The pulse control mode is intended for the turnstile operation from the RC-panel, a WRC
or an ACS controller with outputs supporting the pulse control mode.
Standard control inputs: Unlock A, Unlock Band Stop.
Special control input: Fire Alarm.
Operating modes of the turnstile at this control mode are given in Table 3, algorithm of
control signals is stipulated in Appendix 1.
The minimum input signal duration, when the operating mode can be changed, should be
100msec. The passage waiting time is 5 sec. and it does not depend on the input signal
duration.
The turnstile operation from the special control input Fire Alarm is described in Clause 5.9.
The potential control mode is intended for the turnstile operation from an ACS controller
with outputs supporting the potential control mode (for example, a lock controller).
Standard control inputs: Unlock Aand Unlock B.
Special control inputs: Stop and Fire Alarm.
Operating modes of the turnstile at this control mode are given in Table 4; algorithm of
control signals is stipulated in Appendix 2.
The minimum input signal duration, when the operating mode can be changed, should be
100msec. The passage waiting time is equal to a low-level signal duration (the turnstile
remains open in the set direction if a low-level signal is supplied at the corresponding input
by the moment of passage).
Once the low-level signal is supplied at the Stop input, both directions are closed for the
period of the signal duration regardless of the signals level at the inputs Unlock Aand
Unlock B. At the low-level signal removing from the Stop input, the directions turn to the
operating mode according to the signals level at the inputs UnlockAand Unlock B.
The turnstile operation from the special control input Fire Alarm is described in Clause 5.9.
5.6 Operation from the RC-panel
When the buttons on the RC-panel are pressed (the STOP button and the two other
buttons corresponding to the passage directions), contacting of the relevant Stop,
Unlock Aor Unlock Bwith the GND occurs (i.e. forming of the low-level signal relatively to
the contact GND).
Operation logic of the turnstile at the single passage in the A(B) direction at the pulse
control mode:
1. When the button corresponding to the A (B) passage direction is pressed on the RC-
panel, contacting the Unlock A(B) and the GND occurs (i.e. forming of the low-level
signal on the contact Unlock A(B) relatively to the contact GND).
2. The CLB microcontroller processes the incoming command and generates the
command to the control mechanism, which opens the A (B) passage direction (lifts
the upper (lower) edge of the key holt).
3. The microcontroller traces the status of the optic rotation sensors, which become
active/passive in a certain sequence at the barrier arm rotation, and counts the time
passed since the moment of pushing the RC-panel button corresponding to the
permitted passage direction A (B).
4. At the barrier arms turning at 67° the microcontroller forms signal PASS A(B)
(breaking the contacts PASS A(B) and Common takes place).
5. After the barrier arms turning at 67° or after 5 seconds since the moment of pushing
the RC-panel button corresponding to the permitted passage direction A (B), the
12