Parker DN-6 Series User manual

1
Parker Nitrogen Generator DN-6
Installation, Operation and Maintenance Manual
Original Language EN

Parker Hannin Corporation
Industrial Gas Filtration and
Generation Division
4087 Walden Ave.
Lancaster, NY
716-686-6400
www.parker.com/igfg
2
Retain this user guide for
future reference.

3
Table of Contents
Page
1. Safety Information............................................................................................... 4
1.1 Markings and Symbols.........................................................................................5
2. Description ...... .................................................................................................. 6
2.1 Technical Specification........................................................................................ 6
2.1.1 Dimension ................................................................................................. 8
2.2 Unpacking the Equipment................................................................................... 8
2.2.1 Dimension ..................................................................................... 8
3. Installation & Commissioning........................................................................... 9
3.1 Recommended System Layout ........................................................................... 9
3.2 Installation of the Equipment .............................................................................. 10
3.2.1 Anchoring the System to the Wall................................................. 11
3.3 Electrical Installation ........................................................................................... 11
4. Operating the Equipment................................................................................... 12
4.1 Starting the Equipment ...................................................................................... 12
4.2 Shutting Down the Equipment ........................................................................... 14
4.3 Depressurizing the System................................................................................. 14
5. Maintenance.........................................................................................................15
5.1 Cleaning............................................................................................................. 15
5.1.1 Exterior..................................................................................................... 15
5.1.2 Internal .................................................................................................... 15
5.2 Service Intervals ................................................................................................. 16
5.3 Service Kits....... ................................................................................................. 17
5.4 Annual Filter Service Requirement...................................................................... 18
5.4.1 Filter Replacement........................................................................ 18
5.4.2 Valve Replacement....................................................................... 19
5.4.3 Compressor Replacement............................................................ 20
5.4.4 Temperature Switch Replacement................................................ 21
5.4.5 PLC Display.................................................................................. 21
6. Troubleshooting ................................................................................................. 22
7. Service Parts..... ................................................................................................. 23
8. Schematics ....................................................................................................... 24
The latest revision of this document can be downloaded at www.parker.com/gsfregistration.

Parker Hannin Corporation
Industrial Gas Filtration and
Generation Division
4087 Walden Ave.
Lancaster, NY
716-686-6400
www.parker.com/igfg
4
1 Safety Information
Important: Do not operate this equipment until the safety information and
instructions in this user guide have been read and understood by all personnel
concerned. Use of the equipment in a manner not specified within this user guide
may impair the protection provided by the system and could result in an unplanned
release of pressure, which may cause serious personal injury or damage.
Only competent personnel trained, qualified, and approved by Parker Hannifin
should perform service and repair procedures.
When handling, installing or operating this equipment, personnel must employ safe engineering practices and
observe all related local regulations, health & safety procedures, and legal requirements for safety.
Ensure that the equipment is depressurized and the electrical is disconnected from the supply, prior to
carrying out any of the scheduled maintenance instructions specified within this user guide.
Most accidents that occur during the operation and maintenance of machinery are the result of failure to
observe basic safety rules and procedures. Accidents can be avoided by recognizing that any machinery is
potentially hazardous.
Parker Hannifin can not anticipate every possible circumstance which may represent a potential hazard.
The warnings in this manual cover the most known potential hazards, but by definition can not be all-
inclusive. If the user employs an operating procedure, item of equipment or a method of working which is not
specifically recommended by Parker Hannifin the user must ensure that the equipment will not be damaged
or become hazardous to persons or property.
The system produces a flow of nitrogen and oxygen gases, which quickly disperses in the atmosphere.
Nitrogen is not a poisonous gas but, in a concentrated form, there is a risk of asphyxiation. Do not directly
inhale the output gas from the outlet pipe.
The system is classified as non-hazardous for transportation purposes and as non-flammable for fire
regulations. Any fire should be fought by means appropriate to the material causing the fire with the
exception being the use of water.
Note: Any interference with the calibration warning labels will invalidate the gas system’s warranty
and may incur costs for the re-calibration of the gas system.
This equipment is for indoor use only. Do not operate outdoors.

