Panasonic Firetracker FT1020G3 CIE User manual

Operation Manual
FT1020G3
Rev 2.10.4
For Software V2.10.4
FT1020G3 FDCIE
MA430 March 2023

This page has deliberately been left blank.

3
Operation Manual
FT1020G3 Rev 2.10.4
Table of Contents
1Introduction...................................................................................................................... 10
1.1 Overview............................................................................................................................ 10
1.2 Definitions / Explanations .................................................................................................. 10
2General Description ........................................................................................................ 13
2.1 The FT1020G3 FDCIE ...................................................................................................... 13
2.2 Com Loop Units................................................................................................................. 14
2.3 Address and Mode ............................................................................................................ 14
2.4 Software (S/W) Versions ................................................................................................... 14
2.4.1 EBLWin ..........................................................................................................14
2.4.2 TLON Manager ..............................................................................................14
2.5 Applications ....................................................................................................................... 14
3Fire Detection Control & Indicating Equipment (FDCIE) .............................................15
3.1 FT1020G3 Specifications .................................................................................................. 15
3.2 FT1020G3 Limitations ....................................................................................................... 16
3.3 FT1020G3 FDCIE Layout.................................................................................................. 17
3.4 Front Display ..................................................................................................................... 18
3.4.1 LED Indicators and Push Buttons...................................................................19
3.4.2 The Display (LCD)..........................................................................................21
3.5 System Information in the LCD.......................................................................................... 23
3.5.1 User Definable System Information ................................................................23
4FT1020G3 Options........................................................................................................... 24
4.1 I/O Matrix 4582 .................................................................................................................. 24
4.2 NZ Fire Brigade (LED) Mimic Board.................................................................................. 24
4.3 Occupant Warning System (OWS).................................................................................... 25
4.3.1 Standard OWS Display...................................................................................25
4.4 Gaseous Extinguishing Control Module ............................................................................ 26
4.5 Printer Option .................................................................................................................... 27
519” Rack Cabinet & Brooks Loop Modules ..................................................................28
5.1 Cabinet Overview .............................................................................................................. 28
5.2 Enclosure Components ..................................................................................................... 29
5.3 New G3 Boards ................................................................................................................. 29
5.3.1 Main Control Board 5012................................................................................29
5.3.2 Loop Board 5017............................................................................................31
5.3.3 MMI Board 5015.............................................................................................31
5.4 Addressable COM Loop Display Modules......................................................................... 33
5.4.1 Power monitor and loop connection module 1204 ..........................................34
5.4.2 Zone Control Module 1205 .............................................................................34
5.4.3 Fan / Damper Control Module 1206 / 1211.....................................................35
5.5 Generic FT1020G3 Display and Control Modules............................................................. 37
5.5.1 Generic 8 Switches / 8 LED’s Display / Control Module 1207.........................38
5.5.2 Generic 4 Switches / 8 LED’s Display / Control Module 1208.........................38
5.5.3 Generic 8 LED’s Display Module 1209 ...........................................................38
5.5.4 Pump status 6 LED’s Display Module 1210 ....................................................38
5.6 I/O Field Modules .............................................................................................................. 39
5.6.1 1200 Module – SUB997 .................................................................................39
5.6.2 1202 Module – SUB994 .................................................................................40
5.6.3 1203 Module – SUB991 .................................................................................40
6User Data & Access Levels ............................................................................................ 41
6.1 User Data .......................................................................................................................... 41

4
Operation Manual
FT1020G3 Rev 2.10.4
6.1.1 User Name .....................................................................................................41
6.1.2 Password .......................................................................................................41
6.1.3 Password for Web-server / Gateway Access only ..........................................42
6.2 Access Levels.................................................................................................................... 42
6.2.1 How to Log On ...............................................................................................42
6.2.2 Navigation / General Procedures....................................................................42
6.3 User Level ......................................................................................................................... 43
6.3.1 User Level as specified in AS7240.2 ..............................................................43
6.3.2 User level 0 ....................................................................................................43
6.3.3 User level 1 ....................................................................................................43
6.3.4 User level 2A..................................................................................................44
6.3.5 User Level 2B.................................................................................................45
6.3.6 User level 3A..................................................................................................46
6.3.7 User level 3B..................................................................................................46
6.3.8 User level 4 ....................................................................................................46
7Technical Number / Presentation Number.................................................................... 47
7.1 Technical Number for COM Loop Units ............................................................................47
7.2 Presentation Number......................................................................................................... 47
8Silence Alarm Devices .................................................................................................... 48
8.1 SILENCE ALARM (inside switch) ...................................................................................... 49
8.2 NZ FB “Silence Alarms” Bulgin key (outside switch) ......................................................... 49
9Disable / Re-enable Alarm Devices................................................................................51
10 "SILENCE BUZZER" ........................................................................................................ 52
10.1 Silence buzzer by open door ............................................................................................. 52
10.2 Silence buzzer by the "FB Bulgin Key" .............................................................................. 52
11 Disable or Re-enable Output .......................................................................................... 53
12 Disable/Re-enable Control Outputs ...............................................................................54
13 “DISABLE” Button........................................................................................................... 55
14 Open Door ........................................................................................................................ 56
14.1 Disable Routing Equipment with Door Switch ................................................................... 56
14.2 Silence Buzzer by Door Switch ......................................................................................... 56
15 Alarm Types ..................................................................................................................... 57
15.1 Pre-warning ....................................................................................................................... 57
15.2 Fire Alarm .......................................................................................................................... 58
15.2.1 Entering the Menus during Fire Alarm ..........................................................60
15.2.2 Test Mode Alarm ..........................................................................................60
15.3 Heavy Smoke Alarm / Heavy Heat Alarm ......................................................................... 61
15.4 Alert Annunciation Alarm (AA alarm)................................................................................. 61
15.5 Key Cabinet Alarm............................................................................................................. 62
15.6 Co-Incidence Alarm (2-Address / -Zone Dependence) ..................................................... 62
15.7 Delayed Alarm ................................................................................................................... 63
15.7.1 Standard Alarm Delay Applications ..............................................................63
15.7.2 Alarm Delay Facility (ADF)70 .........................................................................64
15.8 Local Alarm Acknowledgement (LAA) Facility Control......................................................64
15.9 Quiet Alarm........................................................................................................................ 65
15.10 Acknowledged and Isolated Alarm .................................................................................... 66
15.10.1 Acknowledged Alarm..................................................................................66
15.10.2 Isolated Alarm ............................................................................................66
15.11 Alarm Source..................................................................................................................... 66
16 Alarm Reset...................................................................................................................... 68
16.1 Pre-warning Reset............................................................................................................. 68

