PPI neuro 102 User manual

neuro 102
User Manual
Universal Single Loop
Process Controller
MC
AL2
neuro 102
AL1

CONTENTS
User Manual
neuro 102
1. FRONT PANEL LAYOUT 1
2. BASIC OPERATION 3
3. SET-UP MODE ACCESS AND OPERATION 8
4. 10CONTROL PARAMETERS
5. ALARM PARAMETERS 12
6. CONFIGURATION PARAMETERS 14
7. SUPERVISORY PARAMETERS 17
8. 19PROFILE PARAMETERS
9. OP2 & OP3 FUNCTION PARAMETERS 22
10. HARDWARE ASSEMBLY & CONFIGURATIONS 24
11. MECHANICAL INSTALLATION 31
12. ELECTRICAL CONNECTIONS 33
For Size 48X48
For Size 96X96
1. FRONT PANEL LAYOUT 38
2. HARDWARE ASSEMBLY & CONFIGURATION 40
3. 44ELECTRICAL CONNECTIONS

1
Figure 1.1
PPI
neuro 102
AL1 AL2 PRF
Upper Readout
Lower Readout
Profile Status
ENTER Key
UP Key
DOWN Key
PAGE Key
Alarm-1 Status
Alarm-2 Status
Auto / Manual
Status
Control Status
M
C
Table 1.1
FRONT PANEL LAYOUT
The controller front panel comprises of digital readouts, LED indicators and membrane keys as shown in Figure 1.1 below.
READOUTS
The Upper Readout is a 4 digit, 7-segment bright red LED display and usually displays the PV (Process Value). In Set-up
Mode, the Upper Readout displays parameter values/options.
The Lower Readout is a 4 digit, 7-segment bright green LED display and usually displays Setpoint Value or % Output Power. In
Set-up Mode, the Lower Readout displays parameter names (prompts) .
INDICATORS
The front panel indicators are red LED’s that show the status related to control, alarm and operation mode. Refer Table 1.1
below for details.
Section 1
AL1
• Indicates Output-1 ON/OFF status if the Control Output Type is Relay / SSR
drive.
• Remains OFF if the Control Output Type is DC Linear.
C
LED Status
M• Glows if the manual (Hand ) mode is active.
• Remains OFF if Automatic (Auto). Standby or profile mode is active.
• Flashes while the Alarm-1 is active.
• Remains OFF while the Alarm - 1 is inactive or if OP2 is configured as cool
control output
Indicates Alarm-1 status if Output -2 (OP2) is configured as Alarm.
User Manual
neuro 102

2
KEYS
There are four tactile keys provided on the front panel for configuring the controller, setting-up the parameter values and
selecting Operation Modes. Refer Table 1.2 for detailed key operations.
Table 1.2
Symbol Key Function
Press to enter or exit set-up mode.
DOWN
UP
ENTER Press to store the set parameter value and to scroll to the next
parameter on the PAGE.
Press to increase the parameter value. Pressing once increases the
value by one count; keeping pressed speeds up the change.
Press to decrease the parameter value. Pressing once decreases
the value by one count; keeping pressed speeds up the change.
PAGE
AL2 • Flashes while the Alarm-2 is active.
• Remains OFF while the Alarm - 2 is inactive or if OP3 is configured as
Recorder / Retransmission.
Indicates Alarm-1 status if Output -3 (OP3) is configured as Alarm.
PRF • Flashes while the controller is executing ramp/soak profile cycle.
• Glows continuously if the profile cycle is in HOLD state.
• Remains OFF, if not executing a profile Cycle.
Indicates profile status if the Profile mode is Enabled.
User Manual
neuro 102

