Optimus Compact User manual

25/10/2023 V5.2.002


COMPACT version 5.2.002 ENG
3
Modular audio matrix
with IP connection
COMPACT
4ETH
R + D Department
SAFETY INSTRUCTIONS:
IMPORTANT:
•Read carefully the safety instructions.
•Keep this manual for future references.
•Unplug the equipment during lightning storms or if it won’t be used for a long time.
•Always use certified wires to prevent electric shock or fire. In case of doubt, consult a qualified installer.
•Do not use the unit in humid places or near liquids. Do not install it near heat sources. Do not block ventilation openings.
•When it is necessary, remove dust with a dry cloth. Do not use solvents such as alcohol. Keep the unit clean and dust free.
•Maintenance operations require qualified personnel.
Note: The information provided in this manual does not include neither details of design production or variations in equipment, nor
possible risks during installation, operation or maintenance. If you need special assistance beyond the manual, please contact our
customer service

COMPACT version 5.2.002 ENG
4
Modular audio matrix
with IP connection
COMPACT
4ETH
R + D Department
ATTENTION. This is Class A unit. In a domestic environment it may cause radio interference. In such a case, the user will be
required to take appropriate measures.
Table of contents
1. INTRODUCTION......................................................................................................................................5
2. FRONT VIEW...........................................................................................................................................6
3. REAR VIEW.............................................................................................................................................6
3.1. A495MP Power and control module .....................................................................................................7
4. PLACEMENT OF THE BATTERY ...............................................................................................................10
5. CONNECTION OF PERIPHERALS TO THE CAN BUS ...................................................................................12
5.1. Configuration of the CAN bus baud rate of the COMPACT unit ...........................................................13
5.2. Position of the device on the CAN bus (intermediate or final element)...............................................13
5.3. Connection between the COMPACT and COMPACT-E units ................................................................15
5.4. Connection between COMPACT and CAN peripherals........................................................................16
6. INSERTING THE CARDS..........................................................................................................................16
7. DISPLAY, GENERAL VIEW.......................................................................................................................17
8. AVIGATING THROUGH THE MENUS .......................................................................................................17
9. STRUCTURE OF THE MENUS..................................................................................................................18
10. COMMISSIONING OF THE DEVICE..........................................................................................................19
10.1. Configuration of the COMPACT network addresses........................................................................19
10.1.1. Changing the IP address.....................................................................................................19
10.1.2. Changing the Netmask.......................................................................................................19
10.1.3. Changing the Gateway.......................................................................................................19
11. OPERATIONS FROM THE FRONT PANNEL...............................................................................................20
11.1. User levels and changes..................................................................................................................20
11.2. Adjusting display contrast ..............................................................................................................20
11.3. Front USB connector: Playing music from an external memory ......................................................20
11.4. Volume zones adjustment .............................................................................................................21
11.5. Stop or activate all the music channels of the area.........................................................................22
11.6. Stop or activate a specific music channel........................................................................................22
11.7. Configure music channels ...............................................................................................................22
12. SYSTEM ALARMS ..................................................................................................................................23
13. CARACTERÍSTICAS TÉCNICAS .................................................................................................................27
14. NETWORK SPECIFICATIONS...................................................................................................................28
15. SOFTWARE AND FIRMWARE VERSIONS.................................................................................................32
16. DOCUMENT VERSION TRACKING...........................................................................................................32
17. WARRANTY..........................................................................................................................................33

