Penn V43 Series Manual

Refer to the QuickLIT website for the most up-to-date version of this document.
1
V43/V243 Series Pressure-Actuated Water-Regulating Valves Product/
Technical Bulletin
The V43/V243 Pressure-Actuated Water-Regulating
Valves are designed to regulate water flow through the
condenser of large refrigerated cooling systems. These
pilot-operated valves open on an increase in refrigerant
head pressure and provide modulating operation.
The V43/V243 water-regulating valves are available for
commercial and maritime applications.
V43 valves are available for non-corrosive low- and
medium-pressure refrigerants such as R-134A,
R-404A, R-502, and R-507. Specially designed V43
valves are also available for ammonia service (R-717).
V243 valves are available for non-corrosive
high-pressure refrigerants such as R410A.
Commercial V43/V243 valves are constructed with a
cast iron body, brass internal parts, and bronze seat
material.
To resist the corrosive action of sea water, the
V43/V243 maritime and navy models are constructed
with a red brass body, bronze and monel interior parts,
and monel seat material.
This product is made of a copper alloy, which
contains lead. The product is therefore not to be used
on drinking water.
Figure 1: V43 Pressure-Actuated Valve
Table 1: Features and Benefits
Features Benefits
Built-in Pilot Valve Allows more precise throttling.
Easy Adjustment Allows service and adjustment without breaking line connections.
Drain Plug Allows water to be drained during shutdown to reduce the possibility of
freeze-up.
Mesh Monel Screen Protects pilot valve from items such as dirt and scale and is easily
removed for cleaning and servicing without breaking any line
connections.
V43/V243 Series Pressure-Actuated Water-Regulating
Valves
Product/Technical Bulletin Code No. LIT-125683
Part No. 24-7664-699, Rev. D
Issued August 2018

V43/V243 Series Pressure-Actuated Water-Regulating Valves Product/Technical Bulletin
2
Application
Note: The V43 and V243 Series Head Pressure
Regulating Valves are available for cooling applications
only (direct acting).
Operation
The V43/243 valves are refrigerant actuated units,
requiring only system refrigerant head pressure to
operate (no electrical power is required). Only the inlet
and outlet water lines and refrigerant head pressure
connections need to be made for the valve to function.
A built-in pilot valve, driven by refrigerant head
pressure, operates the main valve using water and
spring pressures as the opening and closing forces.
The main valve seat disc assembly is suspended on a
heavy duty rubber diaphragm, eliminating any
close-fitting or sliding parts. This reduces friction within
the valve, allowing more reliable control. Also, the
chance of the valve stem sticking in dirty water
conditions is reduced.
Determining the Required Valve Size
Every system is unique and requires specific
engineering data to properly size and design. Typically,
a valve is replaced with another valve of the same size.
To select the correct valve size, determine the following
variables:
• Maximum Water Flow Required
• Available Water Pressure Drop (Differential) across
the Valve
Use these variables to locate a point on one of the flow
capacity charts (Figure 5 through Figure 12) that
slightly exceeds the maximum water flow required. The
flow capacity chart containing this point represents the
proper valve size.
Maximum Water Flow Required
Use the information provided by the manufacturer of
the condensing unit to determine the maximum water
flow required. If this information is not available,
calculate the maximum water flow required by using
the following formula:
Example: If a 100-ton capacity system has an inlet
water temperature of 85°F and an outlet water
temperature of 95°F, the maximum water flow required
is:
Available Water Pressure Drop (Differential)
across the Valve
The available water pressure drop (differential) across
the valve is the supply pressure to the valve minus all
downstream pressures. This pressure drop is the force
available to push water through the valve.
Water supply pressure is the water pressure supplied
to the inlet side of the valve from a cooling tower, a city
water main, or other source.
Opening Point - the Refrigerant Head
Pressure Rise Above the Opening Point
The forces that operate the valve are refrigerant head
pressure, water pressure, and spring pressure. These
forces oppose each other.
IMPORTANT: All V43/V243 water-regulating valves
are designed for use only as operating devices.
Where valve failure can result in personal injury and
loss of property, it is the responsibility of the installer
to add and maintain devices (pressure relief or
safety shutoff) or systems (alarm or supervisory)
that protect against or warn of device failure.
IMPORTANT: An undersized valve does not deliver
the required amount of water flow under full load
conditions, and an oversized valve tends to hammer
under low load conditions.
Maximum Water
Flow Required (GPM)
Tons of Refrigeration x 30
Outlet Temperature - Inlet Temperature
=
Maximum Water
Flow Required
100 x 30
95 - 85
=
Maximum Water
Flow Required =300 GPM
Figure 2: Pressure Drop across the Valve
Cooling Tower
Pump
P
1
P
2
PP
Loss 1
Loss 2
V43/V243
P
IN
COND
PP
1
P
2
=-
LOSS
PP
P
Loss 1 Loss 2
=++ ...
Condenser
FIG:2wy_prss_drp
P=P-(P +P)
DROP
IN COND LOSS
Pressure Drop
Across the
Valve
All Downstream Pressure Drops (Across
Condensor Piping, Pipe Fittings, and Valves)
=Supply
Pressure -