Parker Hannin Corporation
Industrial Gas Filtration and
Generation Division
4087 Walden Ave.
Lancaster, NY
716-686-6400
www.parker.com/igfg
5
1.1 Markings and symbols
The following markings and international symbols are used on the equipment and within this user guide:
Caution, Read the User Guide.
Highlights actions or procedures which,
if not performed correctly, could lead to
electric shock.
Highlights actions or procedures which,
if not performed correctly, may lead to
personal injury or death.
When disposing products for end of life
including electronic parts and assemblies,
follow local waste disposal regulations.
Highlights actions or procedures which,
if not performed correctly, may lead to
damage to this product.
Highlights information relevant to an
operating procedure or process.
DANGER
Disconnect the mains supply before removing this cover.
NITROGEN (N2)
DO NOT BREATHE
Asphyxiant in high concentrations. No odor. Slightly lighter
than air. Ensure adequate ventilation. Breathing 100%
nitrogen will eventually cause unconsciousness and could
lead to death due to lack of oxygen.
NON-FLAMMABLE COMPRESSED GAS
MAX PRESSURE 160 psig (11 barg)
Use only with equipment compatible with this pressure.
160 psig (11 barg)

Parker Hannin Corporation
Industrial Gas Filtration and
Generation Division
4087 Walden Ave.
Lancaster, NY
716-686-6400
www.parker.com/igfg
6
2 Description
The Parker Nitrogen Generator is designed to provide a constant supply of nitrogen gas,
at a pre-selected purity, flow, and pressure, as specified in section 2.1 below.
The system uses proven Pressure Swing Adsorption (PSA) technology with a Carbon
Molecular Sieve (CMS) to separate nitrogen (N2) from the atmosphere and store it at a high
purity level.
This user guide contains all of the information necessary for the correct use of the
Parker Nitrogen Generator range. Should you have any questions regarding the safe and
correct installation, operation or maintenance of the generator, contact the supplier
before proceeding.
Performance Specifications Model
Units DN-6JA-100 DN-6NA DN-6WD DN-6CHN
Outlet ow SCFH
(l/min)
6
(2.8)
6
(2.8)
6
(2.8)
6
(2.8)
Maximum outlet pressure
psig
(barg)
[kPa]
85
(5.9)
[586]
85
(5.9)
[586]
85
(5.9)
[586]
85
(5.9)
[586]
Mechanical connections
Nitrogen Outlet CPC 1800 (1/4” tubing barb valve inline coupling)
Electrical Specifications
Connection Type IEC320 IEC320 IEC320 IEC320
Supply Voltage Range * VAC 100V 1 phase + PE
50/60Hz
120V 1 phase + PE
60Hz
230V 1 phase + PE
50/60Hz
230V 1 phase + PE
50/60Hz
Supply Voltage Fluctuation ± 10% ± 10% ± 10% ± 10%
Current A 6 6 3 3
Fuse A 10
((T), 10A, 250v)
10
((T), 10A, 250v)
10
((T), 5A, 250v)
10
((T), 5A, 250v)
Cordset Included Included * Included
2.1 Technical Specification
This specification is valid when the equipment is located, installed, operated, and maintained
as specified within this user guide.
*Ordered seperately (see chart on the bottom of page 7).

