Pilz PNOZ mc4p User manual

PNOZ mc4p
Operating Manual 21054-EN-05
}Configurable safety systems PNOZmulti

Preface
This document is a translation of the original document.
All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be made
for internal purposes. Suggestions and comments for improving this documentation will be
gratefully received.
Source code from third-party manufacturers or open source software has been used for
some components. The relevant licence information is available on the Internet on the Pilz
homepage.
Pilz®, PIT®, PMI®, PNOZ®, Primo®, PSEN®, PSS®, PVIS®, SafetyBUS p®,
SafetyEYE®, SafetyNET p®, the spirit of safety® are registered and protected trademarks
of Pilz GmbH & Co. KG in some countries.
SD means Secure Digital

Contents
Operating Manual PNOZ mc4p
21054-EN-05 3
Section 1 Introduction 5
1.1 Validity of documentation 5
1.2 Using the documentation 5
1.3 Definition of symbols 5
Section 2 Overview 7
2.1 Scope 7
2.2 Unit features 7
2.3 Front view 8
Section 3 Safety 9
3.1 Intended use 9
3.2 System requirements 9
3.3 Safety regulations 10
3.3.1 Use of qualified personnel 10
3.3.2 Warranty and liability 10
3.3.3 Disposal 10
3.3.4 For your safety 10
Section 4 Function description 11
4.1 Operation 11
4.2 Input and output data 11
4.3 Assigning the inputs/outputs in the PNOZmulti Configurator to the Devi-
ceNet inputs/outputs
12
4.4 Block diagram 12
Section 5 Installation 13
5.1 General installation guidelines 13
5.2 Dimensions in mm 13
5.3 Connecting the base unit and expansion modules 14
Section 6 Commissioning 15
6.1 General wiring guidelines 15
6.2 Connecting the supply voltage 15
6.3 DeviceNet interface 15
6.4 Setting the transmission rate 16
6.5 Setting the station address 16
6.6 Download modified project to the PNOZmulti safety system 16
6.7 Connection example 17
Section 7 Operation 18
7.1 Messages 18
Section 8 Technical Details 19

Contents
Operating Manual PNOZ mc4p
21054-EN-05 4
Section 9 Order reference 21
9.1 Product 21
9.2 Accessories 21

Introduction
Operating Manual PNOZ mc4p
21054-EN-05 5
1 Introduction
1.1 Validity of documentation
This documentation is valid for the product PNOZ mc4p. It is valid until new documentation
is published.
This operating manual explains the function and operation, describes the installation and
provides guidelines on how to connect the product.
1.2 Using the documentation
This document is intended for instruction. Only install and commission the product if you
have read and understood this document. The document should be retained for future ref-
erence.
1.3 Definition of symbols
Information that is particularly important is identified as follows:
DANGER!
This warning must be heeded! It warns of a hazardous situation that poses
an immediate threat of serious injury and death and indicates preventive
measures that can be taken.
WARNING!
This warning must be heeded! It warns of a hazardous situation that could
lead to serious injury and death and indicates preventive measures that can
be taken.
CAUTION!
This refers to a hazard that can lead to a less serious or minor injury plus
material damage, and also provides information on preventive measures
that can be taken.
NOTICE
This describes a situation in which the product or devices could be dam-
aged and also provides information on preventive measures that can be
taken. It also highlights areas within the text that are of particular import-
ance.

Introduction
Operating Manual PNOZ mc4p
21054-EN-05 6
INFORMATION
This gives advice on applications and provides information on special fea-
tures.

