PERCo Turnichetul TB 1 Supplement

ТВ-01
Electromechanical
Box Tripod
Turnstile
with two built-in readers
Assembly and
operation manual

Assembly and Operation Manual
2
CONTENTS
1. APPLICATION............................................................................................................... 3
2. OPERATION CONDITIONS.......................................................................................... 3
3. TECHNICAL SPECIFICATIONS................................................................................... 3
4. STANDARD DELIVERY SET........................................................................................ 4
5. OPTIONAL EQUIPMENT SUPPLIED ON REQUEST .................................................. 4
6. PRODUCT DESCRIPTION ........................................................................................... 4
6.1. Main features .......................................................................................................... 4
6.2. Design ..................................................................................................................... 5
6.3. Control over the TB-01 turnstile .............................................................................. 8
6.4. Input control signals and their parameters at autonomous control ......................... 9
6.5. Control modes ....................................................................................................... 11
6.6. Operation from the RC panel ................................................................................. 12
6.7. Operation from wireless remote control ................................................................. 13
6.8. Operation from an ACS controller .......................................................................... 13
6.9. Optional external devices connected to the turnstile .............................................. 13
6.10. Unblocking with a mechanical release key........................................................... 14
6.11. Operation contingencies and response............................................................... 14
7. MARKING AND PACKAGING.................................................................................... 15
8. SAFETY REQUIREMENTS......................................................................................... 15
8.1. Installation safety requirements............................................................................. 15
8.2. Operation safety requirements .............................................................................. 16
9. INSTALLATION INSTRUCTIONS .............................................................................. 16
9.1. Installation details .................................................................................................. 16
9.2. Installation tools..................................................................................................... 17
9.3. Cable length .......................................................................................................... 17
9.4. Installation procedure ............................................................................................ 17
9.5. Connecting readers to an ACS.............................................................................. 20
10. OPERATION INSTRUCTIONS ................................................................................. 21
10.1. General................................................................................................................ 21
10.2. Power-up ............................................................................................................. 21
10.3. Turnstile operating modes in pulse control mode............................................. 22
10.4. Operation of the TB-01 turnstile in potential control mode............................... 23
10.5. Operation of the turnstile when controlled by an ACS ........................................ 24
10.6. In case of an emergency ..................................................................................... 25
10.6.1 Unlocking with a mechanical release key .......................................... 25
10.6.2 Anti-panic folding arms....................................................................... 25
10.7. Possible faults ..................................................................................................... 25
11. TRANSPORTATION AND STORAGE...................................................................... 26
12. MAINTENANCE ........................................................................................................ 26
APPENDIX А.................................................................................................................. 28
APPENDIX B .................................................................................................................. 32
APPENDIX C .................................................................................................................. 34

TВ-01 Electromechanical box tripod turnstile with two built-in readers
3
Dear Customer,
Thank you for purchasing a box tripod turnstile manufactured by PERCo. Please follow in-
structions given in this Manual carefully, and this high quality product will provide many
years of trouble-free use.
The Assembly and Operation Manual (hereinafter – the Manual) contains the
instructions you will need for safe transportation, storage, installation, operation and
maintenance of the TB-01 electromechanical box tripod turnstile with built-in readers
(hereinafter – the turnstile).
The product installation must be carried out by qualified installers in strict
accordance with the Manual.
Abbreviations adopted in the Manual:
ACS – access control system;
CLB – control logic board;
RC panel – remote control panel.
1. APPLICATION
1.1. The TВ-01 electromechanical box tripod turnstile with two built-in readers is
designed for pedestrian passage control by proximity cards at entrance points of
industrial facilities, banks, administrative buildings, railway terminals, airports,
etc.
1.2. To ensure fast and convenient passage through the turnstile it is recommended
to install one TB-01 turnstile per each 500 persons working same shift, or based
on the passage pick of 30 persons per minute (Ref. Section 3 for the throughput
rate of the turnstile).
2. OPERATION CONDITIONS
2.1. The TB-01 turnstile with regard to resistance to environmental exposure complies
with GOST 15150 category NF4 (operation in premises with climate control).
2.2. Operation of the TB-01 turnstile is allowed at an ambient air temperature from
+1°Сto + 40 °Сand relative air humidity 80% at +25 °С.
3. TECHNICAL SPECIFICATIONS
Operating voltage.............................................................................................. 12±1,2VDC
Power consumption ........................................................................................... max. 20 W
Consumption current........................................................................................... max.1,5 A
Throughput rate in a single passage mode. .............................................. 30 persons/min.
Throughput rate in a free passage mode...................................................60 persons/min.
Passage width.........................................................................................................500 mm
Barrier arm rotation force ................................................................................ max. 3,5 kgf.
Number of readers .............................................................................................................2
Card reading distance at the rated operating voltage:
HID cards ............................................................................................. min. 6 cm
EM-Marin cards.................................................................................... min. 8 cm
RC panel cable length.........................................................................................min. 6,6 m
RC panel overall dimensions (L хW хH) ...................................................120х80х21 mm