COMPACT version 5.2.002 ENG
5
Modular audio matrix
with IP connection
COMPACT
4ETH
R + D Department
1. INTRODUCTION
Modular audio matrix with IP connection and monitoring functions for fully managing PA and voice alarm systems. It is the main
component of the COMPACT control system.
It has 10 slots for the insertion of UMX-C16, UMX-EA3, UMX-2M3, UMX-2SA, UMX-2SB, UMX-MC6, UMX-LNK or UMX-PS cards.
The capacity of the matrix may be expanded using COMPACT-E units (10 slots per unit) up to a maximum of 10 units. The COMPACT-
E units allow housing cards UMX-2SA, UMX-2SB, UMX-MC6, UMX-C16 or UMX-LNK/E.
It includes the necessary connections, monitoring system and indicators to comply with the EN54-16 fire evacuation standard.
Main characteristics:
•Dual Ethernet connection for installations with redundant
network systems. The connection is constantly monitored
and switches automatically when required.
•It is equipped with two power supplies (one primary and
one secondary) for redundant installations.
•Front USB input for music.
•CAN bus for communicating with the COMPACT-E matrix
and peripherals.
•Reception of digital audio via an IP connection (4
simultaneous channels).
•Reception and sending of control data via an IP connection.
•Monitoring of the operation of the equipment using Call
Point software and/or basic TELNET or SSH (Secure Shell)
functions.
•Configuration of the IP address in Flash memory via
software.
•Constant notification (IP) of the status of the equipment
via a Heart Beat signal.
•It has 16 GB of internal memory for storing audio files to
be used as pre-recorded messages. Messages can be
recorded/updated remotely via IP, using Call Point
software.
•Monitoring functions:
-of the speaker lines (short-circuit and line open).
-of the amplifiers.
-of the cards inserted in the matrix.
-of the primary and secondary power supplies.
-of the input contacts.
-of the pre-recorded messages.
•Control of the volume of zones.
•Management of the musical channels of the system.
•Communication with external systems:
-VoIP: receiving of direct calls from any VoIP digital
telephone that uses standard SIP protocols. Incorporates
zone selection by sending DTMF tones. Provides the
possibility of protecting the access with a password.
-Direct integration (XML, API/DLL).
•Allows housing module ME-200B (front evacuation panel).

COMPACT version 5.2.002 ENG
6
Modular audio matrix
with IP connection
COMPACT
4ETH
R + D Department
2. FRONT VIEW
(1) GENERAL FAULT indicator light. Yellow LED system alarm
indicator.
(2) SYSTEM FAULT indicator light. Yellow LED internal
equipment error indicator.
(3) EMERGENCY indicator light. Red LED emergency
indicator. Remains illuminated while the system is in
Emergency Mode.
(4) Buzzer. The COMPACT incorporates a buzzer that
generates an acoustic signal when an alarm is received.
(5) POWER indicator. Indicates that the unit is receiving
power.
(6) STANDBY push-button. The equipment enters in low
consumption mode, deactivating the music program.
(7) Navigation and OK/CANCEL selection keys.
(8) Front blank plate. Allows adding ME-200B module (voice
alarm fire panel).
(9) Display.
(10) CONSOLE connector. Mini USB connector. Allows
monitoring the system. Specialized personnel only.
(11) Front USB for music input.
(12) JP1 Internal jumper to deactivate the acoustic alarm on
SYSTEM FAULT errors (see section 12. SYSTEM ALARMS).
3. REAR VIEW
1) Slots 1 to 10. Allows insertion of UMX-C16, UMX-EA3, UMX-2M3, UMX-2SA, UMX-2SB, UMX-MC6, UMX-LNK or UMX-PS cards.
2) Power and control module A495MP. See section 3.1. A495MP Power and control module.
Figure 1
Figure 2

COMPACT version 5.2.002 ENG
7
Modular audio matrix
with IP connection
COMPACT
4ETH
R + D Department
3.1.A495MP Power and control module
1) POWER indicator of the equipment.
2) FAIL contacts
Output relay used to indicate a system failure.
If the COM contact is linked to the NO contact, it indicates that there
are no faults or alarms in the system. If on the other hand, COM is linked
to NC, it indicates that the equipment is switched off or alarms detected
(figure 4).
Maximum DC charge current: 150mA
Maximum DC or AC peak charge voltage: 350V
3) BUS CAN contacts
Data communication bus between the COMPACT matrix, the
COMPACT-E expansion unit and CAN peripherals.
For the connection of the CAN bus it is recommended to use a shielded
twisted pair AWG24 cable. See section 5.3. Connection between the
COMPACT and COMPACT-E units and 5.4. Connection between
COMPACT and CAN peripherals.
4) OUTPUT CT contacts
It has three output contacts. Each contact consists of two terminals (A
and B) that can be configured, by means of internal DIP switches as dry
contacts (with or without 3K3 resistor) or referenced to ground (contact
A). For configuration follow figure 7 on the next page.
The functionality and the idle state (NC/NO) are configured via the Call
Point software. They can be configured as general-purpose contacts, or
in evacuation systems as fault notification contacts, Emergency Mode
activated indicator....
To connect as dry contacts, follow figure 5. If contacts referenced to
ground are desired, follow figure 6.
Attention: Max. DC charge current: 150 mA. Max.
DC or AC peak charge voltage: 350 V.
Figure 3
Figure 4
COMPACT
OFF or
alarms
detected
No alarms
Figure 5
CONNECTION OF THE OUTPUT
CONTACTS AS DRY CONTACTS
EXTERNAL
DEVICE
Figure 6
CONNECTION OF THE OUTPUT CONTACTS
AS CONTACTS REFERENCED TO GROUND
EXTERNAL
DEVICE