3
Heat or Cool Power
Uni-directional Control Bi-directional Control
Heat Power Cool Power
Figure 2.1
POWER-UP
Upon power-up, all displays and indicators are lit on for approximately 3 seconds. This is followed by the indication of the
controller model name on the Upper Readout and the firmware version on the Lower Readout, for
approximately 1 second.
MAIN DISPLAY MODE
After the Power-up display sequence, the Upper Readout starts showing the measured PV (Process Value) and the Lower
Readout displays the Setpoint Value. This is the MAIN Display Mode that shall be used most often.
% Output Power Indication
In PID control mode, the Lower Readout can be toggled using ENTER key to indicate either % output power or setpoint value
SP. The output power is indicated with the left most digit showing ‘P’, ‘H’ or ‘C’ depending upon uni-directional (Heat or Cool) or
bi-directional (Heat and Cool) control mode. Refer Figure 2.1 below.
Tune Mode Indication
The Lower Readout flashes while the controller is Tuning. Do not disturb the process or alter any parameter values
while Tuning is in progress. The “Tune” message automatically disappears upon completion of Tuning procedure.
Profile Mode Indications
While a Profile Cycle is in progress, the front panel indicator ‘PRF’ flashes or glows steadily. The steady glowing indicates that
though the profile is active, it is currently in HOLD state. Also, the Lower Readout shows the Profile Setpoint instead of the
control setpoint SP. The % Output Power (if PID Control) can be viewed by toggling the Lower Readout using ENTER key.
Note :
While Profile Cycle is in progress, the Control Setpoint SP can still be adjusted on Lower Readout. While the Lower Readout shows Profile
Setpoint, use UP/DOWN keys to adjust the control setpoint SP as described earlier.
PV Error Indications
The PV Error type is flashed on the Upper Readout. For different errors and the causes, refer Table 2.1 below.
BASIC OPERATION
Adjusting SP (Control Setpoint)
If permitted at Supervisory Level, the SP value can be directly adjusted on the Lower Readout in the MAIN Display Mode.
While the Lower Readout shows the control setpoint, step through the following sequence for adjusting the SP value :
1. Press and release UP or DOWN key once. The Lower Readout starts flashing.
2. Use UP/ DOWN keys to adjust the SP value.
3. Press and release ENTER key. The Lower Readout stops flashing and the new set value is registered and stored.
Section 2
User Manual
neuro 102

4
Table 2.1
PV above Max. Range
PV below Min. Range
Message Error Type Cause
Thermocouple / RTD broken
Sensor Open
Under-range
Over-range
CONTROL / ALARM STATUS UNDER PV ERROR CONDITIONS
a) The tuning, if in progress, is aborted.
b) The Profile Cycle, if in progress, enters in HOLD state.
c) Under Over-range or Under-range error condition, all the control outputs are switched off. However, under Sensor Open
error, the PID control output power is maintained at the value set for the parameter “Sensor Break Output Power” on
PAGE-12.
d) For Alarm activation, the under-range condition is treated as minimum PV, whereas the over-range and open conditions
are treated as maximum PV. Thus, Process High, positive Deviation Band and Window Band alarms activate under Over-
range/Open error. Similarly, Process Low, negative Deviation Band and Window Band alarms activate under Under-range
error.
• MANUAL MODE OPERATION
This operation mode is available only if the control action is PID and if the manual mode operation is permitted at
supervisory level. In this mode, the controller operates in Open loop mode wherein the % Output Power is manually
adjusted by the operator. This mode is often used for process start-up to make sure that the process equilibrium is
achieved before the control is transferred for subsequent automatic (closed loop) control. The controller ensures a
bumpless Auto / Manual transfer.
The manual mode can be activated or de-activated using ENTER key. While in manual mode, the Upper Readout shows PV
while the Lower Readout shows % Power that can be adjusted using UP/DOWN keys.
Follow the steps below to enter (Activate) into Manual Mode and to revert to (De-activate) Automatic Mode.
1. Hold ENTER key pressed for approximately 2 seconds until front panel indicator M (Manual Mode) turns on.
2. Release Enter key. The controller is now placed in Manual mode. The Upper Readout displays the PV and the Lower
Readout displays the %Output Power (with the leftmost digit indicating either P (Unidirectional control) or H / C
(Bidirectional control)).
3. Adjust the Output Power using the UP and DOWN keys. Note that in Unidirectional mode, the Output Power is adjustable
between the set Power Low and Power High limits. However, in Bi-directional mode, the Output Power is adjustable from
-100% to +100%.The power range from -100% to 0 is Cool Power (with the leftmost digit indicating C) and 0 to +100% is
Heat Power (with the leftmost digit indicating H).
To de-activate the Manual mode; Hold the ENTER key pressed for approximately 2 seconds until the front panel indicator M
turns off. The controller now enters into Auto control mode with the first power same as that was adjusted last while in Manual
mode.
User Manual
neuro 102