Assembly and Operation Manual
RC panel net weight.......................................................................................... max. 0,2 kg
4
Ingress Protection Rating.................................................................. IP41 under EN 60529
Electric shock protection class ...............................III according to GOST R IEC 335-1-94
Mean time to failure ..................................................................... min. 1500000 passages
Mean lifetime............................................................................................................8 years
Overall dimensions of the TB-01 with barrier arms (L хW хH).......... 1050х684х1030 mm
Net weight of the turnstile ................................................................................. max. 68 kg
4. STANDARD DELIVERY SET
Turnstile housing................................................................................................................1
Barrier arm (separately itemized in the price list, type is chosen by
a Client at the time of order).. ..............................................................................................3
Key to a housing top cover lock.........................................................................................2
Mechanical release key .....................................................................................................2
Key to a housing side cover lock. ......................................................................................2
RC panel with cable min. 6,6 m long. ................................................................................1
Jumper. ..............................................................................................................................2
Installation tools:
Self-adhesive cable tie mount. .............................................................................3
Nylon cable tie 100 mm ........................................................................................6
Spare parts:
Stop spring. ..........................................................................................................2
Technical documentation:
Assembly and operation manual. .........................................................................1
Certificate. ............................................................................................................1
Package.......................................................................................................................1
5. OPTIONAL EQUIPMENT SUPPLIED ON REQUEST
Wireless remote control kit (consists of a receiver and 2 transmitters (tags)
with operation range up to 40m) ........................................................................................1
Siren (for alerts on unauthorized entry attempts) ..............................................................1
Intrusion detector ..............................................................................................................1
6. PRODUCT DESCRIPTION
6.1 Main features
The TВ-01 turnstile can be operated autonomously: from the remote control panel
or wireless remote control, as well as from an access control system (ACS) via
readers.
The TВ-01 turnstile is supplied with safe operating voltage – maximum 14 V.
The turnstile has low power consumption – maximum 20 W.
At a power supply switching off the turnstile retains the position for each direction
set at the moment of power loss: the open passage direction remains open, the
closed passage direction remains closed.
A resetting mechanism ensures automatic reset of barrier arms to home
position after each passage.
Smooth and quite operation of the resetting mechanism is ensured by a
damper.

TВ-01 Electromechanical box tripod turnstile with two built-in readers
5
To ensure correct register of passages the resetting mechanism has built-in
optic rotation sensors.
A mechanical release lock built into the TB-01 turnstile housing ensures
unlocking of the turnstile with a mechanical release key enabling free rotation of
barrier arms in a case of emergency.
Installed in a line several turnstile housings form a secured passage without
installation of extra guide barriers.
Front covers of the turnstile housing feature mnemonic indicators of proximity card
readers installed under the front covers.
When it is required to have a card capture option on entrance or exit the ТВ-01
turnstile can be used together with a ТВС-01 model featuring a built-in card
capture reader; the TB-01 and TBC-01 models have matching design and
dimensions.
6.2. Design
6.2.1 Design of the TB-01 turnstile is shown in Figure 1. Numbers of the items
hereinafter refer to the item numbers as shown in Figure 1 unless stated
otherwise.
Figure 1 – TВ-01 overall view
– Standard delivery set:
1 – frame; 2 – base; 3 – top cover; items 1-3 form turnstile housing; 4 – top cover lock;
5 – barrier arm; 6 – cover; 7 – mechanical release lock; 8 – indication module;
9,10 – front covers with card readers; 11- blank cover; 12,14 – turnstile housing side cover;
13,15 – turnstile housing side cover lock; 16 – RC panel; 17 – RC panel cable;
– Not included in the standard delivery set:
18 – power cable; 19 – wireless remote control device cable; 20 – ACS connection cable.

