English
This manual describes the rules for the transportation, the installation, the use and the maintenance of the heat recovery. The user will find every-
thing that is normally useful to know for a correct and safe installation of the ERV+ X unit.
The non-observance of what is described in this handbook and an inadequate installation of the ERV+ X unit may cause the cancellation of the
guarantee that the Manufacturer/ istributor Company grants on the same one. The Manufacturer/distributor Company, moreover, does not
answer to possible direct and/or indirect damages due to wrong installation carried out by inexpert and/or non-authorised staff. At the moment
of the purchase, check that the machine is integral and complete. Claims will have to be produced within 8 days from the reception of the goods.
• Galvanized steel self-supporting panels, internally and externally insulated
• Counterflow air-to-air heat recovery device, made of plane sheets of special paper with special sealing to keep airflows separate and only
permeable to water vapor. with temperature efficiency up to 76% and enthalpy efficiency up to 67%, also at high
level during summer season
• ISO 16890 Coarse 50% + ePM2.5 95% (F9 EN779) efficiency class filters on fresh air, Coarse 50% (G3 EN779) filer on return air intake. All
filters are made with synthetic cleanable media.
• Removable side panel to access filters and heat recovery in the event of scheduled maintenance
• Motorised heat recovery by-pass device automatically controlled by unit control to use fresh air free-cooling when convenient
• , high efficiency & low noise direct driven fans with
• (R410A) fitted with solenoid control valve, freon filter, contact temperature sensors on liquid and gas
line, NTC sensors upstream and downstream airflow
• , switched on at fans running, able to do an efficient antibacterial treatment, ensuring a perfect healthi-
ness of supplied air
• Built-in electric box equipped with PCB to control internal fan speed and to interconnect outdoor/indoor units
• uct connection by circular plastic collars
Portata aria nominale / Nominal air flow m3/h 500 800 1000
Pressione statica utile nominale / Nominal external static pressure Pa 90 120 115
Alimentazione elettrica /Electrical power supply V/ph/Hz 230 / 1 / 50 - 60
Corrente assorbita massima totale /Total full load amperage A 0.6 1.4 2.1
Condizioni di esercizio limite / Limit working temperature °C / % - 15 …+ 40°C / 10 … 95 %
Tipologia motore / Motor typology EC EC EC
N° velocità / Number of speeds 33 3
Controllo ventilazione / Fan control (1) Man Man Man
Potenza specifica interna di ventilazione - SFP int /
nternal specific fan power of ventilation components - SFP int (5) W/(m3/s) 547 865 881
Potenza assorbita nominale totale / Total nominal power input kW 0.15 0.32 0.39
Livello di pressione sonora / Sound pressure level (2) dB(A) 39 42 43
Efficienza termica invernale / Winter thermal effic. (3) % 76.0% 76.0% 76.0%
Efficienza entalpica invernale / Winter enthalpy effic. (3) % 67.0% 65.0% 62.0%
Efficienza termica estiva / Summer thermal effic. (4) % 76.0% 76.0% 76.0%
Efficienza entalpica estiva / Summer enthalpy effic. (4) % 63.0% 63.0% 60.0%
Efficienza termica a secco / Dry thermal efficiency (5) % 76.0% 76.0% 76.0%
Potenza termica / Heating capacity (6) kW 2,5 (2,7) 4,4 (4,8) 5,2 (6,7)
Temperatura aria mandata / Supply air temperature °C 28,0 (27,3) 29,6 (29) 28,5 (27,8)
Umidità aria mandata / Supply air humidity % 16 (15) 14 (13) 15 (14)
Potenza frigorifera totale / Total cooling capacity (7) kW 3.0 5.1 5.8
Potenza frigorifera sensibile / Sensible cooling capacity kW 2.1 3.5 4.1
Temperatura aria mandata / Supply air temperature °C 15.9 15.5 16.2
Umidità aria mandata / Supply air humidity % 90 90 89
nstallation, Use and Maintenance Manual - ERV+DX series pag. 23
DC MAN I 05 460 ERVDX 09_SIC 14/01/2019 17.05 Pagina 23