COMPACT version 5.2.002 ENG
8
Modular audio matrix
with IP connection
COMPACT
4ETH
R + D Department
DIPSWITCH
NUMBER
* A/B DRY CONTACT
WITH 3K3 RESISTOR
A/B DRY CONTACT
WITHOUT 3K3
RESISTOR
“A”CONTACT
REFERENCED TO
GROUND
OUTPUT
CONTACT 1
1
OFF
ON
OFF
2
OFF
OFF
OFF
3
OFF
OFF
ON
OUTPUT
CONTACT 2
4
OFF
ON
OFF
5
OFF
OFF
OFF
6
OFF
OFF
ON
OUTPUT
CONTACT 3
7
OFF
ON
OFF
8
OFF
OFF
OFF
9
OFF
OFF
ON
SW2 DIPSWITCH.
JUNCTION BETWEEN POWER
SUPPLY NEGATIVE AND CHASSIS
* JOINED
DIPSWITCH 1 →ON*
DIPSWICTH 2 →ON*
SEPARATED
DIPSWITCH 1 →OFF
DIPSWICTH 2 →OFF
* FACTORY SETTINGS
* FACTORY SETTINGS
Figure 7
OUTPUT CONTACTS CONFIGURATION
WARNING: Disconnect the power
supply of the equipment before
removing and handling the A495MP
control module.
DIPSWITCH S1.
CONFIGURATION OF THE OUTPUT CONTACTS
Remove the A495MP
control module

COMPACT version 5.2.002 ENG
9
Modular audio matrix
with IP connection
COMPACT
4ETH
R + D Department
5) INPUT CONTACTS CT 1, CT2 and CT3
The functionality and de-energized state (NC/NO) are configured through the configuration software. They may be configured
as general-purpose contacts or in the evacuation system as emergency mode activation contacts, evacuation message
activated...
If you wish, the system may monitor these contacts (short-circuit or open line detection).
The detection time of the activation pulse of the input contacts is configurable through the Call Point software (0-50-100-200-
300-400-500-1000-1500-2000 milliseconds).
To connect follow figure 8. If you wish to monitor the contact, follow figure 9.
6) BUS AUDIO LINK
Audio bus expansion connector. it is used for connecting the COMPACT to the
COMPACT-E units. To accomplish this use 34-way flat ribbon cable with 2x17, pitch
2.54mm IDC connectors. When installing the cable be careful to install the
connectors in the same position and side of the flat ribbon cable (see figure 16).
7) POWER SUPPLY 1
24 VDC primary power input strip. Connect a 24 VDC
power supply (not included) to this input, respecting
the polarity indicated in figure 10.
8) POWER SUPPLY 2
Secondary 24 VDC power supply input (see figure 11).
The power supply inputs have been duplicated so that,
if required by safety regulations, two independent
power supplies can be connected.
9) GND contact
10) ETH A connector
It is used to connect the equipment to the IP network
via an RJ45 FTP Cat 5 cable (not included).
The connector has a yellow LED (LINK) indicating
connection to the network, and a green LED
(ACTIVITY) that flashes indicating sending or receiving
data.
11) ETH B connector
It is used, in a redundant network, as a secondary
connection to the IP network.
Figure 8
INPUT CONTACT CONNECTION
WITHOUT SURVEILLANCE
Figure 9
INPUT CONTACT CONNECTION WITH
SURVEILLANCE
Figure 10
PRIMARY POWER
SUPPLY INPUT
Figure 11
SECONDARY POWER
SUPPLY INPUT