V43/V243 Series Pressure-Actuated Water-Regulating Valves Product/Technical Bulletin
3
When the head pressure rises, and the refrigerant
pressure overcomes the spring force (pilot valve), the
valve begins to open (the disk lifts off of the seat). This
point is called the opening point.
The opening point is adjusted by increasing or
decreasing the spring force by using the adjustment
stem. If the head pressure continues to rise, the
refrigerant pressure further opens the valve until the
valve is fully open. The range from the point where the
valve lifts off the seat (the opening point) to the point
where the valve is fully open is called the throttling
range.
The throttling range is fixed and cannot be adjusted.
The throttling range is approximately 40 psig for the
low-pressure V43 Series Valves, approximately 50 psi
for the medium-pressure V43 Series Valves, and
approximately 60 psi for the high pressure V243 Series
Valves.
Head Pressure Rise Above the Opening Point
When the head pressure rises, the force of the
refrigerant head pressure overcomes the spring force
(plus any hysteresis) and pushes the disc off the seat,
allowing water to start flowing through the valve.
Anything above that point is head pressure rise above
the opening point. Typically, the opening point is
approximately 7 psi above the closing point.
Proper Valve Size
A properly sized valve meets the requirements of the
maximum water flow required yet functions at an
acceptable level when minimum flow is required (does
not water hammer, cut, or wire draw the seats and
seating discs). See Figure 3 and Figure 4 to select the
correct valve size for your application.
Use the following steps to help determine the
appropriate valve size for your application:
1. Locate the point where the valve is fully open on
the Refrigerant Head Pressure Rise Above Valve
Opening Point (y-axis).
2. Draw a horizontal line from this point to where the
line intersects with the Water Pressure Available
WPA curve. This is Point A.
3. Draw a vertical line from point A to where it
intersects with Maximum Water Flow Available line
(x-axis). This is Point B.
Point B is the maximum amount of water that the
valve can flow, when fully open, under the stated
conditions. See Figure 3.
4. Locate the Maximum Water Flow Required for your
application (x-axis). This is Point C.
5. Draw a vertical line from Point C to where the line
intersects with the WPA curve. This Point D.
6. Draw a horizontal line from Point D to the left
where it intersects with the Refrigerant Head
Pressure Rise Above Opening Point.
This is where the selected value meets the
maximum flow requirement of the application.
Use the flow charts to select the valve that is most
appropriate for your application.
Example
In this example, the required flow for an R-404A
system is 300 GPM. The cooling tower pump discharge
pressure is 30 psig, and the condenser manufacturer's
table gives a pressure drop through the condenser at
8 psid. The pressure drop through the installed piping,
fittings, and valves is approximately 12 psi.
Maximum Water Flow Required = 300 GPM
Water Pressure Available= 30 - (12 + 8)
Water Pressure Available= 10 psid
You need to select the proper valve size. The proper
size valve is indicated by the flow chart that slightly
exceeds the maximum required flow when the valve is
wide open.
Refrigerant
Head
Pressure
Rise Above
Opening
Point
Refrigerant Head
Pressure at
Opening Point
=
Refrigerant
Head Pressure greater
than Opening Point
-
Figure 3: Capacity Chart
Water Pressure Available Across Valve (psid)
Maximum Water Flow Required
Value Determined in Step 1
Difference ensures
that the valve
meets the maximum
flow rate required.
CAPACITY CHART REPRESENTING
THE PROPER VALVE SIZE
Refrigerant Head Pressure Rise Above
Valve Opening Point (psig)
Point B
WPA Curve
Point C
Point A
FIG:capacity chart
Point D

V43/V243 Series Pressure-Actuated Water-Regulating Valves Product/Technical Bulletin
4
As indicated in Figure 4, the correct valve for this
application is a 3-inch medium-pressure (160/260 psi),
non-corrosive, commercially constructed V43 Series
Valve. The maximum water flow that a 3-inch valve can
deliver (300 GPM) under the stated condition is slightly
greater than the maximum water flow required (300
GPM).
Note: The maximum flow required for the application
is to the left of the dotted vertical line between Point A
and Point B (300 GPM when the valve is approximately
72% open).
Select the valve type from Table 5 through Table 7.
Point Where Valve is Wide Open and Intersects
with the WPA Curve
Maximum Flow the Valve Provides Under the Given
Conditions (Valve Wide Open with a 10 psid)
Maximum Water Flow Required for the Application
Head Pressure Rise Above Opening Point Where
Maximum Flow Required for the Application Occurs
Point
A
Point
C
= 36 psig
= Appr. 330 GPM
= 300 GPM
Point
D
Point
B
= 50 psig
Figure 4: Correct Valve Size for Application
CAPACITY CHART FOR 3 in. VALVE
40
30
20
10
0
Medium Pressure
Refrigerants
Low Pressure
Refrigerants
10
100 200 300 400 500 600 700 800 900
20 30 50
Water Pressure Available Across Valve (psid)
40
50
30
20
10
0
Refrigerant Head Pressure Rise Above
Valve Opening Point (psig)
Water Flow (GPM)
Point A
Point B
Point C
FIG:Valve Size
Point D

