Penn P70 Series User manual

1
Refer to the QuickLIT website for the most up-to-date version of this document.
P70, P72, and P170 Series Controls for Dual PressureApplications
Installation Instructions
Applications
The P70, P72, and P170 Controls for Dual Pressure Applications provide combined high and low pressure control
of compressors on commercial refrigeration and air conditioning applications.
P70S and P170S models have independently operated high and low pressure Single-Pole Double-Throw (SPDT)
switches that can be wired to satisfy a variety of control requirements. These adaptable controls have a high
pressure manual reset lockout mechanism that is convertible to automatic reset. See Table 1.
P70L, M, N, and P170L, M, N models have a Single-Pole Single-Throw (SPST) switch. Models are available with
automatic or manual reset lockout options. Models with manual reset are available with either high-side-only
manual reset, or low-side and high-side manual reset. (See Table 1 and Table 3.) Ammonia compatible models are
available (P70L and P70M only). See Table 2.
P72 models have a Double-Pole Single-Throw (DPST) switch with load-carrying contacts that can provide direct
control of 208/240 VAC, single-phase motors up to 3 hp, 480, and 600 VAC single-phase
non-compressor motors and 208/220 VAC, 3-phase motors up to 5 hp. See Table 3.
These controls are available in several pressure ranges and are compatible with most common refrigerants.
Ammonia-compatible models are also available (P70L and P70M only). See Table 2.
The MICRO-SET® option provides fine adjustment of the differential setting for precision pressure control of low
pressure applications.
Some models feature Limited Knob Adjustment, which restricts adjustment of the pressure settings and deters
over-adjustment or tampering. See Low Pressure Limited Knob Adjustment.
A Manual Reset Lockout option does not allow the pressure control to reset automatically after CUT OUT is
reached, and provides shutdown capability for unmonitored equipment. See Manual Reset Operation.
NEMA 1 enclosures are standard on most models. NEMA 3R enclosures are also available.
Table 1 through Table 2 list the standard models and features of P70, P72, and P170 controls for dual pressure
applications. These standard models are available through most authorized
Johnson Controls/PENN® distributors.
IMPORTANT: Except for those models listed as refrigeration temperature limiting controls, use this P70, P72,
and P170 Series Controls for Dual Pressure Applications only as an operating control. Where failure or
malfunction of the P70, P72, or P170 Pressure Control could lead to personal injury or property damage to the
controlled equipment or other property, additional precautions must be designed into the control system.
Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls,
intended to warn of or protect against failure or malfunction of the P70, P72, or P170 Pressure Control.
P70, P72, and P170 Series Controls for Dual Pressure
Applications
Installation Instructions Part No. 24-8607-0, Rev. J
Issued September 2018

P70, P72, and P170 Series Controls for Dual Pressure Applications Installation Instructions
2
Table 1: Standard Model P70, P72, and P170 MICRO-SET® Dual Pressure Controls for Non-Corrosive
Refrigerants
Model Code
Number Switch
Action Low Pressure Side
psig (kPa) High Pressure Side
psig (kPa) Pressure
Connector Limited
Knob
Adjustment
Range Differential Range Differential
(Non-
Adjustable)
P70LB-61
1. Control models with high pressure side (only) that are UL Listed as Refrigeration Pressure Limiting Controls.
SPST 12 in. Hg to
80 psig
(-41 to 552)
Min 5 (34)
Max 35 (241) 100 to 500
(690 to 3,447) Fixed
Approximately
65 (448)
36in.Capillary
with 1/4 in.
Flare Nut
Low CUT OUT
P70MA-181Lockout
Requires
Manual Reset
None
P70SA-11Two
Independent
SPDT
Fixed at
65 (448) or
Lockout
Requires
Manual Reset
P170LB-61SPST Fixed
Approximately
65 (448)
1/4 in. Male
Flare
Connector
Low CUT OUT
P170MA-181Lockout
Requires
Manual Reset
None
P170SA-11Two
Independent
SPDT
Fixed at
65 (448) or
Lockout
Requires
Manual Reset
Table 2: Standard Model P70, P72, and P170 All Range Dual Pressure Controls for Ammonia
Model Code
Number Switch
Action Low Pressure Side
psig (kPa) High Pressure Side
psig (kPa) Pressure
Connector Limited
Knob
Adjustment
Range Differential Range Differential
(Non-
Adjustable)
P70LA-21
1. Control models with high pressure side (only) that are UL Listed as Refrigeration Pressure Limiting Controls.
SPST 20 in. Hg to
100 psig
(-68 to 690)
Min7(48) Max
50 (345) 100 to 500
(690 to 3,447) Fixed
Approximately
65 (448)
1/4 in. Female
NPT
Connector
None
P70MA-21Lockout
Requires
Manual Reset

