Panasonic CZ-ESWC2 User manual

When installation work is completed, perform a test run and check that no
trouble occurs. Also be sure to explain the methods for using the product to
the customer, based on the contents of the Operation Manual. In addition,
request that the customer keep and conveniently store the “Information for the
Person in Charge of Installation (Electrical) Work and Servicing” together with
the Operation Manual.
Depending on the installation location, it may be necessary to install an
earth leakage breaker. Failure to do so may result in electrical shock or fire.
Do not install in kitchens, workshops, or other locations where there is oil
mist in the air.
Do not install next to windows or in other locations exposed to direct sun-
light or in direct contact with outside air.
Do not install near an elevator, automatic door, industrial sewing machine,
or other devices that can be expected to produce electrical noise.
(with current fuse) *1
T10 relay wire *2
Power wire for
connection to
system controller
1
2
3
4
5
6
7
8
1
1
1
2
2
7
1
1
1
Q'ty Q'ty
Operating
Instructions
Wire joints
No. No.
Supplied parts Supplied parts
Spacers
Label
9
Earth screw for T10
(for indoor unit)
4x 8 - 3
Screws
T10 power wire
M4 x 25
Accessories for Schedule Timer
Indoor unit control PCB
T10 connector (6P, yellow)
1. Power wire 2. Relay wire
Fig. 1
Fig. 4
Fig. 6
Fig. 3
(For connected
installation)
Remote controller
wiring outlet
Electric jinction box
More than
95 mm More than 125 mm
(From wall)
More than
95 mm
More than
125 mm
(From wall) (For connected
installation)
Remote controller
wiring outlet
Electric jinction box
* For maintenance reasons, leave a gap of 25 mm or more between the
remote controller switch and schedule timer if they are arranged in
parallel above/below each other.
1-1 1-2 2-21-3 2-3
2-1 3-1
System 1 System 2 System
3
Schedule timer
Inter-unit control
wiring
Wiring the Schedule Timer
Before beginning wiring
– Use0.5–2mm
2wires for field supply wiring.
–
–
For inter-unit control wiring, use signal wires that allow the
remote controller wiring to be differentiated from the power
wiring, and take care to prevent miswiring. (Miswiring will
damage the schedule timer.)
– Check that the schedule timer communications wiring and
power wiring are connected correctly. (Fig. 5)
<Basic Wiring Diagram>
Route the A/C inter-unit control wiring for central control as
shown in the figure below.
The maximum number of indoor units that can be connected to
a single system is 64. The maximum number of outdoor units is
30.
The maximum number of schedule timer units that can be con-
nected is 8. (A maximum of 10 schedule timer units and other
central control devices can be connected.)
WARNING
CAUTION
*1
*2
Installing the Schedule Timer
<Note 1> Avoid twisting the inter-unit control wiring or the input/out-
put wiring together with power or other wiring, and avoid
running them in the same metal conduit. Doing so can
cause malfunction.
<Note 2> Install the schedule timer at a location away from any
sources of electrical noise.
<Note 3> Install a noise filter or take other appropriate action if elec-
trical noise affects the power supply circuit of the unit.
(1) Open the panel on the schedule timer unit. Insert a standard (flat-
head) screwdriver or similar tool into the notches on the bottom of
the schedule timer unit to open and remove the back case.
(2) Use the 2 supplied M4 small screws and install the schedule
timer back case onto the switch box. Before installing, use a
screwdriver or similar tool to press on and open the screw holes
that correspond to the Electric jinction box that is used.
When fastening the case, use spacers and do not tighten the
screws too much. If the schedule timer does not fit tightly against
the wall, cut the spacers as required to make adjustments.
(3) Connect the supplied power wire (2-core) and inter-unit control
wire (3-core) to the schedule timer unit.
(Refer to “Wiring the Schedule Timer.”)
(4) Align the schedule timer unit with the tabs on the back case and
press to install it.
Installation of connected schedule timers
When installing schedule timers (remote controller switches, system
controllers, etc.) onto the wall, use the method shown in Figs. 3 and 4.
If power is supplied from the indoor unit control PCB of a nearby
indoor unit, connect the provided T10 terminal connection wires to
the T10 terminal on the indoor unit control PCB, and to the sched-
ule timer power wires.
The inter-unit control wiring has no polarity. The wiring may be
connected in either direction to U1 and U2. (Use shielded wiring)
If necessary, use a relay wire when connecting the wiring to the
indoor unit control PCB.
The power wiring has no polarity. The wiring may be connected
in reverse. (Use shielded wiring)
The length of the power wiring must be no more than 100 m.
<Note> The only functions of the schedule timer are indoor unit
ON/OFF and remote controller enable/disable operations. It
is therefore recommended that during installation, a sys-
tem controller, remote controller, or similar device be
installed next to the schedule timer so that the operation
mode and other information can be checked.
