890GTR Quickstart
4 of 13
ProductWarningsandSymbols
Caution
Risk of electric shock
Caution
Refer to
documentation
Earth/Ground
Protective
Conductor Terminal
DirectCurrentSupply
Alternating
CurrentSupply
PhaseSymbol
ONSymbol
OFFSymbol
WARNING: The 890GTR is not provided with a GFDI device. This inverter must be used with an
external GFDI device as required by the Article 690 of the National Electrical Code for the Installation
location.
Hazards
DANGER!–Ignoringthefollowingmayresultininjury
1. This equipment can endanger life by
exposure to high voltages.
2. The equipment must be permanently
earthed due to the high earth leakage
current, and the supplies and loads
must be connected to an appropriate
safety earth.
3. Ensure all incoming supplies are
isolated before working on the
equipment. Be aware that there may be
more than one supply connection to the
inverter.
4. There may still be dangerous voltages
present at power terminals (battery
inputs and DC bus) when the inverter is
stopped.
5. For measurements use only a meter to IEC
61010 (CAT III or higher). Always begin
using the highest range. CAT I and CAT II
meters must not be used on this product.
6. Under normal circumstances the AC and
DC Bus should discharge within 10
minutes. Use a meter capable of
measuring up to 1000 VDC & 600 VAC
RMS to confirm that less than 50V is
present on the DC BUS and between all
power terminals and earth before working
on or near the DC Bus.
7. Unless otherwise stated, this product must
NOT be dismantled. In the event of a fault
the component must be returned.
WARNING! - Ignoring the following may result in injury or damage to equipment
SAFETY
Where there is conflict between EMC and Safety requirements, personnel safety shall always take
precedence.
Never perform high voltage resistance checks on
the wiring without first disconnecting the inverter
from the circuit being tested.
Whilst ensuring ventilation is sufficient, provide
guarding and /or additional safety systems to
prevent injury or damage to equipment.
All control and signal terminals are SELV, i.e.
protected by double insulation. Ensure all external
wiring is rated for the highest system voltage.
All exposed metalwork in the Inverter is protected by
basic insulation and bonded to a safety earth.
When replacing an inverter in an application and
before returning to use, it is essential that all user
defined parameters for the product’s operation are
correctly installed.
RCDs are not recommended for use with this
product but, where their use is mandatory, only Type
B RCDs should be used.