P70, P72, and P170 Series Controls for Dual Pressure Applications Installation Instructions
3
Installation
Dimensions
See Figure 1 and Figure 2 for dimensional information.
Table 3: Standard Model P70, P72, and P170 All Range Dual Pressure Controls for Non-Corrosive
Refrigerants
Model Code
Number Switch
Action Low Pressure Side
psig (kPa) High Pressure Side
psig (kPa) Pressure
Connector Limited
Knob
Adjustment
Range Differential Range Differential
(Non-
Adjustable)
P70LB-11SPST 20 in. Hg to
100 psig
(-68 to 690)
Min 6 (41)
Max 50 (345) 100 to 500
(690 to 3,447) Fixed
Approximately
65 (448)
36in.Capillary
with 1/4 in.
Flare Nut
Low CUT OUT
P70MA-11Lockout
Requires
Manual Reset
None
P70NA-1 Fixed (Manual
Reset)
P72LA-11DPST Min 7 (48)
Max 50 (345) Fixed
Approximately
65 (448)
None
P72LB-11Low CUT OUT
P72MA-11Lockout
Requires
Manual Reset
None
P72NA-11Fixed (Manual
Reset)
P170LB-11SPST Min 7 (48)
Max 50 (345) Fixed
Approximately
65 (448)
1/4 in. Male
Flare
Connector
Low CUT OUT
P170MA-11Lockout
Requires
Manual Reset
None
P170NA-1 Fixed (Manual
Reset)
1. Control models with high pressure side (only) that are UL Listed as Refrigeration Pressure Limiting Controls.

P70, P72, and P170 Series Controls for Dual Pressure Applications Installation Instructions
4
Figure 1: Dimensions for P70, P72, and P170 Dual Pressure Controls with NEMA 1 Enclosure, in.
Figure 2: Dimensions for P70, P72, and P170 Dual Pressure Controls with NEMA 3R Enclosure, in.

P70, P72, and P170 Series Controls for Dual Pressure Applications Installation Instructions
5
Mounting
Observe the following guidelines when installing this device:
• Mount the control in an accessible position, where the control and pressure-connection lines are not subject to
damage.
• Mount the pressure control upright and level.
• Position the pressure-connection lines to allow drainage away from control bellows.
• Locate pressure-tap points on the topside of the refrigerant lines to reduce the possibility of oil, liquids, or
sediment accumulating in the bellows, which could cause control malfunction.
• Mount controls with NEMA 1 enclosures on horizontal or vertical flat surfaces.
• Use two screws or bolts through the two outer holes on the back of the control case when mounting the
control directly to a flat vertical surface. See Figure 3.
• Use the two inner holes with the Universal Mounting Bracket (and screws supplied) when mounting the
control to a flat horizontal surface. See Figure 3.
• Mount controls with NEMA 3R enclosures in a level, upright position with the bellows and conduit connection
facing down. Ensure that all gaskets are in place. Mounting controls with NEMA 3R enclosures in any position
other than upright and level may trap water in the enclosure and submerge internal components.
!
CAUTION: Risk of Property Damage.
Mount the pressure control separately from the electrical cabinet and seal all electrical piping to prevent
ammonia from migrating to electrical components. Where there may be exposure to ammonia, use only
ammonia-compatible control modules and pressure connections. System shutdown due to improper
adjustment may cause property damage.
!
CAUTION: Risk of Property Damage.
Mount the P70, P72, or P170 Pressure Control according to the instructions and guidelines included
with the control. These instructions and guidelines are intended to reduce the risk of malfunction of the
product and resulting property damage. Failure to follow these instructions and guidelines could cause
the control to malfunction, resulting in property damage.
IMPORTANT: Use only the mounting screws supplied with the Universal Mounting Bracket to avoid damaging
internal components. Be careful not to distort or bend the control case when mounting the control to an uneven
surface. Using other screws or bending the control case will void the warranty.
Figure 3: Mounting Dual Pressure Controls
with NEMA 1 Enclosures

