Panduit M1 User manual

M1 Intelligent PDU Installation Manual
V1.1

2
M1 INTELLIGENT PDU INSTALLATION MANUAL
Table of Contents
Before You Begin................................................................................................................3
Overview.......................................................................................................................3
Important Safety Information.........................................................................................3
Required Tools..............................................................................................................5
Section 1 – Introduction .....................................................................................................6
Classification Overview.................................................................................................6
Features........................................................................................................................7
Form Factors ................................................................................................................8
Load Segment and Phase Distinction..............................................................................8
Section 2 –Installing the PDU...........................................................................................9
Vertical PDUs......................................................................................................................................9
Install Mounting Hardware..............................................................................................9
Install Bracket Hardware (BRK01 – Optional)..................................................................10
Vertical (0U) PDU– Single Installation......................................................................11
Vertical (0U) PDU– Two or More Installation............................................................11
1U PDUs............................................................................................................................................12
Mounting Hardware Installation................................................................................12
Grounding the PDU...........................................................................................................................13
Connecting the Ground Bonding Cable....................................................................13
Bonding.......................................................................................................................14
Section 3 –Connectingthe PDU.....................................................................................15
Connecting the PDU to a Power Source ....................................................................15

3
M1 INTELLIGENT PDU INSTALLATION MANUAL
Before You Begin
Overview
This document provides installation instructions and configuration instructions to
qualified personnel for installing a Panduit Metered, Switched, and Metered &
Switched Power Distribution Unit (PDU) into a datacenter rack. Please read all
instructions before operating the equipment and save this manual for future
reference.
Important Safety Information
See the complete regulatory compliance notices in Safety and Compliance Information
for Server, Storage, Power, Networking, and Rack Products on the Panduit website
(http://www.panduit.com/). In addition, follow the safety precautions that are specific to
this device.
This PDU is intended only for Information Technology Equipment (ITE) loads with
linear/Power Factor Corrected (PFC) input current. If non-linear loads are connected,
the nameplate current rating of the PDU must be reduced by a factor of 0.8.
WARNING: A risk of personal injury from electric shock and hazardous energy
levels exists. The installation of options and routine maintenance and service of this
product must be performed by individuals who are knowledgeable about the
procedures, precautions, and hazards associated with AC power products.
IMPORTANT SAFETY INSTRUCTIONS-----SAVE THESE INSTRUCTIONS
Follow these safety precautions when connecting multiple hardware
components to power sources
WARNING: To reduce the risk of fire, electric shock and damage to the
equipment:
HIGH LEAKAGE CURRENT. To reduce the risk of electric shock due to high
leakage currents, ensure that there is a reliable grounded (earthed)
connection before connecting power distribution products to AC power. If a

4
M1 INTELLIGENT PDU INSTALLATION MANUAL
Large number of products will be connected to a single PDU, it may be
necessary to conduct an evaluation of the installation to verify the total
amount of leakage current. The total combined leakage current should not
exceed 5 percent of the input current for the PDU and associated load.
Connect only to a circuit providing branch circuit overcurrent protection of
appropriate current rating.
Connect the input power cord to a grounded (earthed) electrical outlet that is
located near the equipment and is easily accessible.
Be sure all circuit breakers are in the off position before connecting input power.
Be sure that the devices connected to the Panduit PDU are adjusted for, or
otherwise capable of, operation from the same line voltage supplying the
PDU. Failure to verify the voltage can lead to severe equipment damage.
Do not overload the PDU. The total input current rating of all equipment
connected to each output cannot exceed the total output rating marked on the
PDU.
Use only the hardware provided to install the PDU.
To reduce the risk of fire or electric shock, install this PDU in a temperature and
humidity controlled, indoor environment, free of conductive contaminants.
Do not operate near water or excessive humidity (90% maximum
noncondensing).
Ambient temperature must not exceed 0°C to 60°C (32°F to 140°F).
The internal components can become extremely hot during operation. Allow
sufficient time for the PDU to cool before handling.
Do not use a two-wire power cord in any product configuration.
TO ISOLATE THIS EQUIPMENT, DISCONNECT THE POWER CORD.
DANGER: This PDU contains LETHAL VOLTAGES. NO repairs should
be performed on these units except for the replacement of the
management card. There are NO USER SERVICEABLE PARTS inside
the PDU. The installation of options, routine maintenance, and service of
this product must be performed by individuals who are knowledgeable
about the procedures, precautions, and hazards associated with AC power
products.
IT IS ESSENTIAL THAT THIS EQUIPMENT IS CONNECTED TO AN
ELECTRICAL SUPPLY.
For permanently connected PDUs, the installation must be performed by a licensed
electrician, must be connected to an AC power source that is current limited by a properly
rated circuit breaker or fuse meeting national and local electrical codes, and must be
connected to a protective earth ground.

