manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Pepperl+Fuchs
  6. •
  7. Industrial Electrical
  8. •
  9. Pepperl+Fuchs KFD0-SD2-E 1.1045 Series User manual

Pepperl+Fuchs KFD0-SD2-E 1.1045 Series User manual

Instruction Manual
1. Marking
Solenoid Driver
KFD0-SD2-Ex1.1045, KFD0-SD2-Ex1.1065, KFD0-SD2-Ex1.10100,
KFD0-SD2-Ex2.1045, KFD0-SD2-Ex2.1245
ATEX certificate: BASEEFA 06 ATEX 0252
ATEX marking:
1 II (1)G [Ex ia Ga] IIC
1 II (1)D [Ex ia Da] IIIC
1 I (M1) [Ex ia Ma] I
ATEX certificate: TÜV 99 ATEX 1499 X
ATEX marking: 1 II 3G Ex nA II T4
IECEx certificate:
IECEx BAS 06.0058
IECEx CML 19.0093X
IECEx marking:
[Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I
Ex ec IIC T4 Gc
North America Certificates: 3028278 (FMus), FM18CA0106X
Class I, Division 2, Groups A-D, T4
Class I, Zone 2, AEx nA II T4 (US), Ex nA II T4 (Canada)
Associated apparatus with intrinsically safe circuits for:
Class I, Division 1, Groups A-D; Class II, Division 1, Groups E-G;
Class III, Division 1
Class I, Zone 0, [AEx ia] IIC (US), [Ex ia] IIC (Canada)
North America Certificates: E106378 (UL)
Class I, Division 2, Groups A-D, T4
Associated apparatus with intrinsically safe circuits for:
Class I, Division 1, Groups A-D; Class II, Division 1, Groups E-G;
Class III, Division 1
Solenoid Driver
KFD0-SD2-Ex1.1180
ATEX certificate: BASEEFA 06 ATEX 0252
ATEX marking:
1 II (1)G [Ex ia Ga] IIB
1 II (1)D [Ex ia Da] IIIC
1 I (M1) [Ex ia Ma] I
ATEX certificate: TÜV 99 ATEX 1499 X
ATEX marking: 1 II 3G Ex nA II T4
IECEx certificate:
IECEx BAS 06.0058
IECEx CML 19.0093X
IECEx marking:
[Ex ia Ga] IIB , [Ex ia Da] IIIC , [Ex ia Ma] I
Ex ec IIC T4 Gc
North America Certificates: 3028278 (FMus), FM18CA0106X
Class I, Division 2, Groups A-D, T4
Class I, Zone 2, AEx nA II T4 (US), Ex nA II T4 (Canada)
Associated apparatus with intrinsically safe circuits for:
Class I, Division 1, Groups C-D; Class II, Division 1, Groups E-G;
Class III, Division 1
Class I, Zone 0, [AEx ia] IIB (US), [Ex ia] IIB (Canada)
North America Certificates: E106378 (UL)
Class I, Division 2, Groups A-D, T4
Associated apparatus with intrinsically safe circuits for:
Class I, Division 1, Groups C-D; Class II, Division 1, Groups E-G;
Class III, Division 1
Pepperl+Fuchs Group
Lilienthalstraße 200, 68307 Mannheim, Germany
Internet: www.pepperl-fuchs.com
2. Target Group, Personnel
Responsibility for planning, assembly, commissioning, operation,
maintenance, and dismounting lies with the plant operator.
The personnel must be appropriately trained and qualified in order to carry
out mounting, installation, commissioning, operation, maintenance, and
dismounting of the device. The trained and qualified personnel must have
read and understood the instruction manual.
Prior to using the product make yourself familiar with it. Read the
instruction manual carefully.
3. Reference to Further Documentation
Observe laws, standards, and directives applicable to the intended use
and the operating location.
For mining applications, observe laws, standards, and directives
applicable to the operating location.
The corresponding datasheets, manuals, declarations of conformity, EU-
type examination certificates, certificates, and control drawings if
applicable supplement this document. You can find this information under
www.pepperl-fuchs.com.
For specific device information such as the year of construction,
scan the QR code on the device. As an alternative, enter the serial number
in the serial number search at www.pepperl-fuchs.com.
If you use the device in safety-related applications, observe the
requirements for functional safety. You can find these requirements in the
functional safety documentation under www.pepperl-fuchs.com.
4. Intended Use
The device is only approved for appropriate and intended use.
Ignoring these instructions will void any warranty and absolve
the manufacturer from any liability.
The device is used in control and instrumentation technology
(C&I technology) for the galvanic isolation of signals such as 20 mA and
10 V standard signals or alternatively for adapting or standardizing signals.
The device has intrinsically safe circuits that are used for operating
intrinsically safe field devices in hazardous areas.
The device supplies power to solenoids, LEDs and audible alarms located
in the explosion-hazardous area.
The device is controlled with a loop powered signal or a bus powered logic