V43/V243 Series Pressure-Actuated Water-Regulating Valves Product/Technical Bulletin
5
V43 Capacity Flow Charts
Figure 5: 2 in. V43 Capacity Flow Chart
40
40
50
30
30
20
20
10
10
0
0
Refrigerant Head Pressure Rise Above
Valve Opening Point (psig)
10
50 100 150 200 250 300 350 400 450
20 30 50
Water Flow (GPM)
Water Pressure Available Across Valve (psid)
CAPACITY CHART FOR 2 in. VALVE
Medium Pressure
Refrigerants
Low Pressure
Refrigerants
Figure 6: 2-1/2 in. V43 Capacity Flow Chart
40
30
20
10
0
10
50 100 150 200 250 300 350 400 450
20 30 50
Water Pressure Available Across Valve (psid)
40
50
30
20
10
0
Refrigerant Head Pressure Rise Above
Valve Opening Point (psig)
Water Flow (GPM)
CAPACITY CHART FOR 2-1/2 in. VALVE
Medium Pressure
Refrigerants
Low Pressure
Refrigerants
Figure 7: 3 in. V43 Capacity Flow Chart
40
30
20
10
0
10
100 200 300 400 500
600
700
800
900
20 30 50
Water Pressure Available Across Valve (psid)
CAPACITY CHART FOR 3 in. VALVE
40
50
30
20
10
0
Refrigerant Head Pressure Rise Above
Valve Opening Point (psig)
Water Flow (GPM)
Medium Pressure
Refrigerants
Low Pressure
Refrigerants
Figure 8: 4 in. V43 Capacity Flow Chart
40
30
20
10
0
5
150 300 450 600 750
900
1050 1200 1350
10 20 30 50
Water Pressure Available Across Valve (psid)
CAPACITY CHART FOR 4 in. VALVE
40
50
30
20
10
0
Refrigerant Head Pressure Rise Above
Valve Opening Point (psig)
Water Flow (GPM)
Medium Pressure
Refrigerants
Low Pressure
Refrigerants

V43/V243 Series Pressure-Actuated Water-Regulating Valves Product/Technical Bulletin
6
V243 Capacity Flow Charts
Figure 9: 2 in. V243 Capacity Flow Chart
60
40
20
0
10
50 100 150 200 250 300 350 400 450
20 30 50
Water Pressure Available Across Valve (psid)
Refrigerant Head Pressure Rise Above
Valve Opening Point (psig)
Water Flow (GPM)
CAPACITY CHART FOR 2 in. VALVE
2 5 14.5 25 40 60
Figure 10: 2-1/2 in. V243 Capacity Flow Chart
60
40
20
0
10
100 200 300 400 500 600 700 800 900
20 30 50
Water Pressure Available Across Valve (psid)
Refrigerant Head Pressure Rise Above
Valve Opening Point (psig)
Water Flow (GPM)
CAPACITY CHART FOR 2-1/2 in. VALVE
25 14.52540 60
Figure 11: 3 in. V243 Capacity Flow Chart
60
40
20
0
10
100 200 300 400 500 600
700
800
900
20 30 50
Water Pressure Available Across Valve (psid)
Refrigerant Head Pressure Rise Above
Valve Opening Point (psig)
Water Flow (GPM)
CAPACITY CHART FOR 3 in. VALVE
2 5 14.5 25 40 60
Figure 12: 4 in. V243 Capacity Flow Chart
60
40
20
0
10
100 200 300 400 500 600 700 800 900
20 30 50
Water Pressure Available Across Valve (psid)
Refrigerant Head Pressure Rise Above
Valve Opening Point (psig)
Water Flow (GPM)
CAPACITY CHART FOR 4 in. VALVE
2 5 14.5 25 40 60
1000 1100
1200
1300