P70, P72, and P170 Series Controls for Dual Pressure Applications Installation Instructions
6
Wiring
P70, P72, and P170 controls for dual pressure applications are available with several switch options and electrical
ratings. Check the label inside the control cover for model number, switch action, and electrical rating. Check the
wiring terminal designations on the control switch block, and see the following guidelines and applicable wiring
diagrams, when wiring the control. See Table 1 through Table 3 for switch actions and models. See Technical
Specifications.
!
WARNING: Risk of Electric Shock.
Disconnect or isolate all powersupplies before making electrical connections. More than one disconnect
or isolation may be required to completely de-energize equipment. Contact with components carrying
hazardous voltage can cause electric shock and may result in severe personal injury or death.
IMPORTANT: Use copper conductors only. Make all wiring connections in accordance with local, national, and
regional regulations. Do not exceed the P70, P72, or P170 Pressure Control electrical ratings.
IMPORTANT: Use terminal screws furnished in the switch block. Using other terminal screws will void the
warranty and may damage the switch.
Figure 4: Typical Wiring for SPST Switch
(P70L, M, N, and P170L, M, N Models)
Figure 5: Typical Wiring for 4-Wire, 2-Circuit
Switch (P70P, Q and R Models)

P70, P72, and P170 Series Controls for Dual Pressure Applications Installation Instructions
7
Figure 6: Typical Wiring for DPST Switch
(P72L, M, and N Models)
Figure 7: Two SPDT Switches Wired as a
Dual Pressure Control (P70S and P170S
Figure 8: Two SPDT Switches Wired to Control
Two Different Loads (P70S and P170S Models)

P70, P72, and P170 Series Controls for Dual Pressure Applications Installation Instructions
8
Piping
P70, P72, and P170 dual pressure controls are typically connected to the controlled equipment by a capillary
(except ammonia compatible models). These controls are available with a variety of pressure connection styles.
Avoid severe pressure pulsation at high side pressure connections. Install pressure connection to pressure-tap
points away from the compressor, to minimize the effects of pressure pulsation from reciprocating compressors.
Setup and Adjustments
Adjustment of the P70, P72, and P170 dual pressure controls varies depending on the model. The following
guidelines and diagrams illustrate the procedures for adjusting these controls. Refer to the product label inside the
control cover for model number and switch action, and check the front of the control cover to determine if the
control is All-Range or MICRO-SET® model. See Figure 9 for an illustration and instructions on control
adjustments.
!
CAUTION: Risk of Environmental and Property Damage.
Avoid sharp bends in the capillary tubes. Sharp bends can weaken or kink capillary tubes, which may
result in refrigerant leaks or restrictions of flow.
!
CAUTION: Risk of Environmental and Property Damage.
Coil and secure excess capillary tubing away from contact with sharp or abrasive objects or surfaces.
Vibration or sharp or abrasive objects in contact with capillary tubes can cause damage that may result
in refrigerant leaks or loss of element charge, which may result in damage to the environment or
property.
IMPORTANT: If the control is installed on equipment that contains hazardous or regulated materials such as
certain refrigerants or lubricants, you must comply with all standards and regulations governing the containment
and handling of those materials.
IMPORTANT: Do not apply more than 9 ft·lb (12 N·m) of torque to the flare nuts on pressure connection line
fittings. Overtightening or applying more than 9 ft·lb (12 N·m) of torque may cause seal failure and will void the
warranty.
IMPORTANT: After installing the control, evacuate pneumatic and pressure connection lines to remove air,
moisture, and other contaminants in a manner consistent with applicable environmental regulations and
standards.
!
CAUTION: Risk of Property Damage.
Obtain and use the compressor manufacturer’s net oil bearing pressure specifications. If necessary,
reset the
cut-out pressure difference to the manufacturer’s specifications. Using improper pressure settings may
damage the control, compressor, or other controlled equipment.
IMPORTANT: Use the pressure control settings recommended by the manufacturer of the controlled
equipment. Do not exceed the pressure ratings of the controlled equipment or any of its components when
checking pressure control operation or operating the controlled equipment.
IMPORTANT: After mounting, wiring and evacuating the control, attach a reliable set of gauges to the
controlled equipment, and operate the equipment (at least) three cycles at the pressures necessary to verify
control setpoints and proper equipment operation.