5
Operation Manual
FT1020G3 Rev 2.10.4
16.2 Fire Alarm Reset................................................................................................................ 68
16.2.1 All (Default) ..................................................................................................68
16.2.2 Single ...........................................................................................................68
16.2.3 Single with Automatic Disablement...............................................................69
16.3 Test Mode Alarm Reset..................................................................................................... 69
16.4 Acknowledged and Isolated Alarm (for only NZ) Reset.....................................................69
16.5 Heavy Smoke / Heat Alarm Reset..................................................................................... 69
16.6 Alert Annunciation Alarm Reset ........................................................................................ 69
16.7 Co-incidence Alarm Reset................................................................................................. 69
16.8 Delayed Alarm Reset......................................................................................................... 69
16.9 Alarm Delay Facility (ADF) Reset...................................................................................... 70
16.10 Local Alarm Acknowledgement (LAA) Reset .................................................................... 70
16.11 Quiet Alarm Reset ............................................................................................................. 70
17 Fault .................................................................................................................................. 71
17.1 Fault Messages ................................................................................................................. 72
17.2 Fault Acknowledge ............................................................................................................ 84
18 Commissioning an FT1020G3 ........................................................................................ 86
18.1 General .............................................................................................................................. 86
18.2 Single Control Unit............................................................................................................. 86
18.3 Control Units in a TLON Network ...................................................................................... 87
18.3.1 Network No. 0 ..............................................................................................87
18.3.2 TLON Network Installation (Single)...............................................................88
18.3.3 TLON Network Installation (Redundant) .......................................................88
18.3.4 Add a Control Unit into a TLON Network ......................................................88
18.3.5 Merge Two TLON Networks .........................................................................88
18.3.6 Delete a Control Unit in a TLON Network .....................................................89
18.4 Upgrade Number of Alarm Points ..................................................................................... 89
19 Software Installation and SSD Download .....................................................................91
19.1 EBLWin Software Requirements ....................................................................................... 91
19.2 EBLWin Installation Procedures in a PC First Time ..........................................................91
19.2.1 .NET Framework ..........................................................................................91
19.2.2 USB Drivers Installation................................................................................92
19.2.3 HASP Driver Installation (for 5094 key) ........................................................95
19.2.4 EBLWin software Installation ........................................................................95
19.2.5 Installation of EBL Firmware Manager..........................................................97
19.3 Download SSD .................................................................................................................. 99
19.3.1 Version Control for SSD Download...............................................................99
19.3.2 SSD Download to Single Control Unit.........................................................101
19.3.3 SSD Download to Control Units in a TLON Network...................................101
19.3.4 User Definable Text messages Download ..................................................101
20 Download Software (System Firmware)......................................................................102
20.1 Download Software to Single FDCIE .............................................................................. 102
20.2 Download Software in a TLON Network..........................................................................104
20.3 Software Versions ........................................................................................................... 106
21 Restart ............................................................................................................................ 107
21.1 Safe Shut Down............................................................................................................... 107
21.2 Restart Table ................................................................................................................... 107
21.2.1 Explanation of Restart Codes .....................................................................108
21.3 During Restart ................................................................................................................. 108
21.3.1 Memory fault ..............................................................................................109
22 Perform Monthly Test (H1)............................................................................................ 110
23 Disable or Re-enable (H2) ............................................................................................. 112