Assembly and Operation Manual
6
The TВ-01 turnstile consists of a turnstile housing with built-in electronics and two
card readers, three barrier arms and an RC panel (Ref. Fig. 1, items 1-3, 5 and 16).
The turnstile housing is fixed to floor with 4 anchor bolts through holes in the
turnstile housing base (2). The overall dimensions of the TB-01 turnstile housing are
shown in Figure 2.
The turnstile housing contains: rotation unit, which includes a resetting mechanism
(a pusher, stop springs and a roller), control mechanism with optic sensors and a
locking device, as well as a mechanical release lock (7). Rotation unit houses rotation
mechanism which includes a damper, a rotation sensor disc and a hub; the point of
attachment of the barrier arms to the rotating mechanism is hidden with a cover (6).
Front side surfaces of the turnstile housing have side covers (12, 14) with
locks (13, 15).
Internal elements of the turnstile housing are accessed through a removable top
cover (3); at normal operation of the TB-01 turnstile the top cover lock (4) is locked.
6.2.2 To inform on a current status of the TB-01 turnstile both front sides of the
turnstile housing feature indication modules (8), with card readers built-in
under, on the internal side of the cover. The indication module has 3
mnemonic indicators:
Green indicator of authorized passage;
Yellow indicator: card presentation is expected;
Red indicator of ban on passage.
6.2.3 Inside the turnstile housing there is a bracket with a CLB mounted on it with
terminal clamps for connection of external devices. RC panel, ACS outputs,
wireless remote control device (when used), intrusion detector (optional) and
emergency unblocking device are connected to the CLB.Connection lines of
a power supply unit and signal lines of card readers are connected to the
terminal clamps for connection of external devices. External devices are
connected in accordance with connection layout (Ref. Fig. А.1 Appendix А).
Layout of electrical connections inside the turnstile housing is shown in
Figure A.2 Appendix A. The CLB is shown in Figure 3.
6.2.4 The remote control panel is designed as a small desktop device with a shock-
proof ABS plastic case and is intended for setting and indicating operating
modes when the turnstile is operated manually. The RC panel is connected to
the CLB with a flexible multicore cable (17) via a “ХТ1.L” connector block (Ref.
Fig. 3).
The front of the remote control panel houses three control buttons with LED indicators
above to set passage modes of the TB-01 turnstile. The “STOP” button in the middle
serves for setting the “Always locked” operating mode, the right and left buttons – for
unlocking the turnstile in a chosen direction.
The RC panel orientation towards the turnstile (if an operator’s terminal is placed at
the backside of the turnstile housing) can be changed by swopping wires of the RC panel
connected to the contacts: Unlock A and Unlock B respectively, as well as Led A and
Led B respectively (Ref. Fig. 3 and A.1 Appendix A).

TВ-01 Electromechanical box tripod turnstile with two built-in readers
7
Figure 2 – Overall dimensions of the TВ-01 turnstile
6.2.5 The CLB (Ref. Fig. 3) houses:
“X1” (Control) connector to connect the control mechanism (connected to
the “X1” connector of the control mechanism with the turnstile cable);
“XT1.L” (In) connector block to connect the RC panel /the wireless remote
control/ACS controller inputs as well as an emergency unblocking device;
“XT1.H” (Out) connector block to connect a siren and outputs, providing the
turnstile status data to the ACS controller;
“XT2” connector block (Detector) to connect an intrusion detector;
“XT3” (+12VDC) connector block to connect the turnstile power supply;
“XT4” (Light A) and “XT5” (Light B) connector blocks (at delivery indication of
top cover card readers is connected to the connector blocks);
J1 connector to select the turnstile control mode;
J2 connector for programming.
6.2.6 The TВ-01 turnstile is powered via a power cable (18). As power supply it is
recommended to use 12 VDC power supply with linear stabilization of voltage
and pulsation amplitude at output not exceeding 50 mV. Value of output
current should be minimum 1,5А.