(If the system controller or other central control device is not
present, the schedule timer cannot be used in combination
with a system that does not utilize remote controllers.)
Wiring
The schedule timer wiring can be connected by the following two
methods. Select one of these connection methods according to the
actual installation location.
When wiring, extend the lengths of the wires using wire joints (pro-
vided) and extension wires (field supply).
When installing multiple schedule timers,
avoid the use of cross-over wiring.
Connection diagram (Be sure to use the provided wires as the
power wiring.)
If a system controller is also installed:
Connect the wires for the schedule timer inter-unit control wiring (see
Note below) to the U1 and U2 terminals on the system controller ter-
minal board. Connect the system controller power wiring to CN02
and to the schedule timer power wires (white + black).
The inter-unit control wiring has no polarity. The wiring may be
connected in either direction to U1 and U2. (Use shielded wiring)
The power wiring has no polarity. The wiring may be connected in
reverse.
The length of the power wiring must be no more than 100 m.
Note: The inter-unit control wires are pink + blue + blue (using
wire joint crimping). Use pink + blue wires.
If a system controller is not installed (power is supplied from
the indoor unit):
<Note> Depending on the model of A/C, a local adapter may be
required.
Safety Precautions
Read these Safety Precautions before beginning installation or electrical
work, and perform the work only in the correct manner.
Precautions in this manual are given in the form of “Warnings” or
“Cautions.” Both types of precautions contain important information relat-
ed to your safety, the safety of users, and the correct operation, installa-
tion, or maintenance of the air conditioning system. Be sure to carefully
observe all relevant precautions.
This symbol refers to a hazard or unsafe practice
which can result in severe personal injury or death.
This symbol refers to a hazard or unsafe practice
which can result in personal injury or product or
property damage.
WARNING
CAUTION
CAUTION
INSTALLATION INSTRUCTIONS(CZ-ESWC2)
INFORMATION FOR THE PERSON IN CHARGE OF INSTALLATION (ELECTRICAL) WORK AND SERVICING
When mounting the back case to the electric junction box,
tighten the screws securely until the screw heads touch the
back case. Otherwise, a loose screw head may damage the
PCB on the back of the top cover when mounting the top
cover. But do not over-tighten the screws. Overtightening
may deform the back case and cause the unit to fall.
Request installation and electrical work only from the dealer or a qualified
air conditioning specialist.
Attempting to carry out installation work on your own, and doing so incor-
rectly, may result in electrical shock, fire, or other hazards.
Installation procedures must be performed correctly, carefully following
the instructions in this document.
Failure to do so may result in electrical shock, fire, or other hazards.
Electrical work must be performed by a qualified electrician. It must be
performed in accordance with technical standards related to electrical
equipment, interior wiring requlations, local codes, and the contents of
these instructions.
Insufficient power circuit capacity or improper electrical work may result in
electrical shock or fire.
Use only the designated cables for wiring, and connect them securely. Fasten
cables so that no external force is applied to the terminal connections.
Insufficient connections or cable fastening may result in heat generation,
fire, or other hazards. Fig. 2
M4 x 25 small
flat-head screws (2
Wiring for earth (green) *3
)
Spacer
Under-case
(back case) Electric jinction box
Decorative cover
(panel)
Schedule
timer unit
1
Do not allow a screwdriver or other
metal object to touch the PCB
terminals when the power is ON.
Pre-
cautions Power
terminal
(remote
controller
terminal)
Permitted items for
controller operation
Permit all modes
Permit the below items only
Prohibited items for controller operation
Current-time synchro-
nization communication
Temp.
setting Opr.
mode Start/
Stop
Remote controller prohibit
not used.
Schedule timer address
Timer group setting
Connected device
Communi-
cations
terminal
All switches are
OFF when the unit
is shipped.
: OFF
: ON
1Gr
fixed
2Gr
fixed
3Gr
fixed
Manual
assignment
2
3
1
5
6
7
12345678
2
3
4
Inter-unit
communication Remote controller
(4 wires)
Communications wiring
(Inter-unit control wiring)
Power wiring
Wiring outlet
Fig. 5
Fig. 7
Schedule
timer
Field supply
Field supply
(Use shielded wiring)
Communication
wiring
(pink + blue)
Power wiring
(white & black)
Wiring for earth
(green)
System controller
(Back side)
Inter-unit control wiring
(Use shielded wiring)
Fig. 8
T10
U1 U2
Indoor unit control
PCB
Inter-unit
1
Earth screw for T10
cable (Supplied parts 9).
Be sure to disconnect
the .
control wiring
Schedule
timer
Communication
wiring (pink + blue)
Power wiring
(white + black)
Indoor unit
Under-case
(back case)
Wiring for earth
(green)
Field supply
(Use Shielded Wiring)
*3 For used in North America, remove the wiring for earth (green)
on the back case.