6
Operation Manual
FT1020G3 Rev 2.10.4
23.1 Zone or Zone Address (H2/B1) ....................................................................................... 113
23.2 Output (H2/B2) ................................................................................................................ 115
23.3 Output Type (H2/B3) ....................................................................................................... 117
23.4 Alarm Devices (H2/B4) .................................................................................................... 119
23.5 Routing Equipment / ASE (H2/B5) ..................................................................................121
23.6 Alert Annunciation (H2/B6) .............................................................................................. 123
24 Set Calendar and Clock (H3) ........................................................................................ 125
24.1 Daylight Saving Time....................................................................................................... 125
25 Present System Status (H4).......................................................................................... 126
25.1 Disablement (H4/U1) ....................................................................................................... 126
25.2 Disablement by Time Channel (H4/U2)........................................................................... 127
25.3 Open Doors (H4/U3)........................................................................................................ 128
25.4 Sensor Values (H4/U4).................................................................................................... 129
25.4.1 Explanation to the Sensor Values...............................................................130
25.5 Sensors Activating SERVICE Signal (H4/U5) .................................................................131
25.6 Technical Warning (H4/U6) ............................................................................................. 132
25.7 Event Log (H4/U7) ........................................................................................................... 133
25.8 Information (H4/U8) ......................................................................................................... 134
26 Service (H5) .................................................................................................................... 135
26.1 Calibration of Supervised Outputs (H5/A1) ..................................................................... 136
26.2 Sensitive Fault Detection Mode (H5/A2)..........................................................................137
26.3 Service Mode for COM-Loop (H5/A3) ............................................................................. 138
26.4 Display Current Consumption in Unit (H5/A4).................................................................139
26.4.1 Power Supply (Control Unit) .......................................................................139
26.4.2 Battery........................................................................................................139
26.5 Display Current Consumption on COM-loop (H5/A5)......................................................140
26.6 Display Statistics for Communication (H5/A6).................................................................141
26.7 Activate Address Setting Mode for DU (H5/A7) .............................................................. 142
26.8 Setup wireless detectors (H5/A8) .................................................................................... 143
26.9 SSD Information (H5/A9)................................................................................................. 145
27 FAULT Acknowledge (H6) ............................................................................................ 146
28 Perform Zone Test (Test mode) (H7) ........................................................................... 148
29 Maintenance (H8)........................................................................................................... 150
29.1 Disconnect / Reconnect Loop / Zone Line Input (H8/S1) ................................................ 150
29.2 Acknowledge SERVICE Signal (H8/S2) .......................................................................... 152
29.3 Clear Weekly Average (H8/S3) ....................................................................................... 154
29.4 Test of Alarm Devices (H8/S4) ........................................................................................ 155
29.5 Safe Shut Down of Control Unit (H8/S5) ......................................................................... 156
29.6 Activate Address in Alarm Mode (H8/S6)........................................................................ 158
29.7 Synchronise the Control Units (H8/S7) ........................................................................... 160
29.8 Activate / Reset outputs (H8/S8) ..................................................................................... 162
30 Interlocking Outputs and Inputs (H9) .......................................................................... 164
30.1 Activated Interlocking Outputs / Inputs (H9/C1) ..............................................................164
30.2 Activate / Deactivate Interlocking Output (H9/C2)........................................................... 165
30.3 Disable / re-enable interlocking output (H9/C3) .............................................................. 167
31 Change Password (H10) ............................................................................................... 168
32 FDCIE Maintenance ....................................................................................................... 169
32.1 Replacing a TLON Connection Board and/or the Main Board ........................................169
32.2 Battery Maintenance........................................................................................................ 170
33 How to Avoid Nuisance Fire Alarms ........................................................................... 171
34 Block Wiring Diagram ................................................................................................... 173
35 Guarantee ....................................................................................................................... 178

7
Operation Manual
FT1020G3 Rev 2.10.4
36 Revision history............................................................................................................. 179
36.1 Operation Manual Revisions Table ................................................................................. 179
36.2 Software Revision V2.10.4 .............................................................................................. 179

8
Operation Manual
FT1020G3 Rev 2.10.4
Table of Figures
Figure 1 Connection diagram of FT1020G3.........................................................................13
Figure 2 FT1020G3 with Optional OWS and Control/Display Modules ................................17
Figure 3 FT1020G3 front display .........................................................................................18
Figure 4 Occupant Warning System Display .......................................................................25
Figure 5 Gas Extinguishing Display Layout .........................................................................26
Figure 6 Serial Interface Module..........................................................................................27
Figure 7 FT1020G3 Mounted in 22U Large 19" Rack Enclosure .........................................28
Figure 8 FT128 (or FT1020G3) Mounted in 13U Small 19" Rack Enclosure........................29
Figure 9 Main Board 5012 ...................................................................................................30
Figure 10 Loop board 5017 .................................................................................................31
Figure 11 MMI Board 5015..................................................................................................32
Figure 12 3U Ancillary Modules Face Plate.........................................................................33
Figure 13 1204 Power Monitor Module................................................................................34
Figure 14 1205 Zone Control Module ..................................................................................35
Figure 15 1206 / 1211 Fan / Damper Control Module..........................................................35
Figure 16 Display and control modules................................................................................38
Figure 17 Single I/O 1200 connection and SUB997 PCB ....................................................39
Figure 18 4/4 1204 I/O SUB994 ..........................................................................................40
Figure 19 8/8 1203 I/O SUB991 ..........................................................................................40
Figure 20 Final Display Device Manager .............................................................................94
Figure 21 Installing HASPUserSetup in compatibility mode.................................................95
Figure 23 19” Rack 22U FT1020G3 General Arrangement with 6U battery box ................174
Figure 24 19” Rack 13U FT1020G3 General Arrangement with 6U battery box ................175
Figure 25 FT1020G3 Standard Block Wiring Diagram.......................................................176
Figure 26 FT1020G3 New 5012 PCB Layout ....................................................................177