V43/V243 Series Pressure-Actuated Water-Regulating Valves Product/Technical Bulletin
7
Installation and Initial Adjustment
1. Flush the lines to remove any foreign matter before
connecting the lines to the valve. See Servicing.
2. Screw each companion flange and gasket onto the
inlet and outlet water lines as indicated in
Figure 13. The inside of the companion flange is
threaded. See Table 10 for flange and gasket kit
information.
3. Mount the V43/V243 valves so that the water flow
follows in the direction indicated by the arrow on
the V43/V243 casting.
Mount the V43/V243 valves onto a horizontal water
line, with the bellows up.
4. Secure the inlet and outlet water lines (with
companion flange and gasket) to the inlet and
outlet flange connections on the V43/V243 valves
with hex bolts and nuts.
5. Connect a 1/4-inch copper (or UltraCap) tube from
the bellows of the V43/V243 valves to the
refrigerant line as indicated in Figure 14. (In
reciprocating compressor applications, make the
refrigerant connection as far from the compressor
discharge as possible.) If possible, make the
connection on the outlet side of the condenser.
6. Manually flush the valve to remove debris. See
Servicing.
7. Put the system into operation under normal
operating conditions.
8. Determine the correct refrigerant operating head
pressure for the system. Observe the refrigerant
pressure indicated at the high side pressure
service gauge.
9. If necessary, adjust the operating head pressure as
instructed in the Valve Adjustment section.
Checkout Procedure
Note: Before operating equipment, always manually
flush the valve. See Servicing.
Before leaving the installation site, observe at least
three complete operating cycles (bellows open and
close) to verify that all components are functioning
properly.
Valve Adjustment
Make adjustments gradually. Adjust by 1/2 revolution
and wait for the system to stabilize after each
adjustment change. The throttling range (differential) is
not adjustable.
• To increase the opening point of the valve, turn the
adjusting screw (Figure 15, inset) inward, away
from main valve body (clockwise) as viewed from
the bottom up.
• To decrease the opening point, turn the adjusting
screw outward, toward the main valve body
(counterclockwise).
Figure 13: V43/V243 Gasket and Flange
Connections (V43AV Shown)
Companion Flange
Nut
Hex Bolt
Inlet
Flange Connection
Water Line
Gasket
FIG:Gasket Connections
Figure 14: V43/V243 Connections and
Adjustments (V43AV Shown)
Inlet
Flange
Connection
Outlet
Flange
Connection
Bellows
Drain Plug
Adjusting
Screw
To Refrigerant Line
1/4 in. Copper (or UltraCap) Tube
FIG:Adjustments

V43/V243 Series Pressure-Actuated Water-Regulating Valves Product/Technical Bulletin
8
Servicing
The V43/V243 valves can be disassembled, cleaned,
and reassembled without breaking the line
connections.
Accessing Internal Parts
1. Shut off water flow to the V43/V243 valves.
2. Remove the hex bolts (Figure 15) from the top of
the bellows flange.
3. Remove the bellows flange.
Note: For internal parts replacement instructions,
refer to the respective replacement parts
instruction sheet.
Manual Flushing
Before starting equipment, manually flush the valve to
remove any foreign material from the valve.
1. Turn the adjusting screw (Figure 15, inset)
clockwise, raising the adjusting screw away from
the valve body as much as possible (count the
number of turns for reference).
2. Insert a standard slotted screwdriver tip between
the adjusting screw and the push pin.
3. Pry the push pin down with the screwdriver to open
the valve as indicated.
4. Hold the push pin down to hold the valve open.
Flush the valve for several minutes, removing all
foreign matter from the V43/V243 valves.
5. After flushing the V43/V243 valves, remove the
screwdriver and set the adjusting screw to the
desired operating pressure. See Valve Adjustment.
Cleaning the Monel Screen
The pilot valve is protected from debris by a fine mesh
monel screen. To clean the screen, shut off the water
supply, relieve the water pressure, unscrew the hex
bolt (Figure 15), remove the monel screen, brush, and
rinse clean.
Draining the V43/V243 Valves During
Shutdown
To reduce the possibility of freeze-up, drain the
V43/V243 valves during shutdown. To drain, unscrew
the drain plug at the base of the V43/V243 valves. See
Figure 15.
Note: In order to drain, the V43/V243 valves must be
mounted in a horizontal water line with the bellows up
and the drain plug down.
Figure 15: Monel Screen, Drain Plug, and
Manual Flushing Procedures
Drain Plug
Monel Screen
Bolt
Manual Flushing Procedures
Bellows
Flange
Hex Bolt
Push Pin
Adjusting
Screw
Insert screwdriver
tip between
adjusting screw
and push pin.
Pry push pin
down to open
valve.
FIG:Drain Plug

V43/V243 Series Pressure-Actuated Water-Regulating Valves Product/Technical Bulletin
9
Dimensions
V43/V243 Valves Dimensions
Figure 16: V43/V243 Flange Connection
Valves Dimensions
F
H
D
D
D
G
G
G
B
A
C
E
E
E
6- and 8-
Flange Hole Configurations
FIG:Dimensions
Table 2: Dimensions
Symbol 2 Inch 2-1/2 Inch 3 Inch 4 Inch
A19-1/2 in. (241 mm) 10-3/4 in. (273 mm) 11-3/4 in. (298 mm) 14 in. (356 mm)
B7-1/2 in. (191 mm) 8 in. (203 mm) 9 in. (229 mm) 10-3/4 in. (273 mm)
C4-3/4 in. (121 mm) 5-1/2 in. (140 mm) 6 in. (152 mm) 7-1/2 in. (191 mm)
D6 in. (152 mm) 7 in. (178 mm) 7-1/2 in. (191 mm) 9 in. (229 mm)
E2-1/8 in. (54 mm) 2-5/8 in. (67 mm) 3-1/8 in. (80 mm) 4-1/8 in. (105 mm)
F215-1/4 in. (387 mm) 15-9/16 in. (395 mm) 16-9/16 in. (421 mm) 18-7/32 in. (462 mm)
F315-29/32 in. (404 mm) 16-7/32 in. (412 mm) 17-7/32 in. (437 mm) 18-7/8 in. (479 mm)
G3/4 in. (19.05 mm) Dia. (4) 3/4 in. (19.05 mm) Dia. (4) 3/4 in. (19.05 mm) Dia. (4) 3/4 in. (19.05 mm) Dia. (8)
H3-5/8 in. (92 mm) 3-15/16 in. (100 mm) 4-1/4 in. (108 mm) 5-1/16 in. (128 mm)
1. Flange face to flange face.
2. These are the measurements for the V43 valves.
3. These are the measurements for the V243 valves.