Parker Hannin Corporation
Industrial Gas Filtration and
Generation Division
4087 Walden Ave.
Lancaster, NY
716-686-6400
www.parker.com/igfg
7
Regulatory Certifications
Model DN-6NA DN-6WD DN-6JA-100 DN-6CHN
UL Certication
Standard
UL61010-1 3rd Edition
UL61010-2-201 1st Edition
UL61010-1 3rd Edition
UL61010-2-201 1st Edition
UL61010-1 3rd Edition
UL61010-2-201 1st Edition
UL61010-1 3rd Edition
UL61010-2-201 1st Edition
IEC Certication
Standard IEC61010-1:2010, MOD IEC61010-1:2010, MOD IEC61010-1:2010, MOD IEC61010-1:2010, MOD
CSA Certication
Standard
CAN/CSA C22.2 No.
61010-1-12
CAN/CSA-IEC 61010-2-
201:14
CAN/CSA C22.2 No.
61010-1-12
CAN/CSA-IEC 61010-2-
201:14
CAN/CSA C22.2 No.
61010-1-12
CAN/CSA-IEC 61010-2-
201:14
CAN/CSA C22.2 No. 61010-
1-12
CAN/CSA-IEC 61010-2-
201:14
CB Certication DK-65436-UL DK-65436-UL DK-65436-UL DK-65436-UL
S. Korean EMC Test - EMI7053.17 - -
EMC Standard FCC Part 15 Subpart B EN61326-1: 2013
CISPR-11: 2015, Class B
EN61326-1: 2013
CISPR-11: 2015, Class B
EN61326-1: 2013
CISPR-11: 2015, Class B
NSF Certication
Standard NSF/ANSI Standard 18 NSF/ANSI Standard 18 NSF/ANSI Standard 18 NSF/ANSI Standard 18
Environmental Specifications
Ambient Temperature ºF
(ºC)
36 – 95
(2 – 35)
Maximum Humidity (80% MAX ≤ 31°C)
IP Rating IP20
Pollution Degree 2
Installation Category II
Altitude ft
(m)
< 6562
(< 2000)
Noise dB(A) <65
Weight
Shipping weight (single unit) Lbs (kgs) 171 (78)
Product Lbs (kgs) 107 (49)
*Ordered Seperately
Country/Territory Electric Cordset (with Plug)
Australia 13412AU
Brunei 13412UK
Cambodia 13412UK
Europe 13412EU
Hong Kong 13412UK
India 13412IND
Indonesia 13412EU
Malaysia 13412UK
New Zealand 13412AU
Philippines 13412
Singapore 13412UK
South Korea A03-0461
Thailand A03-0469
UK 13412UK
Vietnam 13412EU

Parker Hannin Corporation
Industrial Gas Filtration and
Generation Division
4087 Walden Ave.
Lancaster, NY
716-686-6400
www.parker.com/igfg
8
2.1.1 Dimensions
2.2 Unpacking the equipment
This system is heavy. Be careful in removing the system from the packaging set.
Remove the equipment from its packaging. Check system was not damaged in transit. Verify that the
installation kit is included with your equipment. Installation kit includes:
• CPC female NSF fitting
• Operator Quick Start guide
Figure 1: System Features and Dimensions
If any items are missing or damaged, please contact
your Parker representative.
Description P/N Qty
Installation Kit B04-0690 1
Wall Anchor
and Hardware
(Optional Location)
2.2.1 (Optional) Wall Anchor Bracket Kit
Remove the equipment from its packaging. Check system was not damaged in transit. Verify that the
installation kit is included with your equipment. Installation kit includes:
• Wall anchor bracket
• ¼ in turn fastener
• CPC female NSF fitting
• Decorative screw caps and cap removal tool If any items are missing or damaged, please contact
your Parker representative.
Description P/N Qty
Wall Anchor Bracket Kit B04-0691 1
Wall Anchor
and Hardware
(Optional)
9.50 20.00
20.00 in
(50.80 cm)
9.50 in
(24.13 cm)
28.88 in
(73.35 cm)

Parker Hannin Corporation
Industrial Gas Filtration and
Generation Division
4087 Walden Ave.
Lancaster, NY
716-686-6400
www.parker.com/igfg
9
3 Installation & Commissioning
Do not install this equipment until the following instructions have been read and understood
by all personnel concerned. Minimize the risk of siphoning by installing a check valve between
the system and the source.
Before continuing with the installation and commissioning of this equipment ensure that the
tubing is correctly sized for the pressure and application and that the electrical supply voltage
and frequency meet the requirements detailed within this specification and on the equipment
rating plate.
Figure 2: Recommended System Layout
3.1 Recommended System Layout Maximum
recommended
tubing length to
dispenser =
300 ft (91.4 m)
6 in - 8 in (15.2 - 20.4 cm)
minimum clearance at
back of unit for N2 outlet
tubing and electrical cord.
12 inches (30.5 cm)
minimum clearance
at front of unit.
If any items are missing or damaged, please contact
your Parker representative.
To Dispenser
Customer installed check
valve recommended