Overview
Operating Manual PNOZ mc4p
21054-EN-05 7
2 Overview
2.1 Scope
}Expansion module PNOZ mc4p
}Jumper
2.2 Unit features
Using the product PNOZ mc4p:
Expansion module for connection to a base unit from the configurable control system
PNOZmulti
The product has the following features:
}Can be configured in the PNOZmulti Configurator
}Connection for DeviceNet
}Station addresses from 0 ... 63 can be selected via DIP switches
}Status indicators for communication with DeviceNet and for errors
}Please refer to the document "PNOZmulti System Expansion" for the PNOZmulti base
units that can be connected.
}Coated version:
Increased environmental requirements (see Technical details [ 19])

Overview
Operating Manual PNOZ mc4p
21054-EN-05 8
2.3 Front view
PNOZ mc4p
X1
NS
DR
NA
1 2 3 4 5
V-
V+
CL
CH
SD
S1
S2
32
16
8
4
2
1
MS
ON OFF
Legend:
}X1: DeviceNet interface (5-pin screw connector)
}LED:
– Power
– NS
– MS

Safety
Operating Manual PNOZ mc4p
21054-EN-05 9
3 Safety
3.1 Intended use
The expansion module PNOZ mc4p is used for communication between the configurable
safety system and DeviceNet.
DeviceNet is designed for fast data exchange at field level. The expansion module PNOZ
mc4p is a passive DeviceNet subscriber (Slave). The basic communication functions with
DeviceNet meet the requirements of the DeviceNet specification, Release 2.0. The central
controller (master) reads input information from the slaves and writes output information to
the slaves as part of each cycle. As well as the cyclical transfer of usable data, the expan-
sion module PNOZ mc4p can also be used for diagnostic and commissioning functions.
Data traffic is monitored on the Master/Slave side.
The expansion module may only be connected to a base unit from the configurable system
PNOZmulti (please refer to the document "PNOZmulti System Expansion" for details of the
base units that can be connected).
The configurable system PNOZmulti is used for the safety-related interruption of safety cir-
cuits and is designed for use in:
}Emergency stop equipment
}Safety circuits in accordance with VDE0113 Part 1 and EN60204-1
The expansion module may not be used for safety-related functions.
The following is deemed improper use in particular:
}Any component, technical or electrical modification to the product
}Use of the product outside the areas described in this manual
}Use of the product outside the technical details (see Technical details [ 19]).
NOTICE
EMC-compliant electrical installation
The product is designed for use in an industrial environment. The product
may cause interference if installed in other environments. If installed in other
environments, measures should be taken to comply with the applicable
standards and directives for the respective installation site with regard to in-
terference.
3.2 System requirements
Please refer to the "Product Modifications PNOZmulti" document in the "Version overview"
section for details of which versions of the base unit and PNOZmulti Configurator can be
used for this product.

Safety
Operating Manual PNOZ mc4p
21054-EN-05 10
3.3 Safety regulations
3.3.1 Use of qualified personnel
The products may only be assembled, installed, programmed, commissioned, operated,
maintained and decommissioned by competent persons.
A competent person is someone who, because of their training, experience and current pro-
fessional activity, has the specialist knowledge required to test, assess and operate the
work equipment, devices, systems, plant and machinery in accordance with the general
standards and guidelines for safety technology.
It is the company’s responsibility only to employ personnel who:
}Are familiar with the basic regulations concerning health and safety / accident preven-
tion
}Have read and understood the information provided in this description under "Safety"
}And have a good knowledge of the generic and specialist standards applicable to the
specific application.
3.3.2 Warranty and liability
All claims to warranty and liability will be rendered invalid if
}The product was used contrary to the purpose for which it is intended
}Damage can be attributed to not having followed the guidelines in the manual
}Operating personnel are not suitably qualified
}Any type of modification has been made (e.g. exchanging components on the PCB
boards, soldering work etc.).
3.3.3 Disposal
}When decommissioning, please comply with local regulations regarding the disposal of
electronic devices (e.g. Electrical and Electronic Equipment Act).
3.3.4 For your safety
The unit meets all the necessary conditions for safe operation. However, you should always
ensure that the following safety requirements are met:
}This operating manual only describes the basic functions of the unit. The expanded
functions are described in the PNOZmulti Configurator's online help. Only use these
functions once you have read and understood the documentations.
}Do not open the housing or make any unauthorised modifications.
}Please make sure you shut down the supply voltage when performing maintenance
work (e.g. exchanging contactors).