V43/V243 Series Pressure-Actuated Water-Regulating Valves Product/Technical Bulletin
10
Selection
When ordering V43/V243 valves, specify the complete
product code number including an optional companion
flange and gasket kit. A companion flange and gasket
kit is required to mount the water lines to commercial
type V43/V243 water-regulating valves.
Table 3: Valve Construction and Pressure Type
Designator Construction and Pressure Type
ACommercial Service with Iron Body, Open on Pressure Increase, V43
BMaritime Service with Brass Body, Open on Pressure Increase, V43
CNavy Service with Brass Body, Open on Pressure Increase, V43
GCommercial Service with Iron Body, Open on Pressure Increase, V243
HMaritime Service with Brass Body, Open on Pressure Increase, V243
Table 4: Flange Size
Designator Flange Size
S2 in.
T2-1/2 in.
V3 in.
W4 in.
Table 5: V43 Series Pressure Actuated Water Valves (except NAVSEA valves, see Table 6)
Code Number Pipe Size (in.) Inlet and Outlet Opening Point Adjustment
Range psig (kPa)
Ship Wt. lb (kg)
Commercial Type – Non-Corrosive Refrigerants (R)
V43AS-1C 2 4 Hole ASME Flanged 70 to 150 (483 to 1,034) 59 (26.76)
V43AS-2C 160 to 260 (1,103 to 1,793)
V43AT-1C 2-1/2 70 to 150 (483 to 1,034) 65 (29.48)
V43AT-2C 140 to 260 (1,103 to 1,793)
V43AV-1C 3 70 to 150 (483 to 1,034) 90 (40.82)
V43AV-2C 160 to 260 (1,103 to 1,793) 90 (40.82)
V43AW-2C 4 8 Hole ASME Flanged 142 (64.41)
Commercial Type - Ammonia (R)
V43AV-5C 3 160 to 260 (1,103 to 1,793) 90 (40.82)
Maritime Type – Non-Corrosive Refrigerants (R)
V43BS-6C 2 4 Hole ASME Flanged 70 to 150 (483 to 1,034) 59 (26.76)
V43BS-7C 160 to 260 (1,103 to 1,793)
V43BT-6C 2-1/2 70 to 150 (483 to 1,034) 65 (29.48)
V43BT-7C 140 to 260 (1,103 to 1,793)
V43BV-10C 3 70 to 150 (483 to 1,034) 90 (40.82)
V43BV-7C 140 to 260 (1,103 to 1,793)

V43/V243 Series Pressure-Actuated Water-Regulating Valves Product/Technical Bulletin
11
Table 6: V43 Series Pressure Actuated Water Valves, Navy NAVSEA Certified
Code
Number
Pipe Size
(in.)
Inlet and Outlet Pressure Connector Opening Point Adjustment
Range – psig (kPa)
Ship Wt.
lb (kg)
Navy NAVSEA Certified – Non-Corrosive Refrigerants (R)
V43BS-3C 2 4 Hole ASME Flange 1/4 in. Male Flared Conn. 70 to 150 (483 to 1,034) 59
(26.76)
V43CS-1C 6 Hole Navy Flange
V43CS-2C Female Sweat Conn.
V43BT-3C 2-1/2 4 Hole ASME Flange 1/4 in. Male Flared Conn. 65
(29.48)
V43CT-2C 6 Hole Navy Flange
V43BV-4C 3 4 Hole ASME Flange Female Sweat Conn. 90
(40.82)
V43CV-1C 8 Hole Navy Flange 1/4 in. Male Flared Conn.
V43CV-2C Female Sweat Conn.
V43BW-7C 4 8 Hole ASME Flange 1/4 in. Male Flared Conn. 142
(64.41)
V43BW-2C 140 to 260 (1,103 to 1,793)
Table 7: V243 Series Pressure Actuated Water Valves
Code
Number
Pipe Size
(in.)
Inlet and Outlet Opening Point Adjustment
Range – psig (kPa)
Ship Wt.
lb (kg)
Commercial Type – High Pressure Refrigerants
V243GS-1C 2 4 Hole ASME Flange 200 to 400 (1,379 to 2,758) 59 (26.76)
V243GT-1C 2-1/2 65 (29.48)
V243GV-1C 390 (40.82)
V243GW-1C 4 8 Hole ASME Flange 142 (64.41)
Maritime Type – High Pressure Refrigerants
V243HS-1C 2 4 Hole ASME Flange 200 to 400 (1,379 to 2,758) 59 (26.76)
V243HT-1C 2-1/2 65 (29.48)
V243HV-1C 390 (40.82)
V243HW-1C 4 8 Hole ASME Flange 142 (64.41)