9
Operation Manual
FT1020G3 Rev 2.10.4
List of Tables
Table 1 Definitions and Explanations 10
Table 2 Control unit specifications 15
Table 3 Control Unit limitations 16
Table 4 LED indicators and push buttons on Fire Brigade Panel (FBP) 19
Table 5 LED indicators on Control Panel (CP) 20
Table 6 Push buttons / keypad on Control Panel (CP) 21
Table 7 Symbol indications 22
Table 8 Priority Order 22
Table 9 I/O Matrix 4582 addressing and nd mode setting 24
Table 10 OWS Controls and Indications 25
Table 11 Gas Front Status LED Indication and flash Pattern 26
Table 12 Module specifications 33
Table 13 Fan indicators and controls 36
Table 14 Damper indicators and controls 37
Table 15 Levels of access 43
Table 16 Access Levels and user names 43
Table 17 Latest Software Versions for FT1020G3 106
Table 18 Data affected by restart 107
Table 19 Algorithms and abbreviations in NORMAL mode 130
Table 20 Algorithms in ADVANCED mode 130

10
Operation Manual
FT1020G3 Rev 2.10.4
1 Introduction
1.1 Overview
FT1020G3 Operation Manual is a document intended to be used by the end user and the
fire brigade personnel as well as service / commissioning engineers.
The block wiring diagrams of the standard FT1020G3 in 19” rack configurations and
general arrangements are shown in Chapter 34 page 173.
Due to continual development and improvement, different S/W versions are to be found.
This document is valid for software (firmware) version 2.10.x. On the date of printing this
manual x = 4.
The system software version is the firmware downloaded in to the Control Unit via PC
Windows based software e.g. EBL512G3 V2.10.x. The latest system software is factory
downloaded in FT1020G3 before delivery is EBL512G3 V2.10.x. However, new software
may be upgraded to a newer revision on site.
The software version is dependent on the country where the control panel to be installed,
that is due to the variations in the standard in each country. Two separate software
versions are available, Australian (AU) and New Zealand (NZ).
The PC software is Windows based software EBLWin which has to be installed in your PC,
and must have the first two digits of the version number identical to the system software
(firmware) version number i.e. version 2.10.x. The EBLWin is used to download the
firmware and the Site Specific Data (SSD) into the FDCIE.
Only the first two digits must be identical in the software and the EBLWin version number
i.e. 2.10.x (x = minor modifications).
1.2 Definitions / Explanations
Definitions / explanations and abbreviations are used frequently in this document and are
shown in Table 1 below.
Table 1 Definitions and Explanations
Device or function Description
Alarm points
Units, which can generate a fire alarm in FT1020G3, i.e. analogue
detectors (sensors), manual call points, conventional detectors,
etc.
Smoke detector
Analogue or conventional photoelectric smoke detector
Sensor
Sensor = Analogue detector
Analogue detector
Contains an A/D-converter. The FT1020G3 picks up the digital
values ("sensor values") for each detector individually. All
evaluations and "decisions" are then taken by alarm algorithms in
the FDCIE. The latest detector generation (440x) can be used in
"Advanced mode", i.e. the alarm algorithms are in the detector
instead. Analogue detectors are addressable, an address setting
tool 4414E is used to write the address and select the required
mode of the detectors on a COM loop.
An analogue detector has to be plugged in an Analogue Sensor
Base (ASB).
Analogue Sensor Base (ASB)
An analogue detector is plugged in an ASB, which is connected to
a COM loop (see below).

11
Operation Manual
FT1020G3 Rev 2.10.4
Conventional detector
A detector with only two statuses, i.e. normal or fire alarm. The
detector has a "closing contact" and a series alarm resistor.
Normally plugged in a conventional detector base CDB (see
below), which is connected to a conventional zone line input.
Some types are water proof types and cannot be plugged in the
standard base, it is connected directly to a zone line. An end-of-
line device has to be connected in the last unit on the
conventional zone line.
Conventional Detector Base (CDB)
A conventional detector is plugged in a CDB, connected to a
conventional zone line input.
Addressable Units
A unit with a built-in address device. Each unit is individually
identified, handled and indicated in the FDCIE. The unit can be
an I/O unit with a zone line input, to which one or more
conventional "alarm points" can be connected (It can also be one
of Brooks addressable modules 1200,1202 & 1203).
Conventional zone line input
Input intended for one or more conventional alarm points. End-of-
line device in the last alarm point on the zone must be fitted.
Output unit
Addressable unit with programmable control outputs. Connected
to a COM loop (see below).
Output / Control output
Defined or programmable function. Relay output or voltage output
(supervised or non-supervised), in the FDCIE or an output unit
connected to a COM loop.
Short circuit isolator (ISO) Addressable unit for automatic disconnection of a COM loop
segment (see below) in case of short circuit on the loop. As per
AS1670.1, one isolator is required every zone on the COM loop.
Remote Display Unit (RDU)
Addressable unit (RS485 line) for fire alarm presentation
(including user definable alarm text), alert annunciation, etc., end
of line resistor must be set via a jumper link on the last unit.
COM loop
Loop = twisted pair cable, to which all the addressable units can
be connected. Starts in the FDCIE and returns back to the FDCIE.
Control Unit / C.U. / FDCIE
Control Unit = Fire Detection Control and Indicating Equipment
(FDCIE) = Unit to which the alarm points are connected (via e.g. a
COM loop). Indicates on the front fire alarm, fault conditions, etc.
Fire Brigade Panel (FBP)
The fire brigade panel is an integral part of FT1020G3 intended
for fire alarm, fault and disablement presentation, etc. The FBP
compromises the top part of the front display.
Intended for fire alarm presentation and for the fire brigade
personnel.
Control panel (CP)
A part of the FT1020G3 front display, intended for fire brigade or
service personnel, building officer, etc.
, to "communicate" with the
Control Unit / system. It comprises the bottom part of the front
display.
System / Installation
One or several control units connected via a TLON network (co-
operating control units).
Network / TLON® / LonWorks® /
Echelon / Node / TLON Conn. board
/ Channel / Backbone net / Router /
Repeater
Brief explanations to the words/expressions to be found in
connection with a "TLON Network". See also separate TLON
Technical description.
TLON® = TeleLarm Local Operating Network = a LonWorks®-
based network for communication between several control
units/nodes. The protocol is called LonTalk and the transmission
works with doubly- terminated bus topology (Echelon FTT-10).
To connect a control unit to a network, a TLON connection board
has to be plugged in each control unit. FT1020G3 also supports
a redundant TLON Network. In this case two TLON connection
boards have to be plugged in each control unit.
A network can be one channel (FTT-10) or several channels,
connected via routers. In TLON Network, subnet = channel.
Routers are used for safety reasons in a single TLON
Network (up to six control units per channel). Routers can also
be used to increase the distance (cable length) between the end
nodes in a channel.