Function description
Operating Manual PNOZ mc4p
21054-EN-05 11
4 Function description
4.1 Operation
The virtual inputs and outputs that are to be transferred via DeviceNet are selected and
configured in the PNOZmulti Configurator. The base unit and the expansion module PNOZ
mc4p are connected via a jumper. The expansion module PNOZ mc4p is also supplied with
voltage via this jumper.
The station address and the transmission rate are set using DIP switches. After the supply
voltage is switched on or the PNOZmulti control system is reset, the expansion module
PNOZ mc4p is configured and started automatically.
LEDs indicate the status of the expansion module on DeviceNet.
The configuration is described in detail in the PNOZmulti Configurator's online help.
4.2 Input and output data
The data is structured as follows:
}Input area
The inputs are defined in the master and transferred to the PNOZmulti. Each input has
a number, e.g. input bit 4 of byte 1 has the number i12.
}Output range
The outputs are defined in the PNOZmulti Configurator. Each output that is used is
given a number there, e.g. o0, o5... The status of output o0 is stored in bit 0 of byte 0;
the status of output o5 is stored in bit 5 of byte 0 etc.
}Output range only: Byte 3
Bits 0 … 4: Status of LEDs on the PNOZmulti
– Bit 0: OFAULT
– Bit 1: IFAULT
– Bit 2: FAULT
– Bit 3: DIAG
– Bit 4: RUN
Bit 5: Data is being exchanged.
Detailed information on data exchange (tables, segments) is available in the document
"Communication Interfaces" in the section entitled "Fieldbus modules".

Function description
Operating Manual PNOZ mc4p
21054-EN-05 12
4.3 Assigning the inputs/outputs in the PNOZmulti Configurator
to the DeviceNet inputs/outputs
Virtual inputs on PNOZmulti Configurator i0 ... I7 i8 ... i15 i16 ... i23
Input data DeviceNet Byte 0: Bits 0 … 7 Byte 1: Bits 0 … 7 Byte 2: Bits 0 … 7
Virtual outputs on PNOZmulti Configurator o0 ... o7 o8 ... o15 o16 ... o23
Output data DeviceNet Byte 0: Bits 0 … 7 Byte 1: Bits 0 … 7 Byte 2: Bits 0 … 7
The number of virtual inputs and outputs can be extended to 128 (see document "Commu-
nication Interfaces" in the section entitled "Fieldbus modules")
4.4 Block diagram
Base unit
V-
V+
CL
SD
CH
DeviceNet

Installation
Operating Manual PNOZ mc4p
21054-EN-05 13
5 Installation
5.1 General installation guidelines
}The control system should be installed in a control cabinet with a protection type of at
least IP54. Fit the control system to a horizontal mounting rail. The venting slots must
face upward and downward. Other mounting positions could destroy the control system.
}Use the notches on the rear of the unit to attach it to a mounting rail. Connect the con-
trol system to the mounting rail in an upright position, so that the earthing springs on the
control system are pressed on to the mounting rail.
}The ambient temperature of the PNOZmulti units in the control cabinet must not exceed
the figure stated in the technical details, otherwise air conditioning will be required.
}To comply with EMC requirements, the mounting rail must have a low impedance con-
nection to the control cabinet housing.
CAUTION!
Damage due to electrostatic discharge!
Electrostatic discharge can damage components. Ensure against discharge
before touching the product, e.g. by touching an earthed, conductive sur-
face or by wearing an earthed armband.
5.2 Dimensions in mm
94 (3.70")
22,5
(0.88")
114 (4.49")

Installation
Operating Manual PNOZ mc4p
21054-EN-05 14
5.3 Connecting the base unit and expansion modules
You can install a maximum of 1 PNOZ mc4p to the left of the base unit.
Connect the base unit and the expansion module as described in the operating instructions
for the base units.
}Do not connect a terminator to the last expansion module on the left-hand side.
}Install the expansion module in the position in which it is configured in the PNOZmulti
Configurator.
}A distance of at least 20 mm must be maintained between the fieldbus module PNOZ
mc4p and any external heat sources.