signal.
Use the device only within the specified ambient and operating conditions.
Only use the device stationary.
The device is an associated apparatus according to IEC/EN 60079-11.
The device is an electrical apparatus for hazardous areas of Zone 2.
The device may be installed in the non-hazardous area.
If you use the device in safety-related applications, observe the
information for safety function and safe state.
5. Improper Use
Protection of the personnel and the plant is not ensured if the device
is not used according to its intended use.
If circuits with type of protection Ex i are operated with non-intrinsically
safe circuits, they must no longer be used as circuits with type of
protection Ex i.
6. Mounting and Installation
Do not mount a damaged or polluted device.
The device is designed for mounting on a 35 mm DIN mounting rail
according to EN 60715.
The device must be installed and operated only in a controlled
environment that ensures a pollution degree 2 (or better) according to
IEC/EN 60664-1.
If used in areas with higher pollution degree, the device needs to be
protected accordingly.
Do not mount the device in the dust hazardous area.
The device must be installed and operated only in an environment of
overvoltage category II (or better) according to IEC/EN 60664-1.
Supply the device with a power supply that meets the requirements for
safety extra-low voltage (SELV) or protective extra-low voltage (PELV).
Observe the installation instructions according to IEC/EN 60079-14.
If you install the device in safety-related applications, observe the
requirements for functional safety.
Requirements for Cables and Connection Lines
Use only one conductor per terminal.
Observe the permissible core cross section of the conductor.
When using stranded conductors, crimp wire end ferrules
on the conductor ends.
When installing the conductors the insulation must reach
up to the terminal.
Observe the tightening torque of the terminal screws.
Requirements for Usage as Associated Apparatus
If circuits with type of protection Ex i are operated with non-intrinsically
safe circuits, they must no longer be used as circuits with type of
protection Ex i.
Observe the respective peak values of the field device and the associated
apparatus with regard to explosion protection when connecting intrinsically
safe field devices with intrinsically safe circuits of associated apparatus
(verification of intrinsic safety). Also observe IEC/EN 60079-14 and
IEC/EN 60079-25.
Keep the separation distances between all non-intrinsically safe circuits
and intrinsically safe circuits according to IEC/EN 60079-14.
Observe the compliance of the separation distances between two
adjacent intrinsically safe circuits according to IEC/EN 60079-14.
DOCT-6799 / 2023-04 1 / 2
Requirements for Equipment Protection Level Gc
The device must be installed and operated only in surrounding enclosures
that
lcomply with the requirements for surrounding enclosures according to
IEC/EN 60079-0,
lare rated with the degree of protection IP54 according to
IEC/EN 60529.
Connection or disconnection of energized non-intrinsically safe circuits is
only permitted in the absence of a potentially explosive atmosphere.
7. Operation, Maintenance, Repair
If you operate the device in safety-related applications, observe the
requirements for functional safety. In case of operating in low demand
mode, plan appropriate intervals for the proof test.
Do not use a damaged or polluted device.
Do not repair, modify, or manipulate the device.
If there is a defect, always replace the device with an original device.
Requirements for Equipment Protection Level Gc
Connection or disconnection of energized non-intrinsically safe circuits is
only permitted in the absence of a potentially explosive atmosphere.
8. Delivery, Transport, Disposal
Check the packaging and contents for damage.
Check if you have received every item and if the items received are the
ones you ordered.
Always store and transport the device in the original packaging.
Store the device in a clean and dry environment. The permitted ambient
conditions must be considered, see datasheet.
The device, built-in components, packaging, and any batteries
contained within must be disposed in compliance with the applicable laws
and guidelines of the respective country.
DOCT-6799 / 2023-04 2 / 2