Parker Hannin Corporation
Industrial Gas Filtration and
Generation Division
4087 Walden Ave.
Lancaster, NY
716-686-6400
www.parker.com/igfg
10
3.2 Installation of the System
The system should be located indoors on a flat surface, and be protected from direct sunlight, moisture, and
dust (Refer to section 2.1 of this user guide for the system’s environmental specification). When considering
the final location of the system ensure that:
• The system is positioned within easy access of the electrical supply.
• There is adequate space available around the system for ventilation, maintenance access.
• Casters are locked when system is in position.
• The tubing is NSF ¼ in (.63 cm) with 150 psig (10.3 bar) pressure rating.
• Max length of tubing: 300 ft (91.4 m).
• Clearance: Top, bottom, left and right sides: None. Back 6 - 8 inches (15.2 cm - 20.3 cm) to allow
clearance for tubing and power cord, Front: Minimum 12 in (30.5 cm) to allow for ventilation.
Due to the nature of operation, there is a possibility of oxygen enrichment surrounding the
system. Ensure that the area is adequately ventilated. Where the risk of oxygen enrichment
is high, such as a confined space or poorly ventilated room, the use of oxygen monitoring
equipment is advisable.
The DN-6 Series is capable of delivering nitrogen at a flow rate of 6 SCFH (2.8 lpm). Nitrogen is
not a poisonous gas but, in a concentrated form, there is a risk of asphyxiation. If the system
is operated within a confined space ensure that adequate ventilation and oxygen monitoring
equipment is fitted.
DO NOT
• Position the system so that it is difficult to operate or disconnect from the electrical supply.
• Position the system directly above electrical equipment as condensate may collect at the base
of the system.
• Use noxious chemicals or machinery that produces fumes within a 20 ft (6 m) radius of the system.

Parker Hannin Corporation
Industrial Gas Filtration and
Generation Division
4087 Walden Ave.
Lancaster, NY
716-686-6400
www.parker.com/igfg
11
3.2.1 Anchoring the System to the Wall
Ensure that the wall is capable of supporting the system. Refer to section 2.1 for weights
and dimensions.
The system may be attached to the wall using the optional anchor bracket. Mark a point on the wall at a
height along which the upper mounting holes of the system will be located.
Roll the system up to the wall and use the supplied hardware to attach the anchor bracket onto the wall.
3.3 Electrical Installation
Attach the supplied cordset to the IEC 320 socket and connect the cordset to the electrical outlet.
If a cordset other than the one provided is used to connect the equipment to the electrical supply, ensure
that it is suitably rated for the application and in accordance with local and national code regulations.
The equipment must be connected to earth (grounded) through the cordset.
Figure 3: Recommended installation of IEC320 socket to power source.

Parker Hannin Corporation
Industrial Gas Filtration and
Generation Division
4087 Walden Ave.
Lancaster, NY
716-686-6400
www.parker.com/igfg
12
4 Operating the equipment
4.1 Starting the equipment
1. Install the equipment at the desired location and plug the electrical cord into a properly grounded
electrical outlet.
2. Press the power switch ON (symbol “I” illuminates green) located at the rear of the unit to start the
system. DO NOT CONNECT THE DOWNSTREAM EQUIPMENT YET. The cooling fans will start immedi-
ately and after approximately 2 minutes the on-board compressor will start.
3. Initially, the RED, ”SYSTEM FAULT” light on the front panel will illuminate because the internal nitrogen
storage tanks are empty. Allow the system to operate normally until the pressure gauge displays a pres-
sure within the GREEN range (75-85 psig (5.1-5.9 barg)) and the GREEN “READY” light illuminates (6-8
minutes). The RED, ”SYSTEM FAULT” light will go off.
Figure 4: N2 Pressure Gauge and Indicator Lights.