V43/V243 Series Pressure-Actuated Water-Regulating Valves Product/Technical Bulletin
12
Repair and Replacement Information
If a V43/V243 Pressure-Actuated Water-Regulating
Valve fails to operate within its specifications,
replacement sensing elements, internal parts, and
diaphragms are available for valve repair.
See Servicing for servicing instructions.
To obtain replacement parts kits instructions and
details, contact your nearest Johnson Controls®
distributor at http://cgproducts.johnsoncontrols.com/
dist_locate/locateDIST.asp.
For replacement parts kits product code numbers, see
Table 8 and Table 9.
Table 8: Repair Parts (Part 1 of 2)1
Model Diaphragm
Kit
Seat Disc and
Diaphragm Kit
Seat Repair Kit Screen
Repair Kit
Push Rod
Kit2
Sensing
Element Kit
Disc Body
Kit
V43AS-1C DPM18A-600R DSC16A-600R STT19A-602R SCN10A-600R ROD18A-600R SEP88A-600R DBK11A-600R
V43AS-2C DPM18A-600R DSC16A-600R STT19A-602R SCN10A-600R ROD18A-600R SEP88A-601R DBK11A-600R
V43AS-5C DPM18A-600R DSC16A-600R STT19A-602R SCN10A-600R ROD18A-600R SEP87A-600R DBK11A-600R
V43AT-1C DPM18A-601R DSC16A-601R STT19A-603R SCN10A-600R ROD18A-601R SEP88A-600R DBK11A-601R
V43AT-2C DPM18A-601R DSC16A-601R STT19A-603R SCN10A-600R ROD18A-601R SEP88A-601R DBK11A-601R
V43AT-5C DPM18A-601R DSC16A-601R STT19A-603R SCN10A-600R ROD18A-601R SEP87A-600R DBK11A-601R
V43AV-1C DPM18A-602R DSC16A-602R STT19A-606R SCN10A-600R ROD18A-601R SEP88A-600R DBK11A-602R
V43AV-2C DPM18A-602R DSC16A-602R STT19A-606R SCN10A-600R ROD18A-601R SEP88A-601R DBK11A-602R
V43AV-5C DPM18A-602R DSC16A-602R STT19A-606R SCN10A-600R ROD18A-601R SEP87A-600R DBK11A-602R
V43AW-1C DPM18A-603R DSC16A-603R STT19A-608R SCN10A-600R ROD18A-602R SEP88A-600R DBK11A-603R
V43AW-2C DPM18A-603R DSC16A-603R STT19A-608R SCN10A-600R ROD18A-602R SEP88A-601R DBK11A-603R
V43AW-5C DPM18A-603R DSC16A-603R STT19A-608R SCN10A-600R ROD18A-602R SEP87A-600R DBK11A-603R
V43BS-1C1DPM18A-600R DSC16A-600R STT19A-602R SCN10A-601R ROD18A-602R SEP88A-600R DBK11A-600R
V43BS-2C1DPM18A-600R DSC16A-600R STT19A-602R SCN10A-601R ROD18A-602R SEP88A-601R DBK11A-600R
V43BS-3C DPM18A-600R DSC16A-600R STT19A-600R SCN10A-601R ROD18A-602R SEP88A-600R DBK10A-600R
V43BS-6C DPM18A-600R DSC16A-600R STT19A-600R SCN10A-601R ROD18A-602R SEP88A-600R DBK10A-600R
V43BS-7C DPM18A-600R DSC16A-600R STT19A-600R SCN10A-601R ROD18A-602R SEP88A-601R DBK10A-600R
V43BT-1C1DPM18A-601R DSC16A-601R STT19A-603R SCN10A-601R ROD18A-603R SEP88A-600R DBK11A-601R
V43BT-2C1DPM18A-601R DSC16A-601R STT19A-603R SCN10A-601R ROD18A-603R SEP88A-601R DBK11A-601R
V43BT-3C DPM18A-601R DSC16A-601R STT19A-605R SCN10A-601R ROD18A-603R SEP88A-600R DBK10A-602R
V43BT-6C DPM18A-601R DSC16A-601R STT19A-605R SCN10A-601R ROD18A-603R SEP88A-600R DBK10A-602R
V43BT-7C DPM18A-601R DSC16A-601R STT19A-605R SCN10A-601R ROD18A-603R SEP88A-601R DBK10A-602R
V43BV-1C1DPM18A-602R DSC16A-602R STT19A-606R SCN10A-601R ROD18A-603R SEP88A-600R DBK11A-602R
V43BV-2C1DPM18A-602R DSC16A-602R STT19A-606R SCN10A-601R ROD18A-603R SEP88A-601R DBK11A-602R
V43BV-4C DPM18A-602R DSC16A-602R STT19A-607R SCN10A-601R ROD18A-603R SEP88A-600R DBK10A-601R
V43BV-5C1DPM18A-602R DSC16A-602R STT19A-606R SCN10A-601R ROD18A-603R SEP88A-600R DBK11A-602R
V43BV-6C1DPM18A-602R DSC16A-602R STT19A-606R SCN10A-601R ROD18A-603R SEP88A-601R DBK11A-602R
V43BV-7C DPM18A-602R DSC16A-602R STT19A-607R SCN10A-601R ROD18A-603R SEP88A-601R DBK10A-601R
V43BV-8C DPM18A-602R DSC16A-602R STT19A-607R SCN10A-601R ROD18A-603R SEP88A-600R DBK10A-601R
V43BV-9C DPM18A-602R DSC16A-602R STT19A-607R SCN10A-601R ROD18A-603R SEP88A-601R DBK10A-601R
V43BV-10C DPM18A-602R DSC16A-602R STT19A-607R SCN10A-601R ROD18A-603R SEP88A-600R DBK10A-601R
V43BW-1C DPM18A-603R DSC16A-603R STT19A-609R SCN10A-601R ROD18A-602R SEP88A-600R DBK10A-603R
V43BW-2C DPM18A-603R DSC16A-603R STT19A-609R SCN10A-601R ROD18A-602R SEP88A-601R DBK10A-603R
V43BW-5C DPM18A-603R DSC16A-603R STT19A-609R SCN10A-601R ROD18A-602R SEP88A-600R DBK10A-603R
V43BW-6C DPM18A-603R DSC16A-603R STT19A-609R SCN10A-601R ROD18A-602R SEP88A-601R DBK10A-603R
V43BW-7C DPM18A-603R DSC16A-603R STT19A-609R SCN10A-601R ROD18A-602R SEP88A-600R DBK10A-603R
V43CS-1C DPM18A-600R DSC16A-600R STT19A-600R SCN10A-601R ROD18A-602R SEP88A-600R DBK10A-600R
V43CS-2C DPM18A-600R DSC16A-600R STT19A-600R SCN10A-601R ROD18A-602R SEP88A-600R DBK10A-600R
V43CS-3C DPM18A-600R DSC16A-600R STT19A-600R SCN10A-601R ROD18A-604R SEP88A-600R DBK10A-600R