5
Notes:
1. If the Manual mode is activated while a Profile Cycle is in progress; the profile segment (Ramp or Soak) continues to run uninterrupted.
However, the % output power is in accordance with the user set value. The PV, thus may not follow the setpoint profile closely.
2. The Manual mode Activation / De-activation is suppressed while the Tuning is in progress. However, the Tuning procedure can be
activated regardless of whether the controller is in Auto or Manual control mode.
3. The Standby Mode (explained later in this section) over-rides the Manual control mode (if active).
4. If the power fails while the Manual Control Mode is active; upon resumption of power the controller continues to remain in Manual control
mode with the last user set power.
• STANDBY MODE
This mode, allows the operator to put the controller in ‘indication-only’ mode wherein all the output control signals as well as
Alarm Relays are forced OFF. This may be desired prior to the start of a new process batch.
If enabled at supervisory level, the standby mode can be activated or de-activated by setting the parameter ‘Standby’ to Yes
or No respectively. The standby parameter is available on operator page, explained later in the section.
Notes:
1. The Standby and Tuning modes are mutually exclusive. Similarly, if Standby mode is activated while the controller is tuning, the controller
aborts tuning operation and enters Standby mode.
2. If the Power Supply to the controller is switched-off or a Power-failure occurs while the controller is operating in Standby mode; upon
resumption of power, the controller continues to operate in Standby mode.
OPERATOR PAGE AND PARAMETERS
The controller provides a separate page that contains parameters that require frequent settings by the operator. The page is
called Operator Page and the parameters are called Operator Parameters. The availability of operator parameters is
controlled at supervisory level and the parameter setting is not affected by the master lock status.
Accessing Operator Page & Adjusting Parameters
Step through the following sequence to open the operator page and to adjust the operator parameter values.
1. Press and release PAGE key. The Lower Readout shows (PAGE) and Upper Readout shows (0).
2. Press ENTER key. The Lower Readout shows prompt for the first available operator parameter and the Upper Readout
shows value for the parameter.
3. Use UP / DOWN keys to adjust the value and then press ENTER key to store the set value and scroll to next parameter.
The controller automatically reverts to MAIN Display Mode upon scrolling through the last operator parameter. Alternatively,
use PAGE key to return to MAIN Display Mode.
The operator parameters are described in Table 2.2. Note that the parameters presented on operator page depend upon the
functions selected/enabled and supervisory level permissions.
The operator parameter list mainly includes :
a) Profile related commands like Start, Abort, Pause, Skip etc.
b) Standby mode entry / exit.
c) Control Setpoint (SP) value.
d) Alarm-1 Setpoint / Band values.
e) Alarm-2 Setpoint / Band values.
User Manual
neuro 102

6
Table 2.2
PROFILE ABORT COMMAND
These parameters are mutually exclusive. Use start command to
commence a new Profile Cycle and Abort command to abort /
terminate a running Profile cycle. Set the value to ‘Yes’ to issue the
command.
PROFILE START COMMAND
These parameters are mutually exclusive. Use start command to
commence a new Profile Cycle and Abort command to abort /
terminate a running Profile cycle. Set the value to ‘Yes’ to issue the
command.
Parameter Description Settings
(Default Value)
AUXILIARY SETPOINT
The alternate control setpoint that the controller respects for
control purpose when selected through remote input terminals.
This parameter is available only if the hardware Remote Input
module is fitted and if the selected Utility Option is Auxiliary
Setpoint.
No
Yes
(Default : No)
This is the Setpoint value that the controller respects for the
control purpose while it is not running a profile or not in standby /
tuning mode.
CONTROL SETPOINT
No
Yes
(Default : No)
No
Yes
(Default : No)
(Default : -200)
Setpoint Low Limit
to Setpoint High Limit
(Default : -200)
Setpoint Low Limit
to Setpoint High Limit
This parameter is available and applicable only if Standby mode is
enabled at supervisory level. Set the parameter value to ‘Yes’ or
‘No’ for entering and exiting the Standby mode, respectively.
STAND BY MODE
ALARM-1 WINDOW BAND
Same as Alarm-1 Setpoint
ALARM-1 DEVIATION BAND
Same as Alarm-1 Setpoint
ALARM-1 SETPOINT
The setpoint / Band value (depending upon the type of Alarm) for
Alarm-1. This parameter is not available if the selected Alarm type
is ‘None’.
Throughout the range for
the selected Input Type
(Default :
For Process Low :-200
For Process Low :1300)
(Default : 3)
-999 to 999
(Default : 3)
3 to 999
User Manual
neuro 102