5
M1 INTELLIGENT PDU INSTALLATION MANUAL
Required Tools
The following tools maybe required for installation:
.Phillips screwdriver
.Torx screwdriver

6
M1 INTELLIGENT PDU INSTALLATION MANUAL
Section 1 – Introduction
Classification Overview
The Panduit Essential Monitored, Switched, Monitored per Outlet, and Monitored &
Switched per Outlet PDUs (Power Distribution Units) are intelligent PDUs designed to
distribute power to IT equipment installed into a rack. These PDUs are single-phase
(1Ph) or three-phase (3Ph) models with electrical metering and switching capabilities.
Each PDU provides power distribution to IT loads through C13, C19 outlets. The
quantity and location of outlets vary by model. The PDUs allow you to connect and
manage these outlets from a single power connection. The PDUs can be managed
from a Web interface, or a Command Line Interface (CLI), and viewed from the local
display.
Panduit PDUs are designed for use with all Panduit cabinets and are compatible with
most third-party data center racks. The PDU models vary in form factor with several
mounting configurationsavailable.
Panduit Monitored PDU: Provides aggregate power monitoring to quickly identify
potential power issues and reclaim available or under-utilized power capacity.
Panduit Switched PDU: Provides aggregate power monitoring and outlet level
switching capabilities for individual outlets or a group of outlets. This PDU enables
power sequencing, rebooting equipment or restrict unauthorized use of individual
outlets.
Panduit Monitored per Outlet PDU: Provides outlet-level power monitoring to quickly
identify potential power issues and reclaim available or under-utilized power capacity
at the outlet level.

7
M1 INTELLIGENT PDU INSTALLATION MANUAL
Panduit Monitored & Switched per Outlet PDU: Provides outlet-level power
monitoring and outlet-level switching capabilities for individual outlets or a group of
outlets. Power monitoring at the individual outlet level provides actionable
management data on the power consumption of each connected IT device,
enabling the redeployment or decommissioning of individual servers to
reclaim available or under- utilized power capacity.
Features
The Panduit Monitored, Switched, Monitored per Outlet, and Monitored &
Switched PDUs provide the following features:
•Lower profile on Vertical PDUs – enhances serviceability area in the
back of the rack.
•Multiple mounting options on Vertical PDUs – can be mounted with
outlets facing in toward center of rack, back or front ofrack.
•Higher operating temperature – all Essential series PDUs rated for 60˚C
operating temperature.
•Color-coded outlets to circuit breakers – used to easily differentiate
load segments andphases
•1U PDUs support multiple mounting options – can be mounted
horizontal in a U space or in the True 0U space between the RETMA rails.
•Hot Swappable Network Management Module – allows power
distributionduring module replacementeliminatingdowntime.
•10/100 Ethernet – eliminates the need to manually set the network switch
to run at a slower rate
•Daisy Chain – able to network up to sixteen of the same PDUs on one IP
address.
•Enhanced Sensor Support – supports up to 2 physical sensors and four
measurements per PDU with a total of 128 measurements in a maximum
daisy chainconfiguration.
•Highly Visible LCD display – improves visibility while providing local
access to view configuration setting. Automatically enters sleep mode to
conserve energy and protect the display from burnin.

8
M1 INTELLIGENT PDU INSTALLATION MANUAL
Form Factors
Details of the form factors that are covered within this document.
Form Factor
Details
0U (Vertical)
Vertical PDUs come in Half, Mid, & Full-height versions
and install vertically in the 0U space in the back of the
rack. There are also Half and Full-height dual sided
models that install vertically in the 0U space in the back of the
rack.
1U
1U PDUs can be installed in a U position in the rack, or in the
true 0U space on the side of the rack between the
RETMA rails.
Load Segment and Phase Distinction
Panduit Essential PDUs have colored receptacles to help distinguish between the
different load segments and phases. All Panduit three phase PDUs have different
colored receptacles (white, dark gray, and black) to distinguish the different phases. All
Panduit PDUs with breakers have different colored receptacles to distinguish the
different load segments (with one exception as noted below). For single phase PDUs
with no breakers the receptacles are all black.
Single Phase PDU Example
Three Phase PDU Example

9
M1 INTELLIGENT PDU INSTALLATION MANUAL
Section 2 – Installing the PDU
Vertical PDUs
Panduit Vertical PDUs include the following form factors: half-height, mid-height, and full-
height models. This section covers the recommended installation methods
Install Mounting Hardware
Each vertical PDU has two mounting hole locations on the back of the PDU for the
button installation to assist with mounting in a non-Panduit racks. When installing the
mounting buttons, use either mounting hole as a set.
Mounting Button Installation – Outlets Facing the Center of the Rack
1.
Align and install the mounting buttons with the screw holes on the face,
opposite of thereceptacles.
2.
Install the PDU by inserting the mounting buttons into the keyhole slots on the
PDU mounting bracket in the rack.