Assembly and Operation Manual
8
Figure 3 – The CLB
6.3. Control over the TB-01 turnstile
6.3.1 The turnstile can be operated from the following control devices:
RC panel;
Wireless remote control;
ACS controller.
The above devices can be connected to the turnstile as follows:
any device alone;
in any combination with each other;
all devices simultaneously (in parallel).
Note. At parallel connection of the above devices to the turnstile the superposition of
the control signals from them may occur. In that case the turnstile response will
conform to response to the obtained combination of input signals. (Appendices B
and C).
6.3.2 Connection of the devices mentioned in Clause 6.3.1 is made with
cables (17, 19, 20) to the corresponding connector blocks “XT1.L” and
“XT1.H” of the CLB in accordance with the connection layout (Ref.
Fig. A.1 Appendix A).
6.3.3 The RC panel is connected to the contacts “GND”, “Unlock A”, “Stop”,
“Unlock B”, “Led A”, “Led Stop” and “Led B” of the “XT1.L” connector
block.
6.3.4 The wireless remote control is connected to the contacts “GND”,
“Unlock A”, “Stop” and “Unlock B” of the “XT1.L” connector block.
Power supply of the wireless remote control is connected to the contact
“+12V” of the “XT1.H” connector block.
6.3.5 The ACS controller outputs are connected to the contacts “GND”,
“Unlock A”, “Stop” and “Unlock B” of the “XT1.L” connector block.
6.3.6 The ACS controller inputs are connected to the contacts “Common”,
“PASS A”, “PASS B”, “Ready” and “Det Out” of the “XT1.H” connector
block.

TВ-01 Electromechanical box tripod turnstile with two built-in readers
9
6.3.7 Pin assignment of the CLB connector blocks are given in Figure 3 and
on a label located on the inner surface of the turnstile top cover.
6.4. Input control signals and their parameters at autonomous control
6.4.1 The CLB microcontroller processes incoming commands (i.e. traces
the status of the contacts “Unlock A”, “Stop”, “Unlock B” and “Fire
Alarm”), keeps track of the signals from optic sensors and from the in-
trusion detector (contact “Detector”), and based on those signals, gen-
erates commands to the control mechanism and to the external devices
– indication on the RC panel (“Led A”, “Led Stop” and “Led B”), the sig-
nal of hub turning in the corresponding direction (“PASS А” and “PASS
В”), the signal of the turnstile ready for a next command (“Ready”), the
alarm output signal (“Alarm”) – and relays the signal of the current sta-
tus of the intrusion detector (“Det Out”).
6.4.2 The turnstile is operated by input of a low-level signal, relatively to the
“GND” contact, to “Unlock A”, “Unlock B” and “Stop” contacts of the
“XT1.L” connector block. As a control element there can be used a nor-
mally open relay contact or a circuit with open collector output at that.
Emergency unblocking of the turnstile is carried out by removing of a
low-level relatively to the “GND” contact signal from the “Fire Alarm”
contact. As a control element there can be used a normally closed relay
contact or a circuit with open collector output at that (Ref. Fig. 4).
Note: For generating of a high-level signal at all input contacts (“Unlock A”, “Stop”,
Unlock B”, “Fire Alarm” and “Detector”) 2kOhm resistors connected to the power sup-
ply bus “+ 5V” are used.
The control element must provide the following signal characteristics:
the relay contact as the control element:
minimum switched current ................................................no more than 2mA;
closed contact resistance
(with resistance of the connection cable).................. no more than 300 Ohm;
the circuit with open-collector output as the control element:
voltage at the closed contact
(low - level signal at the CLB input) ..................................no more than 0.8V.

Assembly and Operation Manual
10
а)
b)
Figure 4 – Control elements of an external device:
a– a normally open relay contact;
b– a circuit with open-collector output.
6.4.3 The relays “PASS A” (contacts “PASS A” and “Common”), “PASS B”
(contacts “PASS B” and “Common”), “Ready” (contacts “Ready” and
“Common”), “Detector” (contacts “Det Out” and “Common”) and “Alarm”
(contacts “Alarm 1” and “Alarm 2”) have normally open contacts. The
“Common” contact, common contact for the relays, at that, is not con-
nected to the negative terminal of the turnstile power supply. In the ini-
tial (inactive) state, when the power is on, the relay contacts “PASS A”,
“PASS B”, “Ready” and “Detector” are closed (voltage is supplied to the
relay coil) and the “Alarm” relay contacts are open (voltage is not sup-
plied to the relay coil). Opening/closing of PASS A, PASS B, Ready,

TВ-01 Electromechanical box tripod turnstile with two built-in readers
11
Detector and Alarm relays is indicated by lighting/going out of red indi-
cators located near the corresponding relays (Fig. 3). The output cas-
cades for “PASS A”, “PASS B”, “Ready”, “Det Out” and “Alarm” are the
relay contacts with the following signal characteristics (Ref. Fig. 5):
maximum commutation voltage..................................42V DC;
maximum switched current ...........................................0.25А;
closed contact resistance .................. no more than 0.15Ohm.
Figure 5 – Output cascades for PASS A, PASS B, Ready, Det Out and Alarm
6.5. Control modes
6.5.1 There are two modes of the turnstile control - a pulse control mode and a
potential control mode. They determine available operating modes of the
turnstile (Table 3 and Table 4).
6.5.2 The control mode is set by the jumper on a J1 connector (the J1 connector
location is shown in Figure 3: the jumper is installed – the pulse control
mode, the jumper is not installed – the potential control mode). The jumper
is installed at delivery.
6.5.3 At both control modes the turnstile is controlled by input of a control signal.
Passage waiting time in the pulse control mode is 5 seconds regardless of
duration of the control signal (impulse). In the potential control mode
passage waiting time equals duration of the control signal.