V43/V243 Series Pressure-Actuated Water-Regulating Valves Product/Technical Bulletin
13
The following valves, manufactured after date code
8702, contain monel interior trim. Order replacement
kits as listed in Table 8 or V43xx and V243xx Series
Repair Parts Kits Technical Bulletin (LIT-121690).
V43CT-1C DPM18A-601R DSC16A-601R STT19A-605R SCN10A-601R ROD18A-603R SEP88A-600R DBK10A-602R
V43CT-2C DPM18A-601R DSC16A-601R STT19A-605R SCN10A-601R ROD18A-603R SEP86A-600R DBK10A-602R
V43CV-1C DPM18A-602R DSC16A-602R STT19A-607R SCN10A-601R ROD18A-603R SEP86A-600R DBK10A-601R
V43CV-2C DPM18A-602R DSC16A-602R STT19A-607R SCN10A-601R ROD18A-603R SEP88A-600R DBK10A-601R
V243GS-1C DPM18A-600R DSC16A-600R STT19A-602R SCN10A-600R ROD18A-600R SEP90A-600R DBK11A-600R
V243GT-1C DPM18A-601R DSC16A-601R STT19A-603R SCN10A-600R ROD18A-601R SEP90A-600R DBK11A-601R
V243GV-1C DPM18A-602R DSC16A-602R STT19A-606R SCN10A-600R ROD18A-601R SEP90A-600R DBK11A-602R
V243GW-1C DPM18A-603R DSC16A-603R STT19A-608R SCN10A-600R ROD18A-600R SEP90A-600R DBK11A-603R
V243HS-1C DPM18A-600R DSC16A-600R STT19A-600R SCN10A-601R ROD18A-602R SEP90A-600R DBK10A-600R
V243HT-1C DPM18A-601R DSC16A-601R STT19A-605R SCN10A-601R ROD18A-603R SEP90A-600R DBK10A-601R
V243HV-1C DPM18A-602R DSC16A-602R STT19A-607R SCN10A-601R ROD18A-603R SEP90A-600R DBK10A-602R
V243HW-1C DPM18A-603R DSC16A-603R STT19A-609R SCN10A-601R ROD18A-602R SEP90A-600R DPK10A-603R
1. Repair parts are supplied in kits only and include all parts required to recondition that portion of the valve. To order, specify code number only.
2. Replacement push rod kit requires a seat repair kit and/or a diaphragm kit when replaced.
Table 8: Repair Parts (Part 2 of 2)1
Model Diaphragm
Kit
Seat Disc and
Diaphragm Kit
Seat Repair Kit Screen
Repair Kit
Push Rod
Kit2
Sensing
Element Kit
Disc Body
Kit
Table 9: Parts Kits
Valve Model Order Parts Kits for:
V43BS-1C V43BS-6C
V43BS-2C V43BS-7C
V43BT-1C V43BT-6C
V43BT-2C V43BT-7C
V43BV-1C V43BV-10C
V43BV-2C V43BV-7C
V43BV-5C V43BV-10C
V43BV-6C V43BV-9C