P70, P72, and P170 Series Controls for Dual Pressure Applications Installation Instructions
9
All-Range Controls (Low Side Only)
The low side ofAll-Range controls displays the CUT IN and CUT OUT setpoints. Turn the range screw to adjust the
cut in and cutout setpoints up or down simultaneously which maintains the set differential value. Turn the
differential screw to adjust the cutout setpoint and change the differential value.
MICRO-SET® Controls (Low Side Only)
The low side of MICRO-SET® controls feature a scale plate that displays the CUT IN setpoint and DIFFERENTIAL
setting. Turn the range screw to adjust the cut in setpoint. Turn the differential screw to adjust DIFFERENTIAL
setting. (This changes the cutout pressure.)
Dual Pressure Controls (High Side)
The high side scaleplate of the P70, P72, and P170 dual pressure controls displays only the CUT OUT setpoint.
Turn the range screw to adjust the cutout setpoint. The differential is fixed at about 65 psi.
For controls with Manual Reset Lockout option, see Manual Reset Operation. For P70S and P170S controls, see
Convertible High Pressure Reset Mechanism on P70S and P170S Controls.
To adjust the dual pressure controls:
1. Set the low side cut in setpoint by adjusting the low side range screw.
All-Range Controls: Turn the screw clockwise to raise the cut in setpoint.
MICRO-SET Controls: Turn the screw clockwise to lower the cut in setpoint.
2. Adjust the differential screw.
All-Range Controls: Turn the screw clockwise to raise the cut out setpoint.
MICRO-SET® Controls: Turn the screw clockwise to increase the differential value.
3. Set the high side cutout setpoint by adjusting the high side range screw. Turn the screw clockwise to raise the
cutout setpoint. (The high side differential is fixed.)
4. Set the reset operation (on P70S and P170S models only) for high side automatic reset or manual reset
lockout. See Convertible High Pressure Reset Mechanism on P70S and P170S Controls and Figure 9
.
IMPORTANT: Do not adjust pointers beyond the highest or lowest indicator marks on the control’s pressure
scale. Adjusting pointers beyond indicator marks may damage screw threads, may cause inaccurate control
operation, and will void the warranty.
Figure 9: Adjusting the Dual Pressure Controls

P70, P72, and P170 Series Controls for Dual Pressure Applications Installation Instructions
10
Manual Reset Operation
Pressure controls, with the Manual Reset option, lock out when they reach the cutout pressure setpoint and must
be manually reset by the user to restart the controlled equipment. The manual reset mechanism is trip-free and
cannot be overridden by blocking or tying the reset button down.
On locked-out equipment, first determine and remedy the cause of the lockout before proceeding.
• When lockout is caused by the control’s low side cutout, allow the sensed pressure to rise to the cut in setpoint.
• When lockout is caused by the control’s high side cutout, allow the sensed pressure to drop at least 70 psig
below the cutout setpoint.
After the sensed pressure has reached the desired pressure, press and release the Reset button to restore
operation of the controlled equipment.
Convertible High Pressure Reset Mechanism on P70S and P170S Controls
The P70S and P170S controls have a convertible high side pressure reset. The control may be set to reset
automatically after cutout (when the pressure drops to cutout minus differential), or to be manually reset after
cutout (by pressing down the reset lever).To change the reset operation:
1. Disconnect all power sources to the pressure control and remove the control cover.
2. For Manual Reset Operation: Loosen the lock nut, and unscrew the stop screw, being careful to not remove
the screw completely from the bracket. See Figure 10.
For Automatic Reset Operation: Loosen the lock nut, push the reset lever down, and screw in the stop screw
fully. See Figure 10.
3. Tighten the lock nut to hold the stop screw in place, and replace the control cover.
4. Restore all power sources and cycle the equipment to check control operation.
Low Pressure Limited Knob Adjustment
Some dual pressure controls are supplied with a Limited KnobAdjustment kit for the low pressure side (only) of the
control. This restricts the adjustment of the low-side range and differential screws, and deters overadjustment or
tampering with the control.A stop on the knob limits adjustment to less than one turn.
To install the Limited Knob Adjustment kit, see the following guidelines and steps.
1. To lock the differential adjustment screw and allow limited adjustment of the range screw, install the knob on
the range screw.
To lock the range screw and allow limited adjustment of the differential screw, install the knob on the differential
screw.
2. Adjust control pointers to desired high event and low event setpoints (on All-Range controls), or differential
setting (on MICRO-SET® controls).
Figure 10: Setting the Convertible High
Pressure Reset Mechanism (P70S or P170S