Assembly and Operation Manual
6.5.4
12
The pulse control mode is intended for the turnstile operation from the RC
panel, wireless remote control or an ACS controller, outputs of which
support pulse control mode
Standard control inputs: “Unlock A”, “Unlock B” and “Stop”.
Special control input: “Fire Alarm”.
Refer to Table 3 for the turnstile operating modes at this control mode.
The algorithm of control signals at this mode is described in Appendix B.
To change operating mode of the turnstile the minimum input signal duration
should be 100msec. The passage waiting time is 5 sec. and it does not depend on the
input signal duration.
Refer to Clause 6.9.3.1 for the turnstile operation at special “Fire Alarm” control in-
put.
6.5.5 The potential control mode is intended for the turnstile operation from an
ACS controller, outputs of which support potential control mode (for
instance lock controller).
Standard control inputs: “Unlock A” and “Unlock B”
Special control inputs: “Stop” and “Fire Alarm”.
See Table 4 for the turnstile operating modes at this control mode.
The algorithm of control signals at this mode is described in Appendix C.
To change operating mode of the turnstile the minimum input signal duration
should be 100msec. The passage waiting time is equal to the low-level signal
duration (the turnstile remains open in the set direction if a low-level signal already
exists at the set direction input at the moment of passage).
At the low-level signal inputting to the “Stop” input, both directions will lock for
the time of the signal duration regardless of the signal strength at the inputs “Unlock
A” and “Unlock B”. At the removing of a low-level signal from the “Stop” input, the
directions will set to the modes according to the signal strength at the inputs
“Unlock A” and “Unlock B”.
See Clause 6.9.3.2 for the turnstile operation at the special “Fire Alarm” control
input.
6.6. Operation from the RC panel
6.5.1 When the buttons on the RC panel are pressed (the STOP button and the
two buttons corresponding to a passage direction), the closing of the
relevant contact “Stop”, “Unlock A” or “Unlock B” to the contact “GND”
occurs (i.е. forming of the low-level signal relatively to the contact “GND”).
6.5.2 Operation logic of the turnstile at the single passage in the А(В) direction at
the pulse control mode:
6.5.2.1 When the button, corresponding to the А(В) passage direction, is
pressed on the RC panel, the closing of the contact “Unlock A(В)” to the
contact “GND” occurs (i.е. forming of the low-level signal on the contact
“Unlock A(В)” relatively to the contact “GND”).
6.5.2.2 The CLB microcontroller processes an incoming command and gen-
erates a command to the control mechanism, which opens the А(В)
passage direction (lifts the upper (lower) edge of the key holt).
6.5.2.3 The microcontroller traces a status of the optic sensors, which be-
come active/normal in a certain sequence at barrier arm rotation,