Parker Hannin Corporation
Industrial Gas Filtration and
Generation Division
4087 Walden Ave.
Lancaster, NY
716-686-6400
www.parker.com/igfg
13
4. The compressor will continue to cycle on and off about every 2 minutes until the internal nitrogen storage
tanks are fully pressurized.
5. With no nitrogen being withdrawn from the output fitting, the system should go into standby mode within
a short time and the cooling fans will stop. Allow the system to sit for an additional 15-20 minutes before
connecting any output tubing. During this time the compressor should not operate. If the
compressor operates during this time, it may indicate an internal system leak.
6. Connect the tubing barb valve coupling to the downstream tubing. Then connect that coupling to
the Nitrogen Outlet Port coupling on the back of the system. Make sure that the downstream tubing
has a check valve (not supplied) to prevent back-flow. Refer to section 3.1 for recommended
installation diagram.
7. Nitrogen will immediately begin pressurizing the dispensing system to approximately 80 psig (factory
preset), and the system should come out of standby mode, as indicated by the operation of the cooling
fans. If the internal tanks are de-pressurized sufficiently, the compressor will begin to cycle on and off
to re-pressurize the internal storage tanks.
8. The system should now be ready for supplying nitrogen and will maintain approximately 80 psig output
pressure as nitrogen is withdrawn from the system.
9. If the RED, ”SYSTEM FAULT” light comes on during use, it may: (1) indicate a gas leak in the dispensing
system causing an excess of nitrogen to be withdrawn from the system or (2) indicate an over-temper-
ature condition in the system caused by insufficient cooling air flow. This could be caused by debris
blocking the inlet duct at the bottom-rear of the unit next to the floor, or an obstruction of the exhaust
vent located at the front of the unit.
Refer to Section 2.1 Technical Specifications for ambient temperature specifications.
The nitrogen generation process will consist of a compressor run sequence followed immediately by
an exhaust sequence. These cycle times vary depending upon the model of generator as shown below.
An audible pressure release will indicate that the unit is producing nitrogen.
Model Compressor Run Time
(Seconds)
Exhaust Time
(Seconds)
DN-6 Series 130 120
The system will initially take 15-30 minutes to fully pressurize the internal storage tanks with
no nitrogen being withdrawn from the system.
The system is designed to run continuously and requires no further intervention, other than
regular scheduled maintenance. (See Section 5 for maintenance instructions).

Parker Hannin Corporation
Industrial Gas Filtration and
Generation Division
4087 Walden Ave.
Lancaster, NY
716-686-6400
www.parker.com/igfg
14
Standby Mode
In the event of zero flow, the system cycle will continue until the internal tanks are fully pressurized
whereupon it will enter standby mode. In standby mode, the unit will cease cycling and the fans will turn off.
When the nitrogen pressure falls below a predetermined set point the unit will re-enter normal operation and
the cooling fans will start, followed by cycling of the compressor.
4.2 Shutting Down the System
1. Push the power switch to the “OFF” position (O) and ensure that the green illumination of the switch is off.
Make sure that the power cord is unplugged before performing any maintenance and service.
Failure to do so may result in electrical shock or serious injury.
4.3 Depressurizing the System
Follow this procedure to depressurize the system before
performing any maintenance or service.
1. Push the power switch to the ‘OFF’ position (O) and
unplug the cord set.
2. Remove the system’s cover to access internal components.
3. Loosen the bleed screw (See Figure 5) by turning
counter-clockwise by hand, 2-3 turns until gas can be
heard escaping.
4. Allow the system to de-pressurize until the pressure
gauge on the front of the unit indicates zero pressure.
5. Once the system is relieved of pressure, re-tighten the bleed
screw by turning clockwise while the system is depressurized.
Figure 5: Bleed Screw
The generator will remain pressurized after shut down. Before performing any maintenance
or opening any piping systems, always depressurize the system. Failure to do so may result
in injuries.