12
Operation Manual
FT1020G3 Rev 2.10.4
Router or Repeater is the same type of unit (different
configuration). All network programming (configuration) is
configured using the PC program “TLON Manager”. See also
separate TLON Manager Technical Manual.
Nuisance alarms
False or unwanted alarms
LED
LED (Light Emitting Diode) = Yellow, green or red optical indicator
("lamp").
External Indicator / RIL
A unit with a red LED connected to a base (ASB / CDB) or a
detector with an output for a remote indicator RIL.
Lit when the built-in LED in the detector / base is lit.
Display / LCD
LCD (Liquid Crystal Display) = Display (in the FDCIE or Display
unit) for presentation of fire alarms, fault messages, etc. In
FT1020G3 it is a graphical monochrome LCD (320 x 240 dots)
with backlight.
Door open (Door / Key switch)
In FT1020G3 there is a door switch, which is activated when the
FDCIE door is open. Door open feature can be used to disable
fault, strobes or OWS.
An open door is indicated in the LCD (i.e. an "open door" icon).
Site Specific Data (SSD)
The SSD is unique for each system. All alarm points, presentation
numbers, user definable alarm texts, programmable outputs, etc.
are created in the PC program EBLWin and also downloaded in
FT1020G3 unit(s) with EBLWin.
Software (S/W) / Firmware / System
program
The software (S/W) – also called Firmware and System program –
makes the control unit (the microprocessor) work. It is factory
downloaded but another / new version can be downloaded in
FT1020G3 on site using the PC program EBLWin.
EBLWin
PC program used to create and download the SSD in FT1020G3
unit(s). Also used to download another / new software version and
to upgrade the maximum number of alarm points in FT1020G3.
Can be used during commissioning / maintenance of FT1020G3
system (auto address, check loop, acknowledge faults, etc.)
Web-server / Gateway
The Web-server / Gateway is used to get FT1020G3 information
as well as remote control via a PC (browser) and an intranet /
internet. The Web-server / Gateway is configured via the PC tool
EBLWin.
EBL Firmware Manager PC program, used to download another / new software version.
Multi master system
Each control unit in a network has access to all information.
Note: The TLON configuration must be performed prior creating the Site Specific Data
(SSD).

13
Operation Manual
FT1020G3 Rev 2.10.4
2 General Description
2.1 The FT1020G3 FDCIE
FT1020G3 is a microprocessor controlled intelligent fire alarm system, intended for
analogue addressable detectors, as well as conventional detectors and manual call points.
Four loops are available to connect addressable units e.g. On each COM loop it is possible
to connect up to four SUB-loops.
Programmable control outputs and output units are available.
Up to 1012 addresses can be connected to each FT1020G3. Figure 1 below presents an
overview of the FT1020G3 system.
Programmable control outputs and output units are available.
FT1020G3 is available in several types e.g. large FT1020G3L and small FT1020G3S,
cabinets, versions and configurations. It can be used as a standalone FDCIE or connected
to a TLON network, i.e. in a "system", with up to 30 Control Units. Each Control Unit has
access to all information.
FT1020G3 is designed and assessed to the Australian Standard AS7240.2, AS7240.4 and
NZS4512:2010. The Fire Brigade Panel controls are incorporated as part of the front fascia
and conforms to AS4438.3.
Figure 1 Connection diagram of FT1020G3
Note: Some units are not available for the Australian market e.g. exit emergency light
MX140, aspirating unit AE2010G-P. other units are currently not approved e.g. 4466, 4585,
4464, etc.
Technical Number
The technical number, NNNNNN, is used when programming all units connected to the
COM loops. Technical number is also used to identify which unit has generated a fault. See
section 7.1, page 47.
Presentation Number
Each fire alarm point / input / zone has a presentation number, NNN-NN. The presentation
number is shown in the FDCIE display to identify the point / zone activating fire alarm. See
section 7.2, page 47.
1202
1201
1203