TВ-01 Electromechanical box tripod turnstile with two built-in readers
13
and counts the time passed since the moment the RC button corre-
sponding to the permitted passage direction А(В) is ressed.
6.5.2.4 At the barrier arms turning 67° the microcontroller forms signal “PASS
А(В)” (breaking of the contacts “PASS А(В)” and “Common” oc-
curs).
6.5.2.5 After the barrier arms turning 67° or after 5 seconds since the mo-
ment of pushing the RC button corresponding to the permitted pas-
sage direction А(В), the microcontroller generates a command to
the control mechanism, which closes the passage direction А(В)
(drops the upper (lower) edge of the key holt).
6.5.2.6 When the barrier arms reset to home position (barrier arms turning
112°), the microcontroller removes the signal “PASS А(В)” (contact-
ing of the “PASS А(В)” and “Common” takes place).
6.5.3 The “Always free” operating mode particularity: in this mode the command
described in Clause 6.6.2.5 is not generated and the set passage direction
remains open.
6.7. Operation from wireless remote control
6.5.1 Control over the turnstile with the wireless remote control is similar to that
with the remote control panel.
6.5.2 The buttons on the wireless remote control tag act the same way as those
on the RC panel.
6.5.3 The wireless remote control operation manual is supplied with that device.
6.8. Operation from an ACS controller
6.5.1 In the pulse control mode control over the turnstile from an ACS controller
is similar to that one with the RC panel.
6.5.2 In the potential control mode control over the turnstile from an ACS con-
troller is similar to that one with the RC panel and lies in forming of a low-
level signal on the contacts “Unlock A”, “Stop” and “Unlock B” relatively to
the contact “GND”.
6.5.3 The difference of the operation logic in the potential control mode com-
pared to the one in the pulse control mode (as per Clause 6.6.2): the com-
mand described in Clause 6.6.2.5 is generated only at the moment the RC
button corresponding to the passage direction А(В) is released.
Therefore to arrange single passages in the potential control mode it is
recommended to remove the control low-level signal at the beginning of the
“PASS” signal of the corresponding direction.
6.5.4 The passage through the turnstile in the А(В) direction gets registered
based on the status of the output contacts “PASS A(В)” and “Common”.
6.9. Optional external devices connected to the turnstile
6.9.1 The following external devices can be connected to the turnstile:
an intrusion detector and a siren;
an emergency unblocking device;
6.9.2 The intrusion detector is connected to the “XT2” connector block, and the
siren is connected to the “XT1.H” connector block of the CLB according to
the connection layout (Fig. A.1 Appendix A and Fig. 3). The intrusion detector
should have normally closed contacts.
Note! Only the manufacturer should carry out installation of an intrusion detector
on a turnstile housing.

Assembly and Operation Manual
14
If while the turnstile is in a locked state (in the “Always locked” mode or in the “Both
directions locked” mode, Tables 3 and 4) a signal from the intrusion detector comes,
the “Alarm” signal is generated, which is disabled either after 5 sec. or after execution of
any received command. The signal from the intrusion detector is ignored for the period of
authorized unlocking of the turnstile in either or both directions.
A signal coming from the intrusion detector within 3 sec. after the “Always
locked”/“Both directions locked” mode is set, is ignored.
A signal on current status of the intrusion detector is constantly transmitted to the
“Det Out” and “Common” contacts of the CLB “XT1.H” connector block (Fig. 3).
6.9.3 The emergency unblocking device is connected to the “XT1.L” connector
block of the CLB in accordance with the connection layout (Figure A.1
Appendix A and Figure 3). If the “Fire Alarm” input is not used, it is
necessary to install a jumper between the contacts “Fire Alarm” and
“GND”. This jumper is installed at delivery.
Operation of the turnstile under commands of the emergency unblocking de-
vice:
6.9.3.1 In the pulse control mode, when a low-level signal is removed from
the “Fire Alarm” input, both passage directions open for the whole
period of the signal absence. Other control commands are ignored at
that. When the low-level signal appears at the “Fire Alarm” input, the
turnstile turns to the “Always locked” mode.
6.9.3.2 In the potential control mode, when a low-level signal is removed from
the “Fire Alarm” input, both passage directions open for the whole pe-
riod of the signal absence. Other control commands are ignored at
that. When the low-level signal appears at the “Fire Alarm” input, the
passage directions turn to the mode in accordance with the signal le-
vels at the inputs “Unlock A”, “Unlock B” and “Stop”.
6.10. Unblocking with a mechanical release key
Mechanical release function is intended for unlocking barrier arms ensuring free ro-
tation in case of emergency, or at a power supply failure.
To unlock the turnstile with a mechanical release key proceed as follows:
Insert the key into a mechanical release lock (7);
Turn the key clockwise till it stops (open the lock, the lock cylinder will move out
at this);
Return the key into its reset position and take it out of the lock;
Make sure the TB-01 turnstile is unlocked by turning the barrier arms in both
direction several times;
To mechanically lock the TB-01 turnstile:
Install the barrier arms in their home position;
Press the lock cylinder into lock case till it clicks (without the key);
Make sure the turnstile is locked and the barrier arms cannot be free rotated
manually.
6.11. Operation contingencies and response
6.11.1 The turnstile is capable of providing information on the following
operation contingencies:
unauthorized access;
passage delay for more than 30 sec.;
one or both optic sensors are out of order.