COMPACT version 5.2.002 ENG
10
Modular audio matrix
with IP connection
COMPACT
4ETH
R + D Department
Handling batteries properly:
•Warning! Improper use of battery may lead to explosion. Replace the batteries with the same or equivalent type only.
•Batteries may endanger life if swallowed. If a battery is swallowed, seek medical assistance immediately.
•Before inserting the batteries, check whether the contacts in the device and batteries are clean and, if necessary, clean them.
•Only use new batteries.
•Do not use rechargeable batteries
•Never try to recharge normal batteries. There is a risk of explosion!
•Never expose batteries to heat sources (e.g. radiators) or direct sunlight. There is an increased risk of leakage!
•Never short-circuit the batteries.
•Never throw batteries into a fire.
•Do not disassemble or deform batteries.
•If the equipment is not going to be used for long periods, remove the battery.
•Remove leaking batteries from the device immediately. If battery acid leaks out it is essential to avoid contact with the skin,
eyes and mucous membranes! If the acid does come into contact with skin, immediately rinse the affected areas with plenty
of clear water and consult a doctor immediately. There is a risk of acid poisoning and acid burns!
•Remove exhausted rechargeable battery from the device immediately! There is an increased risk of leakage
•Do not throw used batteries into the household waste. The batteries must be deposited in a collection point for used batteries.
4. PLACEMENT OF THE BATTERY
The Call Point software allows you to create message schedules and volume schedules, and to send these schedules to the equipment.
In this way, it is not necessary to use a server PC to activate the time schedules, but the equipment activates them automatically.
For this purpose, the unit incorporates a RTC (Real-Time Clock) whose function is to maintain the current time. To keep the RTC
powered even if the equipment is turned off, a 3V lithium battery type CR2032 supplied with the equipment must be used.
It is recommended to replace the battery at least every 5 years.
Battery placement procedure:
1) Disconnect the power strips (POWER
SUPPLY 1 and POWER SUPPLY 2).
Figure 12

COMPACT version 5.2.002 ENG
11
Modular audio matrix
with IP connection
COMPACT
4ETH
R + D Department
2) Remove the control module.
3) Insert the battery respecting the
polarity indicated in the drawing in
figure 14.
4) Once placed, insert the control
module and turn on the COMPACT
power.
When inserting or changing the battery, it is necessary to synchronize the time of the equipment with the rest of the equipment
in the installation. To do this:
•If one or more NTP servers are configured in the system, the time and date of the equipment will be updated automatically.
•If there is a server PC in the system, you can update the time using the Call Point software.
•If there are neither NTP servers nor server PCs in the system, connect to the web server of the unit to change
the date and time:
1. From a PC whose IP address is in range with that of the unit, open a browser, enter the IP address of
the unit and press ENTER.
By default, the unit's network settings are as follows:
IP ADDRESS: 10.1.1.1
NETMASK: 255.0.0.0.0
GATETEWAY: 0.0.0.0.0 (no Gateway)
2. Enter the username optimax, the password 1933 and click the Login button.
3. In the Setup section, select Time.
4. Modify the date and time parameters and click Set Time.
Figure 13
Figure 14

COMPACT version 5.2.002 ENG
12
Modular audio matrix
with IP connection
COMPACT
4ETH
R + D Department
External bus CAN
speed adapter
(500 kbit/s -
33.333 kbit/s)
model
CAN-AV
(A465AV)
Figure 15
Internal speed
adapter
Internal speed
adapter
5. CONNECTION OF PERIPHERALS TO THE CAN BUS
The COMPACT device communicates with the COMPACT-E and IF-7P4/0E units via a CAN bus. The data flow rate between the
COMPACT device and the COMPACT-E and IF-7P4/0E expansion units is 500 kbit/s (default rate).
With the other CAN peripherals in the installation (MD-30C, ME-200C, NS-CAN...) and thanks to an internal speed adapter
incorporated in the COMPACT unit, the transmission speed is 33.333 kbit/s. This lower speed makes it possible to reach greater
distances in the connection between the peripherals and the COMPACT
unit. The adapter also makes it possible to galvanically isolate the
COMPACT from the equipment in the installation, protecting it from
possible wiring problems in the installation. To communicate with these
peripherals, the transmission speed of the COMPACT unit must be set to
33.333 kbit/s, as explained in section 5.1.
In installations where COMPACT-E or IF-7P4/0E units coincide on the
same CAN bus with other CAN peripherals (MD-30C, ME-200C, NS-
CAN...) it is necessary to install the external CAN-AV model speed
adapter (code A465AV) to match the transmission speed between units.
Model
SPEED TRANSMISSION
COMPACT
33.333 kbit/s o 500 kbit/s (built-
in speed adapter)
COMPACT-E
500 kbit/s
IF-7P4/0E
500 kbit/s
MD-30C
33.333 kbit/s
ME-200C
33.333 kbit/s
NS-CAN
33.333 kbit/s