7
Parameter Description Settings
(Default Value)
ALARM-2 WINDOW BAND
Same as Alarm-2 Setpoint
ALARM-2 DEVIATION BAND
Same as Alarm-2 Setpoint
ALARM-2 SETPOINT
The setpoint / Band value (depending upon the type of Alarm) for
Alarm-2. This parameter is not available if the selected Alarm type
is ‘None’.
Throughout the range for
the selected Input Type
(Default :
For Process Low : -200
For Process Low : 1300)
(Default : 3)
-999 to 999
(Default : 3)
3 to 999
User Manual
neuro 102

8
The various parameters are arranged in different groups, called PAGES, depending upon the functions they represent. Each
group is assigned a unique numeric value, called PAGE NUMBER, for its access.
The parameters are always presented in a fixed format: The Lower Readout displays the parameter prompt (Identification
Name) and the Upper Readout displays the set value. The parameters appear in the same sequence as listed in their
respective sections.
SET-UP MODE
The Set-up Mode allows the user to view and modify the parameter values. Follow the steps below for setting the parameter
values:
1. Press and release PAGE key. The Lower Readout shows PAGE and the Upper Readout shows page number 0. Refer
Figure 3.1.
2. Use UP / DOWN keys to set the desired PAGE NUMBER.
3. Press and release ENTER key. The Lower Readout shows the prompt for the first parameter listed in the set PAGE and
the Upper Readout shows its current value. If the entered PAGE NUMBER is invalid (contains no parameter list or any
associated function), the controller reverts to the MAIN Display Mode.
4. Press and release the ENTER key until the prompt for the required parameter appears on the Lower Readout. (The last
parameter in the list rolls back to the first parameter).
5. Use UP / DOWN keys to adjust the parameter value. (The display flashes if UP key is pressed after reaching the maximum
value or DOWN key is pressed after reaching the minimum value).
6. Press and release the ENTER key. The new value gets stored in the controller’s non-volatile memory and the next
parameter in the list is displayed.
The Figure 3.1 illustrates the example of altering the value for the parameter ‘Control Output’.
SET-UP MODE : ACCESS AND OPERATION
Figure 3.1
Notes
1. Each page contains a fixed list of parameters that are presented in a pre-determined sequence. Note however that availability of a few
parameters, called Conditional Parameters, depend upon the settings for some other parameters. For example, the parameter ‘Control
Hysteresis’ for Output-1 is available only if, the set value for the parameter ‘Control Action’ is ‘On-Off’.
2. To exit the set-up mode and return to the MAIN Display Mode, press and release PAGE key.
3. If no key is pressed for approximately 30 seconds, the set-up mode times out and reverts to the MAIN Display Mode.
Section 3
Use UP/DOWN
keys to change
the value
Press ENTER
key to store the value &
move to next parameter
First Parameter
on Page-12
New Parameter
value
Next Parameter
on Page-12
or
or
Main Display
Mode
Default Page Page Number
Press PAGE
key to enter
Set-up Mode
Use UP/DOWN
key to set the
Page Number
Press ENTER
key to open
the Page
User Manual
neuro 102

9
MASTER LOCKING
The controller facilitates locking all the PAGES (except Operator PAGE) by applying Master Lock Code. Under Locking, the
parameters are available for view only and cannot be adjusted. The Master Lock, however does not lock the operator
parameters. This feature allows protecting the rather less frequently used parameters against any inadvertent changes while
making the frequently used operator parameters still available for any editing.
For enabling / disabling the Lock, step through the following sequence:
Locking
1. Press and release PAGE key while the controller is in the MAIN Display Mode. The Lower Readout shows PAGE and the
Upper Readout shows 0.
2. Use UP / DOWN keys to set the Page Number to 123 on the Upper Readout.
3. Press and release ENTER key. The controller returns to the MAIN Display Mode with the Lock enabled.
The Figure 3.2 below illustrates the Locking procedure.
Figure 3.2
or
MAIN Display
Mode
Default Page Locking Code MAIN Display
Mode
Press PAGE
key to enter
Set-up Mode
Use UP/DOWN
key to set the
‘Locking Code’
Press ENTER key
to Lock & Return to
Main Mode
UnLocking
Repeat the Locking procedure twice for unlocking.
User Manual
neuro 102