Commissioning
Operating Manual PNOZ mc4p
21054-EN-05 15
6 Commissioning
6.1 General wiring guidelines
The wiring is defined in the circuit diagram of the PNOZmulti Configurator.
Please note:
}Information given in the Technical details [ 19] must be followed.
}Use copper wire that can withstand 75°C.
}The power supply must meet the regulations for extra low voltages with protective sep-
aration.
CAUTION!
Only connect and disconnect the expansion module when the supply
voltage is switched off.
}Always connect the mounting rail to the protective earth via an earthing terminal. This
will be used to dissipate hazardous voltages in the case of a fault.
NOTICE
Be sure to observe the requirements of the DeviceNet specification, volume
I, release 2.0 during installation.
6.2 Connecting the supply voltage
Connect the supply voltage to the base unit:
}Terminal 24 V and A1 (+): + 24VDC
}Terminal 0 V and A2 (-): 0 V
6.3 DeviceNet interface
It is possible to define which outputs on the control system will communicate with Devi-
ceNet. The connection to DeviceNet is made via a 5-pin screw connector.
1 2 3 4 5
V- V+CL CHSD
V-
CL
V+
CH
SD
1:
2:
3:
4:
5:
V-
CL (CAN_L)
Cable screening
CH (CAN_H)
V+
Termination DeviceNet
To minimise cable reflection and to guarantee a defined rest signal on the transmission line,
DeviceNetmust be terminated at both ends.

Commissioning
Operating Manual PNOZ mc4p
21054-EN-05 16
6.4 Setting the transmission rate
Set the transmission rate using DIP switches S1 and S2 (DR).
Transmission rate DIP switch
S1 S2
125 kBit/s Off Off
250 kBit/s On Off
500 kBit/s Off On
--- On On
INFORMATION
The transmission rate cannot be changed during operation.
6.5 Setting the station address
The station address of the expansion module PNOZ mc4p is set from 0 ... 63 (binary) using
DIP switches 1 to 32.
Station address DIP switch
32 16 8 4 2 1
0 Off Off Off Off Off Off
1 Off Off Off Off Off On
2 Off Off Off Off On Off
3 Off Off Off Off On On
... ... ... ... ... ... ...
62 On On On On On Off
63 On On On On On On
6.6 Download modified project to the PNOZmulti safety system
As soon as an additional expansion module has been connected to the system, the project
must be amended using the PNOZmulti Configurator. Proceed as described in the operat-
ing instructions for the base unit.
NOTICE
For the commissioning and after every program change, you must check
whether the safety devices are functioning correctly.

Commissioning
Operating Manual PNOZ mc4p
21054-EN-05 17
6.7 Connection example

Operation
Operating Manual PNOZ mc4p
21054-EN-05 18
7 Operation
When the supply voltage is switched on, the PNOZmulti safety system copies the configur-
ation from the chip card.
The LEDs “POWER”, “DIAG”, “FAULT”, “IFAULT” and “OFAULT” will light up on the base
unit.
The expansion module PNOZ mc4p is configured and started automatically. The LEDs
“MS” and “NS” display the status of the PNOZ mc4p on DeviceNet.
If the expansion module PNOZ mc4p does not receive a configuration from the base unit
for a period of 30 s, the fieldbus module PNOZ mc4p connects to DeviceNet and "Online"
status is displayed on DeviceNet. The "MS" LED flashes red.
7.1 Messages
Legend
LED on
LED flashes
LED off
LED Meaning
NS Green PNOZ mc4p in "Link OK, Online, Connected" status
Green PNOZ mc4p in "Online, Not connected" status
Red PNOZ mc4p detects "Critical link failure"
Red Time monitoring ("Connection Timeout") has expired.
No supply voltage or offline
MS Green PNOZ mc4p in "Device Operational" status
Green Configuration error; size of data does not correspond to the configuration
Red PNOZ mc4p detects non-recoverable error
Red PNOZ mc4p detects recoverable error ("Minor Fault").
No supply voltage on PNOZ mc4p
Remedy: Make sure that the fieldbus module PNOZ mc4p is connected to
the base unit.