Use shielded wiring for Inter-unit control wiring and power
wiring(T10). (Except North America)
Use it according to the form of T10 connector.
If the fuse blows as are sult of a wiring short-circuit, miswiring, or
overcurrent, replace it with a 125 V, 0.5 A fuse.

OFF ON
S41
1
2
3
4
5
6
7
8
OFF OFF
OFF ON
ON OFF
ON ON
OFF ON
S42
1
2
3
4
5
6
7
8
OFF OFF
OFF OFF
OFF ON
OFF ON
ON OFF
ON OFF
ON ON
ON ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF OFF
OFF OFF
OFF ON
OFF ON
ON OFF
ON OFF
ON ON
ON ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
Spare (1)
Be sure that these switches are OFF
when the system is used.
What is a timer group?
This is a group of indoor units, created by
dividing the central control addresses of the 64
indoor units that are connected to the inter-unit
control wiring, and assigning a timer program to
each group.
Timer Group Settings (2, 3)
Function
Function
23
1 timer group – fixed
4 timer group – fixed
8 timer group – fixed
Manual group setting
Central Control Main/Sub
Switching (4)
Sub: OFF
Main: ON
(1) Set to “sub” (OFF) when using together with the AMY
adapter, communications adapter, intelligent
controller, multi-controller, LON I/F, and system
controller.
(2) In cases other than (1) above, when using together
with an ON/OFF central controller, set to “main” (ON)
when only 1 schedule timer unit is used.
(3) In cases other than (1) above, and when using with
multiple schedule timer units, set only 1 unit to “main”
(ON) and set the remainder to “sub” (OFF).
Schedule Timer Address Settings (5, 6, 7)
A maximum of 8 schedule timer units can be connected to the inter-unit
control wiring. If multiple units are connected, use the setting switches
and allocate the addresses, taking care to avoid duplication.
567
Address 1
Address 2
Address 3
Address 4
Address 5
Address 6
Address 7
Address 8
Holiday and Operation Disable Settings for Each Group (8)
When this setting switch is OFF, units are all controlled together. When this
switch is ON, the units are controlled by the settings for each timer group.
* These switches
are all OFF at
the time of
delivery.
* These switches
are all OFF at the
time of delivery.
If remote controller enable/disable is used,
this switch sets the range for remote
controller enable (cancel).
Enable all items* that can be controlled
with the remote controller.
oOFF
Enable only the items determined by
setting switches 2, 3, and 4.
oON
This switch should be OFF for normal use,
or when remote controller enable/disable is
not used.
Remote Controller Enable Items (1)
* This refers to the following items: start/stop,
operation mode, temperature setting, flap,
and fan speed.
Spare (6, 7, 8)
Temperature setting + Operation mode + Start/stop
Remote Controller Disable Item Switches (2, 3, 4)
When timer remote controller disable is used, set the remote controller
disable item switches according to the items for which remote
controller operation will be disabled.
Remote controller disabled items 234
Remote controller disable not used
Start/stop
Operation mode
Operation mode + Start/stop
Temperature setting
Temperature setting + Start/stop
Temperature setting + Operation mode
Central 1 – 4 are the designations for the remote-controller disable
modes for the system controller.
Central 1
Central 4
Central 2
Central 3
When multiple schedule timers are installed, set this switch to ON to
perform time settings for multiple units simultaneously. One minute
after the time is set, the time at the other schedule timers will change
to match the set time. (Ordinarily this switch is OFF.)
Simultaneous time communications (5) Disabled: OFF Enabled: ON
Be sure that these switches are OFF when the system is used.
12
17 18
33 34
49 50
8
24
40
56
9
25
41
57
10
26
42
58
16
32
48
64
[Setting fixed timer groups]
Schedule timer
1 fixed timer group (64 units together)
4 fixed timer group (16 units together)
8 fixed timer group (8 units together)
Central control address 1 – 64
Central control address 1 – 16
Central control address 1 – 8
Central control address 17 – 24
Central control address 17 – 32
Central control address 33 – 40
Central control address 33 – 48
Central control address 49 – 64
Central control address 49 – 56 Central control address 57 – 64
Central control address 41 – 48
Central control address 25 – 32
Central control address 9 – 16
ON
OFF
Backup switch
Backup battery
Room name
1
Schedule timer
Fixed timer group
Central
control
addresses
Indoor unit
Unit No.