10
The parameters presented on PAGE-10 depend upon the type of algorithm selected for the control purpose, viz., On-Off,
Pulsed On-Off and PID. The parameter list further extends if the selected control mode is bi-directional (that is, heat-cool
control). Refer Table 4.1 for the parameter descriptions and settings.
CONTROL PARAMETERS
Table 4.1
Section 4
0 to 250 Seconds
(Default : 25 sec.)
0 to 1000 Seconds
(Default : 100 sec.)
0 to 999 Units
(Default : 50 units)
Parameter Description Settings
(Default Value)
PROPORTIONAL BAND
(Available for PID Control only)
Sets proportional gain (% power per unit error). Defined in same
units and resolution as that for PV.
INTEGRAL TIME
(Available for PID Control only)
Sets integral time constant in seconds. Setting the value to 0, cuts-
off the integral action.
DERIVATIVE TIME
(Available for PID Control only)
Sets derivative time constant in seconds. Setting the value to 0,
cuts-off the derivative action.
0.5 to 120.0 Seconds
(in steps of 0.5 secs.)
(Default : 20.0 sec.)
CYCLE TIME
(Available for PID Control only)
Sets the total ‘On + Off’ time in seconds for time proportional
power output through OP1 Relay / SSR.
0.1 to 10.0
(Default : 1.0)
RELATIVE COOL GAIN
(Available for PID Control with bi-directional, that is, Heat-Cool
mode)
Sets the ratio of cooling power to the heating power.
COOL CYCLE TIME
(Available for PID Control with bi-directional, that is, Heat-Cool
mode)
Sets the On + Off cycle time in seconds for time proportional
power output through OP2 Relay / SSR.
0.5 to 120.0 Seconds
(in steps of 0.5 secs.)
(Default : 20.0 sec.)
HYSTERESIS
(Available for On-Off or Pulsed On-Off Control only)
Sets differential (dead) band between On-Off switching for OP1.
1 to 999
(Default : 2)
HEAT POWER LOW
(Available for PID Control only)
Sets the minimum % output power limit for OP1.
0 to Power High
(Default : 0)
Visit www.ppiindia.net. Refer technical notes on CONTROL and TUNING for detailed understanding of the
parameters / terminologies used for describing control parameters in this section.

11
Parameter Description Settings
(Default Value)
HEAT POWER HIGH
(Available for PID Control only)
Sets the maximum % output power limit for OP1 .
Power Low to 100
(Default : 100)
COOL POWER LOW
(Available for PID Control with bi-directional, that is, Heat-Cool
mode)
Sets the minimum % output power limit for OP2.
0 to Power High
(Default : 0)
COOL POWER HIGH
(Available for PID Control with bi-directional, that is, Heat-Cool
mode)
Sets the maximum % output power limit for OP2.
Power Low to 100
(Default : 100)
User Manual
neuro 102

12
Visit www.ppiindia.net. Refer technical notes on ALARM for detailed understanding of the parameters/terminologies
used for describing the Alarm parameters in this section.
The parameters required for configuring Alarm-1 and Alarm-2 are grouped on PAGE-11. The configuration includes selecting
the type of Alarm, setting the hysteresis value, enabling / disabling start-up alarm suppression, etc. Refer Table 5.1 for
parameter description & settings.
ALARM PARAMETERS
Table 5.1
Section 5
Parameter Description Settings
(Default Value)
-999 to 999
(Default : 3)
ALARM-1 TYPE
Select the Alarm-1 activation type. Selecting ‘None’ will disable
the alarm and suppress all the related parameters for Alarm-1.
ALARM-1 SETPOINT
(Available for Process High or Process Low Alarm-1 Type)
Sets Alarm limit independent of control setpoint.
ALARM-1 DEVIATION BAND
(Available for Deviation Band Alarm-1 Type)
Sets positive or negative deviation (offset) limit from control
setpoint for High or Low Alarm-1 activation, respectively.
3 to 999
(Default : 3)
ALARM-1 WINDOW BAND
(Available for Window Band Alarm-1 Type)
Sets symmetrical positive and negative deviation (offset) limits
from control setpoint for both High and Low Alarm-1 activation.
1 to 999
(Default : 2)
ALARM-1 HYSTERESIS
Sets differential (dead) band between Alarm-1 switching ON and
OFF states.
(Default : None)
None
Process Low
Process High
Deviation Band
Window Band
End of Profile
Min. to Max. Range
specified for the
selected Input Type
(Default :
For Process Low : -200
For Process Low : 1300)
ALARM-1 LOGIC
Set to Yes to suppress Alarm-1 activation upon power-up or
process start-up. (Default : )Direct
Reverse
Direct
User Manual
neuro 102