P70, P72, and P170 Series Controls for Dual Pressure Applications Installation Instructions
11
3. Place the spacer on the desired adjustment screw. All-Range controls (with Limited KnobAdjustment kits)
have round and knurled adjustment screws. The spacer must be placed on the range screw. MICRO-SET®
controls have square adjustment screws. Always place the spacer on the same adjustment screw as the knob.
4. Align the large end of the indicator plate over the adjustment screw with spacer.
5. Align the small end of the indicator plate over the adjustment screw to be locked.
6. Align the knob over the large end of the indicator plate.
7. Attach the knob to the adjustment screw, and tighten the set screw.
Note: The Limited KnobAdjustment kit for the All-Range controls cannot be used with the MICRO-SET® controls
(and vice-versa).
Technical Specifications
Table 4: SPST Electrical Ratings (P70L, M, N, and P170L, M, N Types)
Standard Single-Phase Ratings Hermetic
Compressor
1Ø Ratings
120 VAC 208 VAC 240 VAC 480 VAC1
1. Not for compressor motor loads.
600 VAC1208/240 VAC
Motor Horsepower 1.5 3 3 -- -- --
Motor Full Load Amperes 20 18.7 17 5 4.8 20
Motor Locked Rotor Amperes 120 112.2 102 30 28.8 120
Non-Inductive Amperes 22 22 22 -- -- --
Pilot Duty 125 VA at 120 to 600 VAC; 57.5 VA at 120 to 300 VDC
Table 5: 4-Wire 2-Circuit Electrical Ratings (P70P, Q, and R Types) (Part 1 of 2)
Standard Single-Phase Ratings
Line-M2 (Main Contacts) Line-M1 (Auxiliary Contacts)
120
VAC 208
VAC 240
VAC 277
VAC 480
VAC1600
VAC1120
VAC 208
VAC 240
VAC 277
VAC
Motor Full Load Amperes 16.0 9.2 8.0 -- 5 4.8 6.0 3.3 3.0 --
Motor Locked Rotor Amperes 96.0 55.2 48.0 -- 30 28.8 36.0 19.8 18.0 --
Figure 11: Limited Knob Adjustment