COMPACT version 5.2.002 ENG
13
Modular audio matrix
with IP connection
COMPACT
4ETH
R + D Department
5.1.Configuration of the CAN bus baud rate of the COMPACT unit
During commissioning of the device (see section 10. COMMISSIONING OF THE DEVICE) y and using the Call Point or Call Point
Configurator software, open the COMPACT device configuration window.
In the Parameters window, change
the Baudrate external CAN
parameter. If the COMPACT device
communicates with a COMPACT-E
or IF-7P4/0E expansion unit, set the
baud rate to 500 kbit/s (factory
setting). If the COMPACT unit
communicates with other
peripherals (MD-30C, ME-200C, NS-
CAN...), set the speed to 33.333
kbit/s.
Once modified, send the settings to
the device.
5.2.Position of the device on the CAN bus
(intermediate or final element)
Use the internal DIP switch S2 to configure the position of
the device on the CAN bus (end element or intermediate
element). By default, the matrix is configured as an end
element. If you wish to change this configuration, proceed as
follows:
1) Disconnect the power strips (POWER SUPPLY 1 and
POWER SUPPLY 2).
Figure 16

COMPACT version 5.2.002 ENG
14
Modular audio matrix
with IP connection
COMPACT
4ETH
R + D Department
2) Remove the control module.
3) Set DIP switch S2.
4) Once configured, reinsert the control module and connect the power supply.
* END ELEMENT
DIPSWITCH 1 →ON*
DIPSWICTH 2 →ON*
INTERMEDIATE
ELEMENT
DIPSWITCH 1 →OFF
DIPSWICTH 2 →OFF
Figure 17
Figure 18
DIPSWITCH S2.
CONFIGURATION AS AN INTERMEDIATE OR
END ELEMENT OF THE BUS CAN
* FACTORY SETTINGS

COMPACT version 5.2.002 ENG
15
Modular audio matrix
with IP connection
COMPACT
4ETH
R + D Department
5.3.Connection between the COMPACT and COMPACT-E units
Use the BUS AUDIO LINK connectors and the BUS CAN contacts to connect the COMPACT matrix to the COMPACT-E units.
For the CAN BUS connection, the use of a twisted pair, shielded AWG24 cable is recommended.
For the AUDIO BUS connection use 34-way flat ribbon with 2x17 IDC connectors, 2.54mm pitch. When assembling the cable, special
care should be taken to place the connectors in the same position and on the same side of the flat tape as shown in Figure 19.
The CAN bus transmission rate between the COMPACT unit and the COMPACT-E expansion units is 500 kbit/s.
CAN BUS
AUDIO BUS
Figure 19

COMPACT version 5.2.002 ENG
16
Modular audio matrix
with IP connection
COMPACT
4ETH
R + D Department
CAN peripheral
5.4.Connection between COMPACT and CAN peripherals
The COMPACT matrix must communicate with the CAN peripherals of the installation
(MD-30C, ME-200C, NS-CAN...) at a transmission rate of 33.333 kbit/s (in installations with
COMPACT-E expansion units the transmission rate must be 500 kbit/s). To do this, the CAN
communication speed of the matrix must be changed according to section 5.1.
Configuration of the CAN bus baud rate of the COMPACT unit.
For its connection, the use of a twisted pair and shielded AWG24 cable is recommended.
See figure 20.
6. INSERTING THE CARDS
The COMPACT matrix has 10 slots for inserting UMX-C16,
UMX-EA3, UMX-2M3, UMX-2SA, UMX-2SB, UMX-MC6,
UMX-PS or UMX-LNK cards. All these cards occupy one slot
except the UMX-2SB model which occupies 4 slots.
To insert a card proceed as follows (to insert the UMX-2SB
card consult the specific manual of said model):
1) Disconnect the power supply to the unit (POWER
SUPPLY 1 and POWER SUPPLY 2 strips).
2) Remove the rear blank plate for the slot where the
card is to be inserted.
3) Insert the card by fitting it into the slot guides and
fasten it by means of the fastening screws.
4) Reconnect the power.
(No conectado)
Figure 20
Figure 21
Figure 22