Technical Details
Operating Manual PNOZ mc4p
21054-EN-05 19
8 Technical Details
General 773711 773729
Approvals
CCC, CE, EAC (Eurasian), KCC,
KOSHA, TÜV, cULus Listed
CCC, CE, EAC (Eurasian), KCC,
KOSHA, TÜV, cULus Listed
Electrical data 773711 773729
Supply voltage
for Module supply Module supply
internal Via base unit Via base unit
Voltage 5,0 V 5,0 V
Kind DC DC
Voltage tolerance -2 %/+2 % -2 %/+2 %
Power consumption 1,0 W 1,6 W
Status indicator LED LED
Fieldbus interface 773711 773729
Fieldbus interface DeviceNet DeviceNet
External supply (DC) 24 V 24 V
Power consumption 0,75 W 0,75 W
Device type Slave Slave
Station address 0 ... 63d 0 ... 63d
Transmission rates 125 kBit/s, 250 kBit/s, 500 kBit/s 125 kBit/s, 250 kBit/s, 500 kBit/s
Connection 5-pin Combicon plug-in con-
nector
5-pin Combicon plug-in con-
nector
Galvanic isolation yes yes
Test voltage 500 V AC 500 V AC
Times 773711 773729
Supply interruption before de-ener-
gisation 20 ms 20 ms
Environmental data 773711 773729
Ambient temperature
In accordance with the standard EN 60068-2-14 EN 60068-2-14
Temperature range 0 - 60 °C 0 - 50 °C
Storage temperature
In accordance with the standard EN 60068-2-1/-2 EN 60068-2-1/-2
Temperature range -25 - 70 °C -25 - 70 °C
Climatic suitability
In accordance with the standard EN 60068-2-30, EN 60068-2-78 EN 60068-2-30, EN 60068-2-78
Humidity 93 % r. h. at 40 °C 93 % r. h. at 40 °C
Condensation during operation Not permitted Short-term
EMC EN 61131-2 EN 61131-2
Vibration
In accordance with the standard EN 60068-2-6 EN 60068-2-6
Frequency 10,0 - 150,0 Hz 10,0 - 150,0 Hz
Acceleration 1g 1g

Technical Details
Operating Manual PNOZ mc4p
21054-EN-05 20
Environmental data 773711 773729
Shock stress
In accordance with the standard EN 60068-2-27 EN 60068-2-27
Acceleration 15g 15g
Duration 11 ms 11 ms
Max. operating height above sea
level 2000 m 2000 m
Airgap creepage
In accordance with the standard EN 61131-2 EN 61131-2
Overvoltage category III III
Pollution degree 2 2
Rated insulation voltage 30 V 30 V
Protection type
In accordance with the standard EN 60529 EN 60529
Mounting area (e.g. control cab-
inet) IP54 IP54
Housing IP20 IP20
Terminals IP20 IP20
Mechanical data 773711 773729
Mounting position Horizontal on top hat rail Horizontal on top hat rail
DIN rail
Top hat rail 35 x 7,5 EN 50022 35 x 7,5 EN 50022
Recess width 27 mm 27 mm
Material
Bottom PPO UL 94 V0 PPO UL 94 V0
Front ABS UL 94 V0 ABS UL 94 V0
Dimensions
Height 94,0 mm 94,0 mm
Width 22,5 mm 22,5 mm
Depth 122,0 mm 122,0 mm
Weight 110 g 143 g
Where standards are undated, the 2010-05 latest editions shall apply.
Other manuals for PNOZ mc4p
3
This manual suits for next models
2
Table of contents
Other Pilz Computer Hardware manuals

Pilz
Pilz Intern PMC SR6 User manual

Pilz
Pilz PNOZ m EF 8DI4DO User manual

Pilz
Pilz PNOZ ma1p User manual

Pilz
Pilz PNOZ m ES RS232 User manual

Pilz
Pilz PNOZ m EF PDP Link User manual

Pilz
Pilz PNOZ mc5p User manual

Pilz
Pilz PNOZ po3.2p User manual

Pilz
Pilz PNOZ mc3p User manual

Pilz
Pilz PNOZ m ES EtherNet/IP User manual

Pilz
Pilz PNOZ mo3p User manual