P70, P72, and P170 Series Controls for Dual Pressure Applications Installation Instructions
12
Non-Inductive Amperes 16.0 9.2 8.0 7.2 -- -- 6.0 6.0 6.0 6.0
Pilot Duty (for both sets of
contacts) 125 VA at 24 to 600 VAC; 57.5 VA at 120 to 300 VDC
1.Not for compressor motor loads.
Table 6:
SPDT Electrical Ratings (P70S and P170S Types, per switch)
Standard Single-Phase Ratings
120 VAC 208 VAC 240 VAC 277 VAC
Motor Full Load Ampere 16.0 9.2 8.0 7.0
Motor Locked Rotor Ampere 96.0 55.2 48.0 42.0
Non-Inductive Ampere 16.0 9.2 8.0 7.0
Pilot Duty 125 VA at 24 VAC, 720 VA at 120 to 277 VAC
Table 7: DPST Electrical Ratings (P72L, M, and N Types)
Standard Ratings Hermetic
Compressor
Ratings
120
VAC
1Ø
208
VAC
1Ø
240
VAC
1Ø
208
VAC
3Ø
220
VAC
3Ø
480
VAC
1Ø1
600
VAC
1Ø1
208
VAC
1Ø
240
VAC
1Ø
Motor Horsepower 2 3 3 5 5 -- -- -- --
Motor Full Load Amperes 24 18.7 17 15.9 15 5 4.8 24 24
Motor Locked Rotor Amperes 144 112.2 102 95.4 90 30 28.8 144 144
AC Non-Inductive Amperes 24 24 24 24 24 -- -- -- --
DC Non-Inductive Amperes 3 0.5 0.5 0.5 0.5 -- -- -- --
Pilot Duty 125 VA at 120 to 600 VAC; 57.5 VA at 120 to 300 VDC
1. Not for compressor motor loads
P70, P72, and P170 Controls for Dual Pressure Applications (Part 1 of 2 )
Switch Action P70, P170: SPST or 4-Wire, 2-Circuit
P70S, P170S: Two independent SPDT PENN® switches
P72: DPST
Pressure Connection P70, P72 Standard Models: various connections available (Styles 5, 13, 15, 34, 37)
P170 Standard Models 1/4 in. male flare hose connection (Style 5)
P70LA-2, P70MA-2 Ammonia-Compatible Models 1/4 in. female NPT connection (Style 15)
Maximum Overpressure
(non-recurring) Low Side All-Range: 325 psig (2,241 kPa)
Low Side MICRO-SET®: 525 psig (3,620 kPa)
High Side (All-Range and MICRO-SET®): 525 psig (3,620 kPa)
Maximum Working
Pressure Low Side All-Range: 100 psig (690 kPa)
Low Side MICRO-SET®: 80 psig (552 kPa)
High Side (All-Range and MICRO-SET®): 500 psig (3,447 kPa)
Ambient Conditions -40 to 140°F (-40 to 60°C)
Case and Cover NEMA 1 Enclosures: Galvanized steel case, plated and painted steel cover
NEMA 3R Enclosures: Plated and painted steel case and cover
Table 5: 4-Wire 2-Circuit Electrical Ratings (P70P, Q, and R Types) (Part 2 of 2)

P70, P72, and P170 Series Controls for Dual Pressure Applications Installation Instructions
® Johnson Controls and PENN are registered trademarks of Johnson Controls in the
United States of America and/or other countries. All other trademarks used herein are the property
of their respective owners. © Copyright 2018 by Johnson Controls. All rights reserved.
www.penncontrols.com
European Single Point of Contact: NA/SA Single Point of Contact: APAC Single Point of Contact:
JOHNSON CONTROLS
WESTENDHOF 3
45143 ESSEN
GERMANY
JOHNSON CONTROLS
507 E MICHIGAN ST
MILWAUKEE WI 53202
USA
JOHNSON CONTROLS
C/O CONTROLS PRODUCT MANAGEMENT
NO. 22 BLOCK D NEW DISTRICT
WUXI JIANGSU PROVINCE 214142
CHINA
13
Dimensions (H x W x D) NEMA 1 Enclosure: 3-1/4 x 5-11/16 x 2-1/16 in. (83 x 144 x 53 mm)
NEMA 3R Enclosure: 4-13/16 x 5-13/16 x 3-3/8 in. (122 x 148 x 86 mm)
Approximate
Shipping Weight NEMA 1 Enclosures
Individual: 3.5 lb (1.6 kg)
Bulk pack (25 controls): 75.5 lb (34.2 kg)
NEMA3R Enclosures
Individual: 4.7 lb (2.1 kg)
Bulk pack (25 controls): 116.5 lb (52.9 kg)
Agency Listings For information on specific models, contact Refrigeration Application Engineering at
1-800-275-5676.
Accessories 271-51 Universal Mounting Bracket (supplied with standard controls)
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, contact Refrigeration Application Engineering at 1-800-275-5676. Johnson Controls shall not be liable for damages resulting
from misapplication or misuse of its products.
P70, P72, and P170 Controls for Dual Pressure Applications (Part 2 of 2 )
Other manuals for P70 Series
1
This manual suits for next models
2
Table of contents
Other Penn Control Unit manuals

Penn
Penn System 450 Series User manual

Penn
Penn A421 Series User manual

Penn
Penn QREV Series User manual

Penn
Penn V46 Series User manual

Penn
Penn P70C User manual

Penn
Penn P72 Series User manual

Penn
Penn V43 Series Manual

Penn
Penn V46 Series Use and care manual

Penn
Penn System 450 Series User manual

Penn
Penn System 450 Series User manual