14
Operation Manual
FT1020G3 Rev 2.10.4
2.2 Com Loop Units
Addressable COM loop units are connected directly to a COM loop.
2.3 Address and Mode
The addressable units must have both address and mode set. This is done in different ways
for different units, for example address setting tool 4414E, DIP switches, jumpers, or via
the FDCIE display. For more information, please refer to the Technical Description of each
unit respectively.
2.4 Software (S/W) Versions
Due to continual development and improvement, different S/W versions may be found.
When installing a new Control Unit in a system with "older S/W" Control Units, you must
upgrade the S/W in the old Control Units with the current S/W or downgrade the new
Control Unit software by downloading the same older S/W version in the new Control Unit.
The same S/W version is required in all Control Units in a TLON Network
2.4.1 EBLWin
The PC program EBLWin is used for programming and commissioning of one or more
Control Units.
EBLWin Key 5094 is a USB dongle that has to be plugged in the PC in order to log on to
the FDCIE.
2.4.2 TLON Manager
TLON Manager is an installation and maintenance tool used for the TLON Network
programming and setup, it is Windows based PC software.
2.5 Applications
The FT1020G3 system is intended for small, medium and large installations. The intelligent
Control Units offer the system designer and end user a technically sophisticated range of
facilities and functions.
Programming with the PC programs EBLWin and TLON Manager and commissioning of
the Control Unit / system is an easy process. Start with one Control Unit and then, when
required, add more units. The TLON network allows the installer to install the Control Units
in one building or in different buildings.

15
Operation Manual
FT1020G3 Rev 2.10.4
3 Fire Detection Control & Indicating Equipment
(FDCIE)
3.1 FT1020G3 Specifications
Table 2 Control unit specifications
Item
Specifications
Mains Voltage 230VAC (195-253), 2 A
System Voltage 24VDC @ 6.5A
Current Consumption
Quiescent / alarm current is calculated by EBLWin and is
dependent on other equipment fitted in FT1020G3, type and
number of expansion boards, connected external equipment, etc.
Ambient Temperature (⁰C) Operating 0 to + 40, Storage -40 to +70
Ambient humidity (%RH) Maximum 90, non-condensing
Cabinet Size (mm)
Small 19” cabinet 13U, 700H x 600W x 250D
Large 19” cabinet 22U, 1050H x 600W x 250D
Battery box 19” cabinet 6U, 350H x 700W x 250D
Enclosure Material 1.5 Zinc annealed steel
Enclosure Colour Oyster, ripple finish
Approvals AS7240.2:2018, AS7240.4:2018, AS4428.3:2020 and
NZS4512:2010
Standard Inputs / Outputs1
Four COM loops (0-3), each loop can connect up to 253 devices
Four programmable non-supervised / supervised inputs (N/O or
N/C) I0-I32
Four Programmable Supervised Voltage Outputs, 0.5 Amp each
Two Programmable Relay Outputs, contact rating 2 Amp
Two non-programmable relay outputs for ASE (fire & fault)
Six x 24VDC outputs for Web server, ASE, Remote Display Units,
external applications 0.5 – 3.15 Amp.
Expansion Boards Max. 6 of 4580 or 4581 or a combination3
of both.
I/O Matrix 4582 board
Max. 24, 6 per COM loop if no Expansion Boards on Loop 04
fitted. Up to 6 modules can be used as zone or generic + 18 Fan
Control Modules (4 fans per module)5
Note: I/o matrix 4582 is now integrated in the new zone control 1205, fan control 1206 and
damper control 1211 modules, same limitations apply. Refer to Chapter 5, page 28.
1Refer to G3 block wiring diagrams shown in chapter 34, Figure 24 page 176
2First input I0 cannot be used in NZ convention, only 3 programmable inputs are available.
3Expansion boards are internally connected to COM loop 0, ensure total number of Expansion Boards and
modules with built-in I/O matrix connected to COM loop 0 does not exceed 6.
4Reduce the number of modules containing 4582 connected to COM loop 0 by one for every Expansion Board
used.
5If no Expansion Boards fitted, up to 24 fan/damper control modules can be used i.e. 96 individual fan/damper

16
Operation Manual
FT1020G3 Rev 2.10.4
3.2 FT1020G3 Limitations
Some limitations have been increased as well as adding new types. The following table
lists some of the limitations in V2.10.x software.
Table 3 Control Unit limitations
Item Loop FDCIE
Network System
General fire alarm via programmable input 100 30 x 100
External fault via programmable input 100 30 x 50
Programmable inputs 512 30 x 512
Programmable outputs (= control expressions) 512 30 x 512
Technical warnings 200 30 x 100
Addressable 2 voltage outputs unit 3364 40 30 x 40
Interlocking Combinations 400 4000
Presentation numbers / alarm points that can be presented
in the display(s) in case of fire alarm 255 512 512
Presentation numbers that can be programmed
512
30 x 512 = 15 360
Zones that can be programmed
255
512
999
Zone Group 64 64
Faults 300
Disabled Zones 512
Disabled Alarm Points (zone/address) + Disabled COM loops 2006
Disabled Outputs 2007
Disabled Interlocking Outputs 200
Sensors activating SERVICE signal 200
LAA zones (Max. 5 detectors per AAF zone.) 100 30 x 100
Total number of Expansion Boards 4580 and 45818
6
30 x 6
Number of I/O Matrix Boards 4582924 30 x 24
Total number of 4582 for Zone Control & Generic applications
6
30 x 6
Maximum number of remote display units 5054 (1728 / 1736) 30 30 x 30
Maximum number of 19” rack fan/damper modules with built-
in 4582 (4 fan/damper for each module) 24 30 x 24
Maximum number of 19” rack zone modules with built-in 4582
(15 zone)
6
30 x 6
Note: The addresses 254 and 255 in each loop are reserved for auto addressing purposes and
cannot be used. If these addresses are used there will be a fault in the "Validity check".
6Zone/address disabled via time channel not included.
7Control outputs disabled via menu H2/B3 and Alarm devices disabled via menu H2/B4 are not included.
8Expansion boards 4580 and 4581 are physical connected to COM loop 0
9Reduce no. of 4582 boards by one for every Expansion Board used (4580 or 4581), applicable to 19” rack
modules for zone control and fan / damper control.