15
5 Maintenance
It is essential that the system is powered down and fully depressurized before carrying out
any servicing procedures (Refer to sections 4.2 and 4.3)
The quality and reliability of the system is maintained through preventative maintenance performed on
a scheduled, regular basis. Although the frequency of this maintenance is determined by particular use
conditions, it is recommended that filter elements are changed at least every twelve months.
5.1 Cleaning
Clean the system with a damp cloth only and avoid excessive moisture around any electrical components. If
required you may use a mild detergent, however do not use abrasives or solvents as they may damage the
warning labels on the equipment.
5.1.1 Exterior
It is highly recommended that an internal inspection of the unit be performed after the first 6 months of
operation following installation. One of the main purposes of this inspection is to check the hour meter on
the PLC. See section 5.4.5 for accessing the hour meter on the PLC. Access and record the number of
RUN hours and ECO hours for the unit operation as shown on the PLC display. In general, the number of
ECO hours should be many times that of the RUN hours (for example, for 1 year of operation, 400-600 hours
of RUN time, and 8000 hours or more of ECO time would be considered normal). The number of ECO hours
should be ten to fifteen times that of the number of RUN hours for a leak tight system. If the number of ECO
hours is only two or three times the number of RUN hours, this indicates that the system likely has nitrogen
leaks either internally or externally causing the compressor to operate excessively and reducing the life of
the system. With a high number of RUN hours, the system’s replacement filters will need to be changed out
more frequently in order to maintain optimum system performance and reduce the chances of further system
damage.
To check for internal leaks, the nitrogen outlet tubing can be disconnected from the generator and the
compressor operation monitored. With the outlet tubing disconnected, if the compressor operates more
than once per hour, then internal leaks are likely and leak test solution (soap + water) can be used to isolate
internal leaks. If the compressor does not operate with the outlet tubing disconnected, and there are a high
number of RUN hours, then leaks in the coffee dispense system are likely (keg o-rings, etc). Find and repair
any dispense system nitrogen leaks to minimize the number of RUN hours of compressor operation. Re-
connect nitrogen output tubing once internal system leaks are checked and repaired if necessary.
With the cover removed, vacuum any excessive dirt and dust from the air intake duct area, exhaust screen,
and check coalescing filter for debris. Replace any filters if necessary, especially the coalescing and
compressor air intake filter if an excessive number of run hours are observed.
5.1.2 Internal

Parker Hannin Corporation
Industrial Gas Filtration and
Generation Division
4087 Walden Ave.
Lancaster, NY
716-686-6400
www.parker.com/igfg
16
5.2 Service Intervals
Maintenance Operations 6 Months 12 Months
36 Months
or
5000 Hours
Remove cover and inspect internals of
unit. Check compressor RUN and ECO
hours on PLC (see section 5.4.5)
Remove dust and debris from air intake,
exhaust vent and other internal sections
as required. Replace specic lter ele-
ments if needed.
Ensure system “ready” light
is illuminated.
Check that the exhaust valve is discharg-
ing, as described in section 4.1
Ensure “system fault” light is not illumi-
nated. Internal or External leaks will pre-
vent the system from operating at peak
performance and may lead to premature
compressor failure. (See Section 6.0 for
leak troubleshooting procedures)
Check that the pressure gauge is
between 75 and 85 psi (517-586 kPa)
during normal operation.
Check the condition of the electrical
supply cables.
Ensure there is adequate ventilation
clearance around the generator.
Remove dust and debris from air intake,
exhaust vent and other internal sections
as required.
Filter Element Replacement
Recommended Service A
Compressor Replacement
Recommended Service B
Exhaust Valve Replacement
Recommended Service C
Essential
Procedure
Check
Key:

Parker Hannin Corporation
Industrial Gas Filtration and
Generation Division
4087 Walden Ave.
Lancaster, NY
716-686-6400
www.parker.com/igfg
17
5.3 Service Items
Service
Kit Interval Description P/N
DN-6NA DN-6JA-100 DN-6WD DN-6CHN
A 12 months Filter Kit MKCN-6 MKCN-6 MKCN-6 MKCN-6
B
36 months
or
5000 running
hrs.
Compressor
Replacement B04-0647 B04-0647 B04-0648 B04-0648
C
36 months
or
5000 running
hrs.
Exhaust Valve
Replacement B04-0664 B04-0664 B04-0665 B04-0665
Figure 6: Replacement Parts

