HOBO®Data Node, 2 Analog, 2 Pulse
(Part No: ZW-008)
1
Inside this package:
•ZW-008 HOBO data node
•AC power adapter
•3 AAA batteries
•Accessory kit
© 2010 Onset Computer Corporation
Manual Part No: MAN-ZW-008
Doc No: 13559-B
Introduction
Thank you for purchasing an Onset HOBO data node. With
proper care, it will give you years of accurate and reliable
measurements.
The ZW-008 HOBO data node is configured with 2 analog and
2 pulse channels.
The analog channels accept a wide range of Onset and third-
party sensors/transducers with a 0-2.5 VDC output, including
external temperature and AC current sensors. Specifications
for Onset sensors can be found at www.onsetcomp.com or by
contacting your Onset Authorized Dealer. For 0-5 VDC, 0-10
VDC, or 4-20 mA output, use optional Onset part no. CABLE-
ADAP5, CABLE-ADAP10, or CABLE-4-20mA respectively.
Onset part no. CABLE-2.5-STEREO is required to connect to
the HOBO data node's pulse channels. (Connect the pulse
output device to the cable's black and white leads.)
Note: Refer to the Onset Wireless Data Node Setup Guide and HOBOware®Pro Software User Guide for information on
configuring and using the HOBO data node.
Specifications
Radio power 1.6 mW (2 dBm)
Transmission range Approx. 100 m (328 ft), depending on obstructions or interference
Wireless data standard IEEE 802.15.4 2.4 GHz band
Measurement ranges Analog channels: 0 to 2.5 VDC, 0 to 5 VDC (w/ CABLE-ADAP5), 0 to 10 VDC (w/ CABLE-ADAP10)
Pulse channels: Maximum input frequency: 120 Hz (120 pulses per second) ·Measurement range: 0 to 65,535 pulses per logging
interval ·Resolution: 1 pulse ·Recommended input type: Electronic solid state switch closure or CMOS-level digital
output (example: FET, opto-FET or open collector) ·Minimum pulse width: 1 ms ·Input/output impedance: 100 KΩ·
Maximum input voltage: 2.8 V ·Bits per sample: 16
Accuracy Analog channels: +/- 1.544 mV plus 2% of reading typical
Resolution Analog channels: 0.6 mV
Operating temperature (batteries installed): -20 to 50° C (-4 to 122° F) ·(no batteries): -20 to 70° C (-4 to 158° F)
Operating humidity 5% to 95% non-condensing
Time accuracy ± 1 minute per month at 25° C (77° F)
Memory capacity 128K
Power options AC power adapter: Onset part no. AC-ZW-1; Batteries: 3 alkaline AAA included
Battery life 1 year @ 15 minute measurement interval, 60 minute transmit interval
Note: For a ZW-008 that has been designated as a router in a network, battery life is approximately 24 hours
Case material ABS
Dimensions 96.5 x 108 x 28 mm (3.8 x 4.25 x 1.1 in.)
Analog channel (A1)*
Analog channel (A2)*
Pulse channel (P1)
Pulse channel (P2)
Activation button access hole
Locking screw hole
Battery compartment cover/case mount
Status LEDs
External power
(Onset part no. AC-ZW-x)
*Caution: Analog channel input cannot exceed 2.5 VDC.
For sensor outputs up to 10 VDC, use appropriate
voltage adapter cable.