TВ-01 Electromechanical box tripod turnstile with two built-in readers
A special signal “Ready” is generated in each of the above cases.
15
6.11.2 In case of unauthorized access the “Ready” signal is formed as follows:
at 8° arm rotation one of the optic sensors (Fig. 10) responds and the
output contacts “Ready” and “Common” get broken (the beginning of the
signal). When the barrier arms reset to home position, the both optical
sensors become normal and the output contacts “Ready” and “Common”
get closed (the finish of the signal).
6.11.3 In case of delay of an authorized passage for more than 30 sec. the
signal “Ready” is formed as follows: if within 30 seconds from the
moment of passage commencing, which is determined by the arm
rotation at no less than 8° (i.e. activation of one of the optic sensors), the
reset of barrier arms to home position does not happen, the output
contacts “Ready” and “Common” break (the beginning of the signal).
When the barrier arms reset to home position, the both optic sensors
become normal and the output contacts “Ready” and “Common” get
closed (finish of the signal).
6.11.4 When one or both of the optic sensors become out of order, the output
contacts “Ready” and “Common” get broken (the beginning of the signal
“Ready”). After fault removal the closed status of the contacts “Ready” and
“Common” is resumed.
7. MARKING AND PACKAGING
7.1 The turnstile has a marking sticker on the internal side of the turnstile top
cover and a label – inside, on the rear side of the turnstile housing. To get
access to the marking sticker and the label, open the top cover (3).
To do so proceed as follows:
Switch off power supply of the turnstile;
Insert the key into the top cover lock (4);
Turn the key clockwise till it stops (open the lock, the lock cylinder will move out
together with a lock bolt at this);
Holding the front edge of the top cover (3) carefully lift it and turning it remove it
from the turnstile housing. Be careful not to damage the CLB located under the
cover while removing the top cover;
Place the top cover on a flat steady surface.
Installation of the top cover back into its operation position is carried out in reverse
order. After mounting the top cover, lock the top cover lock by pushing lock cylinder
into its case till it clicks. Turn on the TB-01 turnstile power supply.
7.2 To protect the turnstile against damage during transportation and storage
the TB-01 turnstile as standard (Ref. Section 4) is packed in a transportation
box, 1200х390х1100 mm, weight brutto– 88 kg.
8. SAFETY REQUIREMENTS
8.1. Installation safety requirements
8.1.1 The installation should be carried out only by qualified personnel after
careful study of this Manual with observance of general safety rules.
8.1.2 Only serviceable tools should be used for installation.
8.1.3 All works should be performed only after the power supply is switched off
and disconnected from the AC mains.
8.1.4 During installation before the turnstile housing is fixed to the floor be care-

Assembly and Operation Manual
16
ful not to drop the turnstile housing.
8.1.5 Before first power-up of the TB-01 turnstile make sure installation and all
connections are done properly.
8.1.6 Installation of a power supply unit must be performed with observance of
safety requirements mentioned in its certificate.
8.2. Operation safety requirements
8.2.1 Observe general electrical safety rules when operating the turnstile.
8.2.2 Do not use the turnstile under conditions that do not comply with the re-
quirements of Section 2 of this Manual.
8.2.3 Do not use the turnstile at supply voltage that does not comply with the re-
quirements of Section 3 of the Manual.
8.2.4 Power supply unit must be operated with observance of safety require-
ments mentioned it its certificate.
9. INSTALLATION INSTRUCTIONS
9.1. Installation details
It is recommended:
to mount the turnstile on steady and level concrete (grade 400 or higher,
strength class B22,5), stone or similar foundations at least 150mm thick;
to level the foundation so that the anchoring points of the turnstile lie in the same
plane (check it with a level);
to apply reinforcing elements (550х550х200mm) for installation on less steady
foundation;
to mark the mounting holes according to Figure 7;
to control vertical alignment of the turnstile with a level during installation;
to do installation of the TB-01 turnstile by at least 2 skilled installers;
when arranging a passage area through the turnstile please take into account that
the resetting mechanism operates as follows:
at the barrier arm turning at the angle of more than 60 the reset is effected
in the direction of movement;
at the barrier arm turning at the angle less than 60 the reset is effected
counter the movement direction (reset to home position).
Note: The angle gradient, at which the barrier arm reset commences, may vary in the range
of ± 5°.
To ensure accurate passage tracking, when the turnstile is operated from an ACS,
it is recommended to arrange the passage area in such a way that the barrier arms
should turn in the direction of movement at the angle no less than 70° (Fig. 6).