COMPACT version 5.2.002 ENG
17
Modular audio matrix
with IP connection
COMPACT
4ETH
R + D Department
7. DISPLAY, GENERAL VIEW
In standby, the unit displays the following information:
Name: Name, identifier of the unit in the installation
Version: Version of the unit firmware
Date: System date and time
4 tabs identified by icons are displayed on the top line:
EMERGENCY
This menu allows viewing the units as well as the zones that are
in emergency mode. The following information is displayed by
the tab:
SYSTEM ALARMS
Enables to display the alarms in the system, showing the unit generating the alarm and the type of alarm.
SELECTION OF ZONES
Allows viewing the zones status, modify the zones volume, and if the unit has an ME-200B module, select zones to
make an announcement using the front microphone (ME-200B).
SETTINGS
Allows modifying certain parameters of the unit (IP address, Netmask...), change user, check status of the unit or
monitor channels.
8. AVIGATING THROUGH THE MENUS
Using the navigation buttons you can access the different menus of the COMPACT.
Basic navigation through the menus:
Number of zones in Emergency Mode
that are making announcements
Total number of zones in
the installation
Total number of zones
in the installation
Number of zones
in emergency mode
-Move between tabs
(previous tab)
-Return to the top level menu
-Move between options in a menu
(previous item)
-Move between options in a menu
(next item)
-Enter the selected menu
-Confirm a data entry
-Confirm a chosen option
-Move between tabs (next tab)

COMPACT version 5.2.002 ENG
18
Modular audio matrix
with IP connection
COMPACT
4ETH
R + D Department
9. STRUCTURE OF THE MENUS
Press
Press
Press
Operator or Administrator user level is required
Administrator user level is required
SETTINGS
MENU
EMERGENCY
ALARMS
SELECTION
OF ZONES
AND VOLUME
ADJUSTMENTS
(EMERGENCY
MODE
OFF)
(SYSTEM IN
EMERGENCY
MODE)
(Only if it incorporates
module ME-200B)
Zone in
Emergency Mode
Zone
playing
audio
Alarms
in zone
Zone
selected
Zone
playing
audio
Alarms
in zone
(values between -80 and +4dB)
(values between
-80 and +4dB)
(values between 0 and 30)
(values between
-80 and +4dB)

COMPACT version 5.2.002 ENG
19
Modular audio matrix
with IP connection
COMPACT
4ETH
R + D Department
10. COMMISSIONING OF THE DEVICE
The commissioning of the device requires the sending of configurations to the device via the Ethernet connection. For this purpose,
a PC equipped with a network card and connected to the COMPACT, either via a switch or directly via a network cable, is required.
The PC must have the Call Point or Call Point Configurator software installed on it.
1. Insert the battery (see section ¡Error! No se encuentra el origen de la referencia.) and insert the cards required for the installation
into the COMPACT (see section 6. INSERTING THE CARDS).
2. Make the connections between the devices.
3. Turn on the power supply to the devices.
4. Configure the parameters of the COMPACT matrix and the cards it contains using the Call Point or Call Point Configurator software
and send the settings to the device.
10.1. Configuration of the COMPACT network addresses
In order to be able to send configurations, the network addresses established from the configuration software and those of the unit
must match.
The network configurations of the unit may be modified directly from the front panel if an Administrator user access level is available.
To change the user, follow the section11.1. User levels and changes.
10.1.1. Changing the IP address
1. Use the / navigation keys to select the settings menu
().
2. Using the /keys select IP (10.1.1.1) and press OK.
3. Use the or keys to enter the desired digit (from 0 to
9 and blank space).
Move to the next digit using the or navigation keys.
(for example, to enter number 24
enter a blank space, 2, 4)
4. To finish press OK.
10.1.2. Changing the Netmask
1. Use the / navigation keys to select the settings menu
().
2. Using the /keys select NETMASK (255.0.0.0) and
press OK.
3. Use the or keys to enter the desired digit (from 0 to
9 and blank space).
Move to the next digit using the or navigation keys.
4. To finish press OK.
10.1.3. Changing the Gateway
1. Use the / navigation keys to select the settings menu
().
2. Using the /keys select GATEWAY (0.0.0.0) and press
OK.
3. Use the or keys to enter the desired digit (from 0 to
9 and blank space).
Move to the next digit using the or navigation keys.
4. To finish press OK.
ATTENTION. In order to be able to send configurations to the device, it is necessary that the device and the PC are within
the same IP address range. It is also necessary that the network addresses of the device and those set from the
configuration software match.
By default, the device’s network configurations are as follows:
IP ADDRESS: 10.1.1.1.1
NETMASK: 255.0.0.0
GATETEWAY: 0.0.0.0 (without Gateway)
If you wish to assign a different network address to the unit than the default one, follow the next section 10.1.
Configuration of the COMPACT network addresses

