guide

Omron

Omron NT21 User guide

Omron NS - REV 12 User guide

Omron

Omron NS - REV 12 User guide

Omron NB-series User manual

Omron

Omron NB-series User manual

Omron NV3W Series Instruction manual

Omron

Omron NV3W Series Instruction manual

Omron DRT2 SERIES DEVICENET SLAVES - OPERATION ... User manual

Omron

Omron DRT2 SERIES DEVICENET SLAVES - OPERATION ... User manual

Omron NB-series User manual

Omron

Omron NB-series User manual

Omron NXR-ILM08C-EIT User manual

Omron

Omron NXR-ILM08C-EIT User manual

Omron NS10-TV Series Owner's manual

Omron

Omron NS10-TV Series Owner's manual

Omron NT20 User manual

Omron

Omron NT20 User manual

Omron NS-CXDC1-V1 User manual

Omron

Omron NS-CXDC1-V1 User manual

Omron NP3 Series Reference manual

Omron

Omron NP3 Series Reference manual

Omron NT612G Series User manual

Omron

Omron NT612G Series User manual

Omron NT2S-SF122B-E START V1.03 Instruction manual

Omron

Omron NT2S-SF122B-E START V1.03 Instruction manual

Omron NXR-ILM08C-ECT User manual

Omron

Omron NXR-ILM08C-ECT User manual

Popular Touch Terminal manuals by other brands

Festo CPV GE-IL Series Description

Festo

Festo CPV GE-IL Series Description

Philips/Magnavox MAT972A1 owner's manual

Philips/Magnavox

Philips/Magnavox MAT972A1 owner's manual

Mitsubishi Electric F930GOT-BWD Operation manual

Mitsubishi Electric

Mitsubishi Electric F930GOT-BWD Operation manual

Digital Equipment VT520 Installation and operating information

Digital Equipment

Digital Equipment VT520 Installation and operating information

Poslab Airpod OP-430 user manual

Poslab

Poslab Airpod OP-430 user manual

NEC SL1000 user guide

NEC

NEC SL1000 user guide

DIGM Technology GSM-TIT200A user manual

DIGM Technology

DIGM Technology GSM-TIT200A user manual

Magtek DynaFlex II Series Installation and operation manual

Magtek

Magtek DynaFlex II Series Installation and operation manual

VeriFone T650p user manual

VeriFone

VeriFone T650p user manual

Carel TH Tune user manual

Carel

Carel TH Tune user manual

VeriFone VX570 Quick tips

VeriFone

VeriFone VX570 Quick tips

Toast Contactless Pay Installation and configuration instructions

Toast

Toast Contactless Pay Installation and configuration instructions

AVYCON AVR-NN Series Instruction guide

AVYCON

AVYCON AVR-NN Series Instruction guide

red lion GRAPHITE G15 installation guide

red lion

red lion GRAPHITE G15 installation guide

protech PA-J580 Series user manual

protech

protech PA-J580 Series user manual

red lion GL300 manual

red lion

red lion GL300 manual

UNIONCOMMUNITY UBio-X Face Premium installation guide

UNIONCOMMUNITY

UNIONCOMMUNITY UBio-X Face Premium installation guide

ProX PA-5822 M1 user manual

ProX

ProX PA-5822 M1 user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.