System - Indoor
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
1
2
3
4
5
6
7
8
4
3
2
1
148
At the
time of
shipment
-
,
-
-
,
-
-
,
-
-
,
-
-
,
-
-
,
-
-
,
-
-
,
-
-
,
-
-
,
-
-
,
-
-
,
-
-
,
-
-
,
-
-
,
-
-
,
-
-
,
-
-
,
-
-
,
-
-
,
-
-
,
-
-
,
-
-
,
-
-
,
-
-
,
-
-
,
-
-
,
-
-
,
-
-
,
-
-
,
-
-
,
-
-
,
-
-
,
-
-
,
-
-
,
-
-
,
-
-
,
-
-
,
-
-
,
-
-
,
-
-
,
-
-
,
-
-
,
-
-
,
-
-
,
-
-
,
-
-
,
-
-
,
-
-
,
-
-
,
-
-
,
-
-
,
-
-
,
-
-
,
-
-
,
-
-
,
-
-
,
-
-
,
-
-
,
-
-
,
-
-
,
-
-
,
-
-
,
-
-
,
-
About the Setting Switches
Complete the switch settings before turning ON the schedule timer
power.
Memory Backup Switch
After installation is completed, check that the backup switch on the
reverse side of the schedule timer PCB is turned to ON.
(The backup battery will retain the current time for up to 100 hours.)
Installation Work Plan
Use the wired remote controller to check the unit No. of the indoor
units.
(Start the A/C unit with the wired remote controller, then press the
remote controller UNIT SELECT button once to display the unit
No. of the master unit.)
Explanation to Customers
After work is completed, present the Operation Manual and
Information for the Person in Charge of Installation (Electrical) Work
to the customer.
Explain to the customer the methods for use of the system, as
described in the Operation Manual.
Checking the Central Control Addresses and Operating
the Units that are Controlled by the Schedule Timer
The schedule timer communicates with the indoor units to check which
central control addresses can be controlled with the current timer control.
The schedule timer can then be used to start and stop these units.
(1) Press and hold the schedule timer button, button,
and CLEAR button for 4 seconds or longer. “Ad-(central control
address)” appears in sequence, blinking.
(2) Use the GROUP button in the area to display the blinking central
control addresses in sequential order. In this way, it is possible to
check which central control addresses in the displayed timer group can
be operated by the timer.
(3) With the selected timer group displayed, press the timer but-
ton. Each time the button is pressed the indoor units in the displayed
timer group start or stop. Pressing the button in this mode
permits all items (operation start/stop, operation mode, temperature set-
ting items) at the indoor units in the displayed timer group where remote
controller prohibit is in effect.
(4) After checking the addresses and operating the units, press and hold
the button for 2 seconds or longer. The schedule timer dis-
play returns to the normal display and all controllable indoor units stop.
Creating Timer Groups
The schedule timer can be set for 6 time status changes. These can be
used to create up to 8 groups (timer groups). For systems in which sched-
ule timers are used, set the timer groups to match the central control
addresses of the indoor units that will be subject to group timer control.
The timer-group settings for the schedule timer involve assignment of
central control addresses. Therefore, use the system controller (or other
central control device) or wired remote controllers to set the central con-
trol addresses of the indoor units, then make the schedule timer settings.
Procedure for making fixed timer group settings (fixed groups)
(1) First, use a different central control device (system controller or other
device) or the wired remote controllers to set the central control
addresses, as assigned in the figure above, to the indoor units that will
be subject to group timer control.
(2) Next, use S41 switches 2 and 3 to set the number of timer groups you
wish to create.
(3) Finally, turn ON the schedule timer power. Initial communications are
performed. (SCAn blinks in the display.) The normal display appears
after several minutes, and the timer group settings are confirmed.
Procedure for making manual timer group settings (manual
group assignments)
Manual timer group settings allow central control addresses to be assigned
freely within the timer groups.
(1) Turn ON S41 setting switches 2 and 3, then turn ON the power. Restart
and initial communications are performed. (SCAn blinks in the display.)
The normal display appears after several minutes.
(2) When the normal display appears, press and hold the schedule timer
button, the timer button, and the button for 4
seconds or longer. “Ad-01” appears, blinking, in the current time display.
(Ad indicates “address” and 01 is the central address number.)
(3) Use the button in the area to select the timer group. Then
use the button in the area to select the central control address
to assign and register for that timer group. Press the button
to register the selected central control address.
(4) To continue registering addresses, repeat step (3). (Central control
address numbers will be added to the right side of the LCD display.) To
cancel a registered central control address, use the button in
the area to select the timer group, then use the button in the
area to select the central control address and press the button.
(5) Repeat steps (3) – (4) for each timer group. When registration is com-
pleted, press the timer button. The schedule timer restarts
automatically and performs initial communications. (SCAN blinks in the
display.) The normal display appears after several minutes, and the
manually assigned timer group settings are confirmed.
85464369351012
Printed in Japan
Other manuals for CZ-ESWC2
2
Other Panasonic Timer manuals