TВ-01 Electromechanical box tripod turnstile with two built-in readers
Figure 6 – Installation recommendations
9.2. Installation tools
– hammer drill 1,21,5 kW;
– hard-alloyed drill bit 16 mm for anchor bolt sleeves;
– floor chaser for cable raceways;
–flat slot screwdriver №2;
– flat slot screwdriver №5 (length 150 mm);
– cross-head screwdriver №2;
– horn-type and socket wrenches: S17, S13, S10, S8, S7;
– level;
– measuring tape 2 m;
– slide caliper.
Note: It is allowed to use other testing equipment and measuring tools providedthe
equipment in use ensures the required parameters and measurement accuracy.
9.3. Cable length
The maximum allowed length of the remote control panel / wireless remote control
cable is 30m.
The maximum allowed length of the turnstile power cable depends on the cable
cross-section and should not exceed:
for cable with 0.75mm2 cross – section (AWG 18) .......................... 10 m;
for cable with 1.5mm2 cross – section (AWG 16) ........................... 30 m.
9.4. Installation procedure
Note! The manufacturer shall not be liable for any damage caused as the result of
improper installation and declines any claims arising thereof in case if the installation
is done not in compliance with the instructions provided in this Manual.
9.4.1 Unpack the TВ-01 turnstile and check the completeness as per Section 3
of the product certificate.
9.4.2 Make holes for anchor bolt sleeves for the turnstile housing installation
(Fig. 7).
Prepare a cable raceway for cables when cables are laid concealed under floor. Install
and fix the turnstile housing only after all cables inside the turnstile housing and in
17

Assembly and Operation Manual
electric raceways are laid. Cable routing inside the turnstile housing is shown in
Figure 8.
Figure 7 – TB-01 turnstile housing installation layout
9.4.3 Insert anchor bolts sleeves into the holes so that they did not stick out
above the floor surface. Remove the turnstile housing side covers (12, 14)
by unlocking the locks (13, 15). Set up the housing on anchor bolt sleeves
and fix it with the M10 bolts.
9.4.4 Install the turnstile power supply unit in its place (See power supply unit
certificate for installation procedure of the power supply unit).
9.4.5 Remove the turnstile housing top cover (3) by unlocking the lock with a
key (4 ref. Section 6).
9.4.6 Connect the power cable (18) to a connector block “X1.1” (Ref. Fig. А.1
Appendix А). Connect the cable (17) of the RC panel (16) to a connector
block “XT1.L” on the CLB (Fig. 3). Connect cables of other devices, when
used, to corresponding connector blocks of the CLB (Ref. Fig. 3 and
Fig. А.1 Appendix А).
9.4.7 Check serviceability and accuracy of all the electrical connections. Fix the
cables using self-adhesive cable tie mounts and nylon cable ties supplied
with a standard delivery set. After all cables are connected and the turn-
stile housing is fixed to the floor return the top cover (3) to its place (Ref.
Section 6) and the turnstile housing side covers (12, 14) in order reverse to
their removing.
9.4.8 To mount the barrier arms into the run position remove the cover (6) from the
hub after unscrewing the screw М4х25. Unscrew the М8х30 bolt on the
barrier arm (5). Fit the barrier arm into the mounting hole on the hub and
fasten it with the bolt. Put a spring washer under the bolt head. The bolts
must be tightened so as to ensure reliable non-play fixation of the barrier
arms.
Repeat the above-described procedure for fitting up the remaining barrier arms.
Put the cover (6) in its operation position and fix it with the screw.
9.4.9 Run a test switch on of the turnstile as specified in Clause 10.2.
After the installation and testing are complete the turnstile is ready to operate.
18

TВ-01 Electromechanical box tripod turnstile with two built-in readers
19
Figure 8 – Cable routing inside the TВ-01 turnstile housing:
1 – power cable; 2 – cable from the RC panel/ wireless remote control device; 3 – rotation mechanism
connection cable; 4 – cables of card readers №1 and №2; 5 –CLB; 6 – rotation mechanism; 7 - bracket
(ACS installation)
№1 – cover with reader 1; №2 – cover with reader 2.
Table of contents
Other PERCo Turnstile manuals

PERCo
PERCo RTD-15 Series User manual

PERCo
PERCo TTD-03.2 User manual

PERCo
PERCo TTR-11A Supplement

PERCo
PERCo TTR-08A Installation and operating instructions

PERCo
PERCo TTD-12A Installation and operating instructions

PERCo
PERCo TTR-04CW Installation and operating instructions

PERCo
PERCo TTR-04CW-24 Installation and operating instructions

PERCo
PERCo TTR-10A Series Installation and operating instructions

PERCo
PERCo TTR-07.1 Installation and operating instructions

PERCo
PERCo T-5 Installation and operating instructions