
EBL512 G3 - FIRE ALARM SOLUTIONS DAILY USER'S MANUAL
6
15 DEL Used to clear / delete all visible entry elds.
16 ESC Used to stop input of data or to step upwards in the menu system.
17 Key pad Numeric key pad for the digits 0-9.
18 Enter Used to accept / select a menu or input of data. Also used to acknowledge fault signal and service signal.
19 Left / right keys Used to move the cursor in a menu.
20 Up / down keys Used to scroll between the menus.
21 Alarms queued Used when LEDs "Alarms queued" are lit. Scroll through the queued alarm points or zone addresses.
NOTE! To scroll/browse through the queued zones, use the soft key "Next zone" (23).
22 - 25 Soft keys The function is shown in the display above the soft key. The function of a soft key may vary. If nothing is
shown above the key in the display, the key has no function for the moment.
26 Reset Used to reset: Fire alarms, co-incidence alarms.
NOTE! Has to be pressed for > 0.5 sec.
27 Silence alarm devices Used to silence alarm devices / sounders. If “silence alarm devices” is activated, it is indicated by a
symbol in the display, see (35).
28 Silence buzzer Used to silence the buzzer in the c.i.e. when it is sounding.
2.2. PUSH BUTTONS
See reference picture on page 4.
29 The door is open in any c.i.e. (not valid for 5055) in the system.
30 Loss of mains in any c.i.e. or external power supply unit in the system. The unit is currently power supplied via batteries.
31
Service signal. The week average sensor value is over the service level, or detector is outdated, for one or more analog smoke detectors in the system.
Menu H4/U5 (Symbol ashing): The system is in service mode:
• A COM loop is disconnected
• A COM loop is in service mode
• A Zone line input is disconnected
• Check loop, Autogenerate loop or Auto-addressing function etc. is in progress
32 The c.i.e. is set into “Sensitive fault detection mode” via menu H5/A2.
33 One or more “Technical warnings” are generated in the system.
34 The functions of the soft keys will vary depending on the situation, convention and language.
35 “Silenced Alarm devices” is indicated by this symbol.
2.3. DISPLAY
See reference picture on page 4.