17
Operation Manual
FT1020G3 Rev 2.10.4
3.3 FT1020G3 FDCIE Layout
The FT1020G3 is available in many configurations depending on the number of options fitted
in the FDCIE. The 19” rack cabinet 22U style is shown in Figure 2 below.
Figure 2 FT1020G3 with Optional OWS and Control/Display Modules
The cabinet is fitted with different options e.g. Occupant Warning System (OWS), Zone
Control Module, Fan/damper control module, 1200 series ancillary modules, MCP, etc.
Refer to the general arrangement in Figure 22 page 174.
The appearance and functions of FT1020G3 may vary depending on the number of optional
modules fitted.
Note: Custom’s hardware is required to add the options.
The 19” rack FT1020G3 22U Control and Indicating Equipment (FDCIE) shown in Figure 2
is housed in an oyster coloured powder coated metal cabinet. The cabinet has an inner
metal door and acrylic outer door. The outer door is fitted with 003 keys to provide access
level 1 and is made of tinted high impact acrylic which allows for easy viewing of all
indicators and controls. The appearance of the FT1020G3 might vary based on the number
of options fitted, cabinet size, additional battery enclosure, etc.
Access to the inner door is gained by opening the outer door which then provides access
to the inner door fixing screws. Opening the inner door allows access to the Control Unit
hardware for the purpose of maintenance or service.
Each FT1020G3 has the following basic configuration:
•Metal cabinet powder coated oyster with smoky acrylic door as shown above.
Different sizes available.
•MMI board 5015, see Figure 11 page 32.

18
Operation Manual
FT1020G3 Rev 2.10.4
•Main board 5012, see Figure 9 page 30.
4 x COM loops (0-3) to which the loop units are connected, refer to Figure
24 page 176.
4 x programmable supervised voltage outputs (S0-S3), refer to Figure 24
page 176.
2 x programmable relay outputs (R0-R1), refer to Figure 24 page 176.
4 x programmable supervised / non-supervised inputs (I0-I3), refer to Figure
24 page 176.
6 x 24 V DC outputs (power supply outputs for Web-server / Gateway, ASE
and external equipment), refer to Figure 24 page 176.
2 x non-programmable relay outputs for ASE, Fire brigade tx (alarm) and
Fault tx (fault). Fault relay is normally energised, see Figure 24 page 176..
Space & connectors for two TLON connection boards (5090).
RS485 and 24 VDC outputs for Display Units, refer to Figure 24 page 176.
Connector for expansion boards (4580 & 4581), refer to Figure 24 page 176.
Connectors for Web-server / Gateway, refer to Figure 24 page 176.
Connectors for power supply and batteries, refer to Figure 24 page 176..
•Power supply, refer to Figure 24 page 176.
Switch mode power supply, 230 VAC / 24 VDC (LS150-24).
Space and connection cables for two Sealed Lead-Acid backup batteries.
Optional 6U height battery box is available for additional batteries.
Battery temperature sensor.
•Space for up to six expansion boards 458x.
Note: Some drawings shown in Chapter 34 page 173, others are shown in a separate
drawing document
3.4 Front Display
Figure 3 FT1020G3 front display
P1
P2
P3
P4
P5 - P8
L1
L2
L3
L4
L5
L6
L7,L8
L11,L12
L9,L10
L13,L14
P9