V43/V243 Series Pressure-Actuated Water-Regulating Valves Product/Technical Bulletin
14
Accessories
A companion flange and gasket kit is required to mount
the water lines to commercial type V43/V243
water-regulating valves.
Table 10: Companion Flanges and Gaskets
Kit Code Number Water Valve Size (in.) Shipping Wt. lb (kg)
KIT14A-613 1’22 11.8 (5.4)
KIT14A-614 1’22-1/2 16.5 (7.5)
FLG15A-600 1’33 20 (9.1)
FLG15A-601 1’34 34 (15.4)
1. Commercial valves only.
2. See Figure 17 for a diagram of the parts included in the flange and gasket kit for the
2-inch and 2-1/2-inch valves.
3. See Figure 18 for a diagram of the parts included in the flange and gasket kit for the
3-inch and 4-inch valves.
flange
Ring
Gasket (2)
Cast Iron
Flange (2)
Machine
Bolt (8)
Hex
Nut (8)
Figure 17: KIT14A
Figure 18: FLG15A
Gasket (2)
Cast Iron Flange (2)
Hex Nut (8)
Machine Bolt (8)
FIG:FLG15A

V43/V243 Series Pressure-Actuated Water-Regulating Valves Product/Technical Bulletin
15
® Johnson Controls and PENN are registered trademarks of Johnson Controls in the
United States of America and/or other countries. All other trademarks used herein are the property
of their respective owners. © Copyright 2018 by Johnson Controls. All rights reserved.
www.penncontrols.com
Technical Specifications
V43/V243 Pressure-Actuated Water-Regulating Valves
Maximum Water Supply Pressure 150 psig (1,034 kPa)
V43 Maximum Head Pressure 300 psig (2,068 kPa)
V243 Maximum Head Pressure 630 psig (4,344 kPa)
Head Pressure Range (Opening Points) V43 Low Pressure
Refrigerants
R-134A – 70 to 150 psig (482 to 1,034 kPa)
Medium
Pressure
Refrigerants
R-22, R-502, R404A – 160 to 260 psig (1,103
to 1,793 kPa)
Ammonia 160 to 260 psig (1,103 to 1,793 kPa)
V243 High Pressure R410A – 200 to 400 psig (1,379 to 2,758 kPa)
Factory Settings1
1. Factory setpoint for the valve is adjustable.
V43 Low Pressure
Refrigerants
90 psig (621 kPa)
Medium
Pressure
Refrigerants
180 psig (1,241 kPa)
Ammonia 180 psig (1,241 kPa)
V243 High Pressure 200 psig (1,379 kPa)
Maximum Water Supply Temperature 160°F (71°C)
Valve Body Material Commercial Cast Iron
Maritime Red Brass
Internal Parts Material Commercial Brass
Maritime Bronze, Monel
Seat Material Pilot Monel
Main Valve Commercial – Bronze, Maritime – Monel
Seat Disc Material Buna N™
Packing – Bellows Assembly Brass Stem, Stainless Steel Spring, Synthetic
Rubber Boot
Pressure Connection Refrigerant Side Non-corrosive 1/4 in. SAE Male Flare
Ammonia 1/4 in. FNPT
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, contact Johnson Controls/PENN Refrigeration Technical Support at 1-800-275-5676. Johnson Controls shall not be liable for
damages resulting from misapplication or misuse of its products.
This manual suits for next models
51
Table of contents
Other Penn Control Unit manuals

Penn
Penn P70 Series User manual

Penn
Penn A421 Series User manual

Penn
Penn System 450 Series User manual

Penn
Penn V46 Series User manual

Penn
Penn System 450 Series User manual

Penn
Penn V246 Series User manual

Penn
Penn P72 Series User manual

Penn
Penn System 450 C450RCN-1 User manual

Penn
Penn QREV Series User manual

Penn
Penn System 450 Series User manual
Popular Control Unit manuals by other brands

Zurn Wilkins
Zurn Wilkins 4-ZW207 Installation, Troubleshooting, Maintenance Instructions

Carel
Carel EVD0000UC0 instructions

Altronix
Altronix LINQ8PD Installation and programming manual

M-system
M-system R7L-EC8A instruction manual

EOS
EOS EmoTouch 3 operating instructions

Trox Technik
Trox Technik XS installation manual