This manual suits for next models

4

Other Pepperl+Fuchs Industrial Electrical manuals

Pepperl+Fuchs SIL KCD2-SCS-Ex2.SP User guide

Pepperl+Fuchs

Pepperl+Fuchs SIL KCD2-SCS-Ex2.SP User guide

Pepperl+Fuchs KFD0-TR-1 User guide

Pepperl+Fuchs

Pepperl+Fuchs KFD0-TR-1 User guide

Pepperl+Fuchs F-FT-EX1.I.IEC Series User manual

Pepperl+Fuchs

Pepperl+Fuchs F-FT-EX1.I.IEC Series User manual

Pepperl+Fuchs K-System User manual

Pepperl+Fuchs

Pepperl+Fuchs K-System User manual

Pepperl+Fuchs FC-GPCD-SDI16-PF User guide

Pepperl+Fuchs

Pepperl+Fuchs FC-GPCD-SDI16-PF User guide

Pepperl+Fuchs EI-0D2-10Y-10B User manual

Pepperl+Fuchs

Pepperl+Fuchs EI-0D2-10Y-10B User manual

Pepperl+Fuchs LS680-DA User manual

Pepperl+Fuchs

Pepperl+Fuchs LS680-DA User manual

Pepperl+Fuchs H-System User manual

Pepperl+Fuchs

Pepperl+Fuchs H-System User manual

Pepperl+Fuchs PCV-F200-SSI-V19 Series User manual

Pepperl+Fuchs

Pepperl+Fuchs PCV-F200-SSI-V19 Series User manual

Pepperl+Fuchs Bebco EPS 5500 Series User manual

Pepperl+Fuchs

Pepperl+Fuchs Bebco EPS 5500 Series User manual

Pepperl+Fuchs 6000 SERIES User manual

Pepperl+Fuchs

Pepperl+Fuchs 6000 SERIES User manual

Pepperl+Fuchs KCD0-RSH-1.1D.4 User guide

Pepperl+Fuchs

Pepperl+Fuchs KCD0-RSH-1.1D.4 User guide

Pepperl+Fuchs IQT-18GM-R4-V1-Y911215 User manual

Pepperl+Fuchs

Pepperl+Fuchs IQT-18GM-R4-V1-Y911215 User manual

Pepperl+Fuchs H-System User manual

Pepperl+Fuchs

Pepperl+Fuchs H-System User manual

Pepperl+Fuchs KCD2-SCD-Ex1.ES.SP User manual

Pepperl+Fuchs

Pepperl+Fuchs KCD2-SCD-Ex1.ES.SP User manual

Pepperl+Fuchs HiC5861 User guide

Pepperl+Fuchs

Pepperl+Fuchs HiC5861 User guide

Popular Industrial Electrical manuals by other brands

Murata GQM2195C2E180GB12 Series Reference sheet

Murata

Murata GQM2195C2E180GB12 Series Reference sheet

Murata GQM2195C2E4R0CB12 Series Reference sheet

Murata

Murata GQM2195C2E4R0CB12 Series Reference sheet

Murata GRM31CR71H225KA88L Reference sheet

Murata

Murata GRM31CR71H225KA88L Reference sheet

Murata GRM1885C1H130GA01 Series Reference sheet

Murata

Murata GRM1885C1H130GA01 Series Reference sheet

CyberPower CRA30008 user manual

CyberPower

CyberPower CRA30008 user manual

Eaton S801T Instructions for installing

Eaton

Eaton S801T Instructions for installing

Murata GRM155R61A334KE15 Series Reference sheet

Murata

Murata GRM155R61A334KE15 Series Reference sheet

Phoenix Contact Axioline F SBT V3 quick start guide

Phoenix Contact

Phoenix Contact Axioline F SBT V3 quick start guide

Murata GRM32ER71C226KEA8 Series Reference sheet

Murata

Murata GRM32ER71C226KEA8 Series Reference sheet

Murata GRM0225C1E560JA02 Series Reference sheet

Murata

Murata GRM0225C1E560JA02 Series Reference sheet

Murata GRM0335C1E220FA01D Reference sheet

Murata

Murata GRM0335C1E220FA01D Reference sheet

Murata GRM1555C1H6R3DA01 Series Reference sheet

Murata

Murata GRM1555C1H6R3DA01 Series Reference sheet

SEW-Eurodrive MOVIFIT basic manual

SEW-Eurodrive

SEW-Eurodrive MOVIFIT basic manual

Rockwell Automation C09 Series Installation instruction

Rockwell Automation

Rockwell Automation C09 Series Installation instruction

UVP 3UV Series user guide

UVP

UVP 3UV Series user guide

Moeller H6 installation instructions

Moeller

Moeller H6 installation instructions

Generex BACS System quick start guide

Generex

Generex BACS System quick start guide

eks FIMP XL-E manual

eks

eks FIMP XL-E manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.