19
Operation Manual
FT1020G3 Rev 2.10.4
Note: “Alarm Routing Activated” LED will be replaced by “ASE Activated” in the revised
front to fulfil AS4428.3:2020
The Fire Brigade Panel (section framed by red boarder) is integrated in the main FT1020G3
front display. FBP is normally used by fire services personnel to investigate which alarm
point / zone(s) have activated a fire alarm and take the required operational control of the
system. Fire brigade personnel can control active alarms via the buttons and keys P1-P4
and P9 within the FBP. P5 – P8 buttons are used to navigate the menu. In the graphical
display, the information displayed in the upper part is dependent on how many alarm points
/ zones have generated fire alarm. In the middle part, the fire alarms will be shown, i.e. one
alarm point or one zone together with a user definable alarm text (if programmed) plus
some other information.
The Control Panel CP is used to "communicate" with the system, i.e. for commissioning,
monthly tests, maintenance, etc. Access code for different access levels is required. To get
access to the system (a menu tree with main and sub menus) and for operational control
of the system, up to ten User names can be used for three different User level types. A
Password (six digits) for each user name is required to logon to the panel and Webserver.
3.4.1 LED Indicators and Push Buttons
LED’s and push buttons are contained on the front panel display and are described
in the tables below. See also Figure 3above, for the LEDs and push buttons.
3.4.1.1 Fire Brigade Panel Display and Control
Table 4 LED indicators and push buttons on Fire Brigade Panel (FBP)
No Label Colour Indicating / Action
L1
Fire
5xRed
Fire alarms. See chapter "Alarm types", page 57.
L2 Fire Protection
Activated Red
Output(s) for extinguishing (suppression) equipment
activated. (Or a programmable input type "Extinguishing" is
activated.)
L3 Smoke Control
Activated Yellow
Output(s) for smoke control ventilation equipment (AS1668)
activated (fan / damper). Or a programmable input type
"Ventilation" is activated.
L4 ASE (Alarm Routing)
Activated Red
Output "Fire alarm" for Fire Brigade TX and/or
corresponding programmable output(s) of type
"FireBrigadeTx") is/are activated (or a programmable input
type "Activated routing equipment" is activated.) or testing of
routing equipment in progress.
L5 Power Green
Steady: FDCIE is powered via the primary power supply
and/or the battery.
Flashing: FDCIE start up.
L6 Several Alarms 2xRed
Multiple units / zones have activated fire alarm. Use push
button "Several Alarms" (P9) to scroll amongst the alarm
points (zone-address) or soft key "Next zone" (P6) to scroll
amongst the zones.
P1
Silence Buzzer
White
Used to silence the buzzer in the FDCIE when it is sounding
P2 Silence Alarm Red
Used to silence alarm devices e.g. OWS / sounders in the
building when they sound. Silenced alarm devices is
indicated to the right in the display's soft key area (a symbol
near this button), see Table 6page 21.
P3 Reset Green
Used to reset fire alarms, only after all fire alarms have been
silenced, see "Fire alarm reset", page 68.
Note: P3 has to be pressed for > 0.5 sec.
P4 Disable Yellow
Used to disable active alarm(s), all outputs of the device or
zone in alarm will be disabled and reset after fire alarm
devices have been silenced.
P5
to
P8
Soft keys Grey
Operation/function is shown above each key in the display
i.e. soft key area. The function of a soft key may vary
depending on the FDCIE condition. If no text is shown above

20
Operation Manual
FT1020G3 Rev 2.10.4
the key in the display, the key has no function10
P9 Several Alarms Grey
Used when LEDs "Several Alarms" (L6) are lit, scroll
through the queued alarm points or zone-addresses. For
more details, see chapter "Fire alarm" page 58.
Note: To scroll/browse through the queued zones, use
the soft key "Next zone" (P5).
3.4.1.2 FT1020G3 Display CP Indicators
Table 5 LED indicators on Control Panel (CP)
No.
LED Indicator
Colour
Indicating
L7 System fault Yellow
FT1020G3 is not running due to one of the following:
•S/W fault
•CPU fault
•Memory fault
•No contact between main board and MMI board
•FDCIE restart (fault code ≠ 00 / 03 / 25 / 50 / 53)
L8 Test mode Yellow One or more zones are in "test mode", see page 110 &
148.
Fault / Disablements
L9 General fault Yellow Fault(s) in the system, i.e. not acknowledged fault(s) and /
or not corrected fault(s)11. See also page 146.
L10 General
disablements
Yellow Disablement(s) in the system.
L11 Alarm devices Yellow
Steady: Output(s) type "Alarm devices" are disabled.
Flashing: Output(s) type "Alarm devices" have generated
fault(s).
This is also valid when the FDCIE has no "contact" with a
unit with such an output, e.g. 3379, 4487, etc.
L12 Fire brigade TX Yellow
Steady: Output(s) for "ASE" disabled12 via menu (H2/B5).
Flashing: ASE (routing equipment) power supply output13
or one or more supervised outputs (of type "Routing
equipment" have generated fault(s). This is also valid
when the FDCIE has lost "contact" with a unit with such an
output, e.g. 4461.
ASE (routing equipment)
L13 Fault TX
activated
Yellow
One or more of faults not serviced 14.
Output "Fault condition" for fault TX (routing equipment) is
activated.
Test of routing equipment in progress (see menu H1).
Sensitive fault detection mode is on (see menu H5/A2).
L14 Fire brigade TX
delay Yellow The Alert Annunciation function is enabled.
Note: Acknowledged alarm and isolated alarm are used only in the NZ convention.
10 The soft key “P8” has the function Alert Annunciation Acknowledge, if a COM loop unit is configured for alert annunciation.
11 Serviced fault will clear if the fault is set to non-latching in the system properties
12 Serviced fault will clear if the fault is set to non-latching in the system properties
13 Main board 5012 Terminal Block "J3:3-4", fuse F8 (T500mA 250 V – 5 x 20mm Ceramic).
14 See also chapter “Fault acknowledge”
Other manuals for Firetracker FT1020G3 CIE
1
Table of contents
Other Panasonic Fire Alarm manuals

Panasonic
Panasonic MEW01349 User manual

Panasonic
Panasonic EBL128 User manual

Panasonic
Panasonic EBL512 User manual

Panasonic
Panasonic EBL512 G3 5000 User manual

Panasonic
Panasonic EBL512 User manual

Panasonic
Panasonic EBL512 User manual

Panasonic
Panasonic 3314 User manual

Panasonic
Panasonic MEW01091 User manual

Panasonic
Panasonic 4479 User manual

Panasonic
Panasonic EBL128 User manual