10
M1 INTELLIGENT PDU INSTALLATION MANUAL
Install Bracket Hardware (BRK01 – Optional)
Each vertical PDU can install the optional bracket (BRK01) on the end of the PDU
when non-condition for installing the mounting buttons.
Bracket Installation – Outlets Facing the Center of the Rack
Each vertical PDU can install the optional bracket with provided screws on the end of
the PDU.
1.
Align and install the bracket with the screw holes on the end of PDU, fix with
provided screws.
2.
Install to the rack with provided four (4) M5x10mm self-tapping screws.

11
M1 INTELLIGENT PDU INSTALLATION MANUAL
Vertical (0U) PDU– Single Installation
A single vertical unit can be installed with the outlets facing the center (A) The pictures
below illustrate these installation methods.
(A)
NOTE: The above installation methods are true for all vertical models. Those units
can only mount on its side with outlets facing the back of the rack.
Vertical (0U) PDU– Two or More Installation
For two full-height (in a 42U/45U/48U rack), two mid-height (in a 42U/45U/48U rack),
or four half-height (in a 42U/45U/48U rack) vertical units to be mounted on one side
of the rack, all units must be installed with the outlets facing in towards the center of
the rack.
(A)
(B) (C)
NOTE: (A) Two full-height PDUs with outlets facing in towards the center of the rack;
(B)
Two mid-height PDUs with outlets facing in towards center of therack;
(C)
Four half- height PDUs with outlets facing in towards center of the rack.

12
M1 INTELLIGENT PDU INSTALLATION MANUAL
1U PDUs
Mounting Hardware Installation
1U PDU Mounting in a U Position of the Rack
1.
Install the cage nuts at the desired U location.
2.
Screw the mounting bracket ears into the RETMA rail surface at the U
location where the cage nuts wereinstalled.

13
M1 INTELLIGENT PDU INSTALLATION MANUAL
Grounding the PDU
Connecting the Ground Bonding Cable
Per international regulatory requirements, the primary Safety Earth Bond connection is
contained in the PDU as an integral part of the branch circuit cabling and plug. There is
an external ground bonding point located on the chassis of the PDU. The ground
bonding screw is provided as an attachment point for conductors. Use a ground bonding
cable if the rack contains any conductors for functional grounding or bonding of
ungrounded metal parts. This bonding point can also be used to bond the PDU to a
known earthed reference terminal in the building. The ground bounding point is located
on the surface with the receptacles on all PDUs except for the dual-sided models.
These models have the ground bounding point on the surface with the circuit breakers.
Bond Power Distribution Units (PDUs) to grounding strip or grounding bus bar.
See Panduit Grounding and Bonding Jumper kits for factory terminated
options to provide a bolt-on solution.

14
M1 INTELLIGENT PDU INSTALLATION MANUAL
Bonding
This product contains an external earthing screw with a star washer,
which should be used for supplementary Earth bonding to the rack
metalwork.
Bonding
Minimum Requirements for Bonding Conductors
Up to and including 32A 12 AWG
Screw Size
Over 16A, less than or equal to 40A 5mm

15
M1 INTELLIGENT PDU INSTALLATION MANUAL
Section 3 – Connecting the PDU
Connecting the PDU to a Power Source
Always follow local and national codes when installing the PDU. The PDU should be
connected to a dedicated circuit protected by a branch circuit breaker matching the PDU
input plug type.
NOTE: When connecting the PDU to a Power Source, make sure that you have enough
length in the PDU power cord to reach the PDU power source.
1.
Turn the feed circuit breaker Off.
2.
Make sure that all circuit breakers on the PDU are set toOn.
3.
Connect each PDU to an appropriately rated branchcircuit.
NOTE: Refer to the label on the PDU for the input ratings.
4.
Turn the feed circuit breaker On. The LCD screen (on units with display) will
display a status bar when the PDU operating system is loading. When complete, the
Main Menu will display on the LCD screen. Switched and Monitored & switched PDUs
show a light corresponding to each outlet as it is poweredup.
Table of contents
Other Panduit Network Hardware manuals

Panduit
Panduit PANVIEW iQ PVQ-MIQPS96F User manual

Panduit
Panduit PVMAPU24 User manual

Panduit
Panduit smartzone G5 User manual

Panduit
Panduit NetKey NK366M**Y User manual

Panduit
Panduit GP6 Plus User manual

Panduit
Panduit SmartZone Use and care manual

Panduit
Panduit Atlona AT-HDR-EX-70C-RX User manual

Panduit
Panduit CDPP8RG-S User manual

Panduit
Panduit DPOE24U1XG User manual

Panduit
Panduit Atlona AT-HDR-EX-100CEA-RX User manual