LIST OF LEVEL 1 VARIABLES (User level)
VARIABLE MEANING VALUES DEFAULT
r0 Temperature differential referred to main SETPOINT 1 - 10 °C 2°C
r1
Ambient temperature limit during cooling The compressor
stops and the fans are activated during the cooling phase if the
ambient temperature drops below this differential with respect
to the program-specific storage temperature
(ST1,ST3,ST4,ST6). The compressor restarts on re-attainment
of the settings (ST1,ST3,ST4,ST6).
1 - 50 °C 5°C
d0 Defrost interval (hours) 0 - 24 hours 4 hours
d2
End-of-defrost setpoint.
Defrost is not executed if the temperature read by the defrost
sensor is greater than value d2
(If the sensor is faulty defrosting is time-based)
-35 - 45 °C
10°C
d3 Maximum defrost duration (minutes) 1 - 240 min 25 min
d7
Drip duration (minutes)
At the end of defrosting the compressor and the fans remain at
standstill for time setting d7: the defrost LED on the front of the
panel flashes.
0 - 30 min
0 min
F5
Fan pause after defrost (minutes)
Allows fans to be kept at standstill for a time F5 after dripping.
This time is counted from the end of dripping. If dripping is not
set the fan pause is executed directly after the end of
defrosting. During the pause the fan icon flashes.
0 - 10 min
0 min
A1
Minimum temperature alarm
(active only during storage)
Allows user to define a minimum cold room storage
temperature. Below the value A1 a warning is given: the alarm
LED and the displayed temperature flash and the fault is also
highlighted by an internal buzzer.
- -45°C
A2
Maximum temperature alarm
(active only during storage).
Allows user to define a maximum cold room storage
temperature. Above the value A2 a warning is given: the alarm
LED and the displayed temperature flash and the fault is also
highlighted by an internal buzzer.
- +45°C
tEu
Displays evaporator sensor temperature / current day-date
/ product sensor temperature
0 = displays the
day on the LCD
1 = displays
evaporator
temperature on
LCD (nothing
displayed if dE =1
2 = displays
product sensor
2