COMPACT version 5.2.002 ENG
20
Modular audio matrix
with IP connection
COMPACT
4ETH
R + D Department
11. OPERATIONS FROM THE FRONT PANNEL
11.1. User levels and changes
To restrict the access to specific functions of the equipment, 3 user levels have been established. Basic, Operator and
Administrator.
Basic: Level by default when the equipment is booted. No access code. It cannot modify the volume, network addresses or adjust the
display contrast.
Operator: With access code (by default 1234). The access code may be changed via the Call Point software; It must be a four-digit
number. In addition to all the permissions granted to the basic user, he can configure the volume of the zones (except the emergency
volume) and the contrast of the display. He cannot configure the network addresses.
Administrator: With access code (by default 1234). Without restrictions. The access code may be changed via the Call Point software.
It must be a four-digit number.
A. Login as an ADMINISTRATOR USER
1. Using the /navigation keys, select the settings menu
().
2. Using the /keys select USER and press OK.
3. Using the /keys select LOGIN ADMINISTRATOR (OFF)
and press OK.
4. Enter the administrator user code (1234by default) and
press OK. Use the /keys to enter the desired digit (0
to 9). Scroll to the next digit by using the navigation
key.
5. Press OK to finish.
B. Logout as ADMINISTRATOR
1. Using the /navigation keys, select the settings menu
().
2. Using the /keys select USER and press OK.
3. Using the /keys select LOGOUT ADMINISTRATOR
and press OK.
C. Login as an OPERATOR USER
1. Using the /navigation keys, select the settings menu
().
2. Using the /keys select USER and press OK.
3. Using the /keys select LOGIN OPERATOR (OFF) and
press OK.
4. Enter the operator user code (1 2 3 4 by default) and press
OK. Use the /keys to enter the desired digit (0 to 9).
Scroll to the next digit by using the navigation key.
5. Press OK to finish.
D. Logout as OPERATOR
1. Using the /navigation keys, select the settings menu
().
2. Using the /keys select USER and press OK.
Using the /keys select LOGOUT OPERATOR and press
OK.
11.2. Adjusting display contrast
(Operator or Administrator user level is required)
1. Using the /navigation keys, select the settings menu ( ).
2. Using the /keys select CONTRAST and press OK.
3. Using the /keys adjust the contrast and press OK.
11.3. Front USB connector: Playing music from an external memory
The unit has a USB 2.0 port on the front panel for use as a musical program input. To do this, connect to this port an external memory
that contains audio files in MP3, WAV or OGG format.
Through the Call Point software, you can configure the parameters corresponding to this music program (random playback of audio
files, music activated or deactivated by zones…).
Other manuals for Compact
1
Table of contents
Languages:
Other Optimus Security System manuals
Popular Security System manuals by other brands

American Dynamics
American Dynamics AD1273 CobraDome Installation and operation instructions

Metra Electronics
Metra Electronics TE-DVR-MM user manual

E2S
E2S D1xS2 Series Instructions/service manual

Berkeley
Berkeley SentryHound-Pro user manual

Spitzer
Spitzer EWF Series installation manual

ADEMCO
ADEMCO VIA-30PSE quick guide