18
Prop. Directional Control Valve
Series DFplusOperation Manual
Parker Hannifin Corporation
Hydraulic Controls Division
D_FP_20 5715-658 UK.indd CM 06.11.13
5. Operating Instructions
Basically the valve performs the task of converting a
command signal into a proportional spool stroke with
the highest possible dynamic. For these purposes
the input value will be electronically compared
with the actual spool position value. The signal
difference feeds a position controller, that in turn
provides via a power amplifier stage the required
current for the actuator.
Preferred Hydraulic Initial State
The valve has -as all zero lap valves- no safe
initial state when switched off.In this case the
valve takes a position which is selectable by
the valve type (preferred hydraulic initial state).
This position depends on contamination
level and therefore is not ensured.That applies
also for pressure drops above 120 bar at
single flow path on the control lands A-T resp.
B-T. We would therefore recommend the ap-
plication of additional check valves with se-
quential control.
Solenoid Current Monitoring
The electronic driver contains a circuit to monitor
the solenoid current. The current measurement
compares for exceeding of a certain value and
switches off after a time period of approx. 10 sec.
for temperature rise protection of the actuator.
For normal operating conditions this state will not
reached, but it may occur with a contaminated
sluggish valve.
In this case the reason for the contamination
should be repaired (hydraulic fluid exchange,
filtration review, valve flushing).
The overcurrent shutoff condition may be resetted
by the actions below:
Code 0: Temporary disconnection of the supply
voltage.
Code 5: Temporary disconnection of the enable
signal.
Code 7: Temporary disconnection of the enable
signal.
The shutoff of the actuator drive due to overload
will be signaled via the diagnostics output.
The condensed function conditions of the actuator
drive are given below:
The actuator drive is enabled, if:
the actuator drive is in normal operation, AND cur-
rent of > 3.8 mA flows into input (4...20 mA option)
The actuator drive is disabled, if:
the actuator drive is in overload operation, OR cur-
rent of < 3.6 mA flows into input (4...20 mA option)
Zero Position Adjustment
The valve zero position is already pre-adjusted by
the factory. However, the valve has additionally the
option for manual adjustment of the zero position.
This allows for zero adjustment of the flow inde-
pendently from further system parameters. The
adjustment takes place by a multiturn trimming
potentiometer, which is accesible on the top side of
the valve after removing of a cover screw. Required
default conditions prior to the adjustment procedure:
•supply voltage switched on
•command input signal of 0 V resp. 0 mA / 12mA
•hydraulic system switched on
The adjustment requires a screw driver with
a blade width of 2 mm.
Usage of unsuitable tooling may cause ir-
reparable damages to the valve!
After adjustment of zero position the cover
screw has to be refitted including the seal.