Parker Hannin Corporation
Industrial Gas Filtration and
Generation Division
4087 Walden Ave.
Lancaster, NY
716-686-6400
www.parker.com/igfg
18
Coalescing Filter Replacement
1. Ensure that the internal pressure is completely
relieved.
2. Unscrew the bowl counter-clock wise from the
head and remove the element from the bowl.
3. Carefully remove the replacement element from its
packaging and insert it into the bowl. Ensure that
the element fits correctly into the guides provided
in the bowl.
4. Refit the bowl to the head ensuring that the
locking detail on the head and bowl are lined up
when hand tight.
5.4 Annual Filter Service Requirement
Note: Follow depressurize instruction before any maintenance and disconnect the power plug from the
wall outlet.
5.4.1 Filter Replacement
Filter Replacement: Inlet Filter, Exhaust Silencer
and Relief Silencer.
1. For the Inlet Filter and Relief Silencer unscrew
counter-clockwise to remove the filter. Replace
with a new filter by turning clock wise.
2. For the Exhaust Silencer, disconnect the silencer
assembly from the tubing and replace with a
new silencer assembly.
Figure 7: Filter
Replacement
Figure 8: Coalescing Filter Replacement

Parker Hannin Corporation
Industrial Gas Filtration and
Generation Division
4087 Walden Ave.
Lancaster, NY
716-686-6400
www.parker.com/igfg
19
5.4.2 Exhaust Valve
Replacement
1. Pull valve from clips for easier access.
2. Disconnect tubing from the quick connect
fitting at both ends of solenoid valve.
3. Disconnect the DIN plug on to the solenoid valve
by removing the center screw.
4. Follow steps 3, 2, 1 in reverse to install the
replacement exhaust valve.
Final Filter Replacement
1. Ensure that the internal pressure is completely
relieved.
2. Unscrew the filter bowl from the head and remove
the filter element.
3. Carefully remove the replacement filter element
from its packaging and gently slide it over the
support core.
4. Refit the bowl to the head ensuring that the O-ring
properly seated and tighten bowl with wrench. Figure 9: Final Filter Element Replacement
Figure 10: Exhaust Valve Replacement
Figure 11: DIN Removal
1" Wrench

20
5.4.3 Compressor Replacement
1. Disconnect the braided tubing from the compressor by loosening the nut using two wrenches, paying
careful attention not to twist or damage the braided tubing. See 5.4.5 to identify and document
compressor run hours. Keep this information as it will be requested if service is required.
2. Disconnect the compressor wiring at the in-line 3 Pin Connector.
3. Remove exhaust Silencer Assembly for easier access.
4. Loosen (7) Screws (do not remove) holding the Inlet Duct. Slide and remove the Inlet Duct.
5. Remove (4) Nuts holding the Vibration Mounts to the chassis and carefully remove the Compressor.
6. Screw the (4) Vibration Mounts supplied into the threaded holes on the replacement Compressor.
7. Mount the Compressor onto the chassis and secure it into place using (4) nuts.
8. Reinstall the Inlet Duct and tighten the (7) screws.
9. Reconnect the 3 Pin Connector and braided tubing.
10. Reinstall the exhaust Silencer Assembly.
Figure 12: Compressor Replacement
This manual suits for next models
4
Table of contents
Other Parker Inverter manuals

Parker
Parker 890GTR Instruction manual

Parker
Parker 890GTR User manual

Parker
Parker LCMS-5000 User manual

Parker
Parker AC30 series User manual

Parker
Parker LINKnet AC30P Assembly instructions

Parker
Parker GVI Series User manual

Parker
Parker NitroFlow Lab User manual

Parker
Parker 890SD Instruction manual

Parker
Parker AC30V Series User manual

Parker
Parker N2 NITROSource Compact N2C-2 User manual