Operation Manual
This brief manual is primarily meant for quick reference to wiring
connections and parameter searching. For more details on
operation and application; please log on to www.ppiindia.net
Enhanced Universal Single Loop
Process Controller
neuro 102 EX
(Default : Relay)
Relay
SSR
0 - 20mA
4 - 20mA
0 - 5 V
0 - 10 V
Parameters Settings
(Default Value)
(Default : -200.0)
Min. Range for the
selected Input Type to
Setpoint High Limit
Setpoint Low Limit to
Max. Range for the
selected Input Type
(Default : 1376.0)
-19999 to PV Range High
(Default : 0)
PV Range Low to 9999
(Default : 1000)
Refer Table 1
(Default : Type K)
CONFIGURATION PARAMETERS : PAGE 12
0 to 100 or -100.0 to 100.0
(Default : 0)
0 to 600 Seconds
(Default : 16 Sec.)
0 to 3600 Seconds
(Default : 100 Sec.)
Parameters Settings
(Default Value)
0.1 to 999.9 Units
(Default : 50 units)
0.1 to 10.0
(Default : 1.0)
Proportional Band
CONTROL PARAMETERS : PAGE 10
Parameters Settings
(Default Value)
1 to 999 or 0.1 to 999.9
(Default : 0.2)
1 to 999 or 0.1 to 999.9
(Default : 2)
Pulse Time
Cool Cycle Time
Hysteresis
Heat Power Low
ON Time
Cool Hysteresis
Cool Pulse Time
Cool ON Time
Heat Power High
Cool Power High
Cool Power Low
Active Segment Number
Upper Readout
Information
Lower Readout
Prompt
Target Setpoint
Ramping Setpoint
Balance Time
Balance Repeats
Segment Type
PROFILE STATUS INFORMATION : PAGE 1
RA MP :- Alter ing th e ti me
inte rval s hall imme diately
affect the ‘Ramp Rate’ for the
current segment.
SOAK:- Elapsed time so far is
ignored and the soak timer
starts counting down to 0 from
the altered time interval value.
Time Interval
Effect on the running segment
Parameters
Holdback Type
The modified Holdback Band
Type is applied immediately on
the current segment.
Holdback Value
The modified Holdback Band
Value is applied immediately
on the current segment.
ON-LINE ALTERATION PARAMETERS : PAGE 2
Option Range (Min. to Max.)
0 to +960°C / +32 to +1760°F
-200 to +1376°C / -328 to +2508°F
-200 to +385°C / -328 to +725°F
Fixed
1°C / 1°F
-1999 to +9999 units
-199 to +600°C / -328 to +1112°F
-199.9 to 600.0°C / -199.9 to 999.9°F
or
User settable
1 / 0.1 / 0.01/
0.001 units
0 to +1770°C / +32 to +3218°F
0 to +1765°C / +32 to +3209°F
0 to +1825°C / +32 to +3218°F
0 to +1300°C / +32 to +2372°F
J Type T/C
RTD Pt100
0 to 20mA DC
4 to 20mA DC
0 to 50mV DC
0 to 200mV DC
0 to 1.25V DC
0 to 5.0V DC
0 to 10.0V DC
1 to 5.0V DC
K Type T/C
T Type T/C
R Type T/C
S Type T/C
B Type T/C
N Type T/C
Reserved for customer specific
Thermocouple type not listed
above.
TABLE- 1
101, Diamond Industrial Estate, Navghar,
Vasai Road (E), Dist. Palghar - 401 210.
T: 0250 - 2391722/33/37/42
M: 07498799226
09321985369
PV Range Low
PV Range High
Control Output
(OP1) Type
Control Action
Control Logic
PV Units
PV Resolution
Input Type
Setpoint Low Limit
Offset for PV
Sensor Break Output
Power
Digital Filter Time
Constant
Setpoint High Limit
Integral Time
Derivative Time
Cycle Time
Relative Cool Gain
Parameters Settings
(Default Value)
PROFILE CONFIGURATION PARAMETERS : PAGE 16
Number of Segments
Number of Repeats
Common Holdback
Output Off
Power Fail Strategy
(Default : Continue)
Abort
Continue
Parameters Settings
(Default Value)
Segment Number
Time Interval
Holdback Type
Holdback Value
Target Setpoint
(Default : -199)
Min. to Max. Range
specified for the
selected Input Type
PROFILE SETTING PARAMETERS : PAGE 14
(Default : PID)
On-Off
PID
Pulse
(Default : Reverse)
Reverse
Direct
(Default : C)°
°C
°F
0.5 to 60.0 Seconds
(in steps of 0.5 Seconds)
(Default : 2.0 Sec.)
0.5 to 100.0 Seconds
(in steps of 0.5 secs.)
(Default : 10.0 sec.)
Pulse ON Time
to 120.0 Seconds
(Default : 2.0 sec.)
0.1 to Value set
for Pulse Time
(Default : 1.0)
Profile mode selection
0.1 to Value set for
Cool Pulse Time
(Default : 1.0)
Cool ON Time
to 120.0 Seconds
(Default : 2.0)
0 to Power High
(Default : 0)
Power Low to 100%
(Default : 100.0)
0 to Cool Power High
(Default : 0)
Cool Power Low to 100%
(Default : 100)
1 to 16
(Default : 16)
Parameters Settings
(Default Value)
Alarm-1 Type
None
Process
Low
Process
High
Deviation
Band
Window
Band
(Default : None)
Alarm-1 Setpoint
Min. to Max. Range
specified for the
selected Input Type
(Default : Min or Max Range)
ALARM PARAMETERS : PAGE 11
Min. to Max. Range
specified for the
selected Input Type
(Default : Min or Max Range)
None
Process
Low
Process
High
Deviation
Band
Window
Band
(Default : None)
Alarm-1 Deviation Band
Alarm-1 Window Band
Alarm-1 Hysteresis
Alarm-1 Inhibit
Alarm-2 Setpoint
Alarm-2 Type
Alarm-2 Deviation Band
Alarm-2 Window Band
Alarm-2 Hysteresis
Alarm-2 Inhibit
-999 to 999 or
-999.9 to 999.9
(Default : 5.0)
1 to 999 or 0.1 to 999.9
(Default : 2)
3 to 999 or 0.3 to 999.9
(Default : 5.0)
-999 to 999
or -999.9 to 999.9
(Default : 5.0)
1 to 999 or
0.1 to 999.9
(Default : 2.0)
Standby Mode
Alarm SP Adjustment
on Operator Page
SP Adjustment on
Lower Readout
Auxiliary Setpoint
Recorder
(Retransmission)
Output
Settings
(Default Value)
Parameters
SUPERVISORY PARAMETERS : PAGE 13
Self-Tune Command
1.0 to 2.0
(Default : 1.0)
Disable
Enable
(Default : Disable)
Overshoot Inhibit
Overshoot Inhibit
Factor
SP Adjustment
on Operator Page
Manual Mode
(Default : Disable)
Disable
Enable
Profile Abort Command
on Operator Page
Settings
(Default Value)
Parameters
Baud Rate
Communication Parity
Controller ID Number
Communication
Write Enable
(Default : Even)
(Default : 9.6)
4800
9600
19200
38400
57600
Parameters Settings
(Default Value)
(Default : Relay)
Relay
SSR
0 - 20mA
4 - 20mA
0 - 10 V
0 - 5 V
(Default : Seconds)
Seconds
Minutes
Hours
(Default : ON)
OFF
ON
Output-2 Function
Selection
(Default : Normal)
Reverse
Normal
OP2 & OP3,OP4,OP5 FUNCTION PARAMETERS : PAGE 15
(Default : ON)
OFF
ON
(Default : None)
Cool Control
End Of
Profile
None
Output-2 Type
OP2 Event Time
OP2 Event Status
OP2 Event Time Units
Alarm-1 Logic
OP3 Event Status
Output-3 Function
Selection
OP3 Event Time
(Default : Seconds)
Seconds
Minutes
Hours
OP3 Event Time Units
-199 to 999 or
-1999.9 to 9999.9
(Default : 0)
Refer Table 1
(Default : 1)
0.5 to 100.0 Seconds
(in steps of 0.5 secs.)
(Default : 10.0 Sec.)
(Default : No)
No
Yes
Disable
Enable
(Default : Disable)
Disable
Enable
(Default : Enable)
Disable
Enable
(Default : Enable)
Disable
Enable
(Default : Disable)
Disable
Enable
(Default : Disable)
Disable
Enable
(Default : Disable)
Disable
Enable
(Default : Disable)
(Default : No)
No
Yes
(Default : Alarm)
None
End of
Profile
Alarm
(Default : Normal)
Reverse
Normal
Alarm-2 Logic
Parameters Settings
(Default Value)
(Default : -199)
Min. to Max. Range
Specified for the
Selected Input Type
(Default : 1376)
Min. to Max. Range
Specified for the
Selected Input Type
Recorder Low
Recorder Output Type
Recorder High
Recorder
Transmission Type
(Default : Process Value)
Setpoint
Process
Value
(Default : 0 to 20mA)
0 to 20mA
0 to 10 Volts
0 to 5 Volts
4 to 20mA
(Default : Yes)
No
Yes
3 to 999 or
0.3 to 999.9
(Default : 5.0)
(Default : Yes)
No
Yes
(Default : Disable)
Disable
Enable
(Default : Yes)
No
Yes
(Default : No)
No
Yes
(Default : None)
None
Both
Down
Up
Effect on the running segment
Parameters
USER LINEARISATION PARAMETERS : PAGE 33
0 to 9999
(Default : 0)
Code
User Linearisation
1 to 32
(Default : 2)
Total Break
Points
Break Point
Number
-1999 to 9999
(Default : Undefined)
Actual Value for
Break Point
(X co-ord)
Derived Value for
Break Point
(Y co-ord) -1999 to 9999
(Default : Undefined)
(Default : Disable)
Disable
Enable
1 to 32
(Default : 1)
1 to 9999
(Default : 1)
1 to 16
(Default : 1)
0 to 9999 Minutes
(Default : 0)
1 to 999
(Default : 1)
1 to 127
(Default : 1)
0 to 9999
(Default : 0)
0 to 9999
(Default : 0)
Resolution
None
Even
Odd
User settable
1°C / 1°F
or
0.1°C / 0.1°F