13
User Manual
neuro 102
Parameter Description Settings
(Default Value)
-999 to 999
(Default : 3)
ALARM-2 TYPE
Select the Alarm-2 activation type. Selecting ‘None’ will disable
the alarm and suppress all the related parameters for Alarm-2.
ALARM-2 SETPOINT
(Available for Process High or Process Low Alarm-2 Type)
Sets Alarm limit independent of control setpoint.
ALARM-2 DEVIATION BAND
(Available for Deviation Band Alarm-2 Type)
Sets positive or negative deviation (offset) limit from control
setpoint for High or Low Alarm-2 activation, respectively.
3 to 999
(Default : 3)
ALARM-2 WINDOW BAND
(Available for Window Band Alarm-2 Type)
Sets symmetrical positive and negative deviation (offset) limits
from control setpoint for both High and Low Alarm-2 activation.
1 to 999
(Default : 2)
ALARM-2 HYSTERESIS
Sets differential (dead) band between Alarm-2 switching ON and
OFF states.
ALARM-2 INHIBIT
Set to Yes to suppress Alarm-2 activation upon power-up or
process start-up.
ALARM-1 INHIBIT
Set to Yes to suppress Alarm-1 activation upon power-up or
process start-up. (Default : Yes)
No
Yes
(Default : None)
None
Process Low
Process High
Deviation Band
Window Band
End of Profile
Min. to Max. Range
specified for the
selected Input Type
(Default :
For Process Low : -200
For Process Low : 1300)
ALARM-2 LOGIC
(Default : )Direct
Reverse
Direct
Set to Yes to suppress Alarm-2 activation upon power-up or
process start-up.
(Default : Yes)
No
Yes

14
CONFIGURATION PARAMETERS
The controller is provided with a variety of hardware options and software features to cater to a host of applications. The
controller thus needs to be appropriately configured in terms of inputs / outputs and other features like control algorithm, digital
filter etc.
The PAGE-12 presents configuration parameters that are listed below in Table 6.1 .
Table 6.1
Section 6
Parameter Description Settings
(Default Value)
CONTROL OUTPUT (OP1) TYPE
Select the output type in accordance with the hardware
configuration for Output-1 (OP1).
CONTROL LOGIC
Select Reverse (heat logic) or Direct (cool logic).
(Default : Relay)
Relay
SSR
0 - 20mA
4 - 20mA
0 - 5V
0 - 10V
Refer Table 6.2
(Default : 0)
UNITS SELECTION FOR PV
(Available for Thermocouple / RTD Inputs)
Selects temperature measurement units in °C or °F.
RESOLUTION FOR PV
(Not Available for Thermocouple Inputs)
Sets the process value indication resolution (decimal point). All
the resolution based parameters (control setpoint, hysteresis,
alarm setpoints etc.) then follow this resolution setting.
PV RANGE LOW
(Available for DC Linear Inputs)
Sets process value corresponding to minimum DC Linear signal
input (e.g., 0V, 0mA, 4mA, etc.)
Refer Table 6.2
(Default : 1)
INPUT TYPE
Select Input type in accordance with the type of Thermocouple or
RTD, sensor or transducer output connected for process value
measurement. Ensure proper hardware jumper settings, if
required.
Refer Table 6.2
(Default : Type K)
(Default : C)°
°F
°C
(Default : Reverse)
Reverse
Direct
Refer Table 6.2
(Default : 1000)
PV RANGE HIGH
(Available for DC Linear Inputs)
Sets process value corresponding to maximum DC Linear signal
input (e.g., 5V, 10V, 20mA, etc.)
User Manual
neuro 102

15
Parameter Description Settings
(Default Value)
SETPOINT LOW LIMIT
Sets minimum permissible control setpoint value.
(Default : -200)
Min. Range to
Setpoint High for the
selected Input Type
OFFSET FOR PV
This value is algebraically added to the measured PV to derive the
final PV that is displayed and compared for alarm / control.
Final PV = Measured PV + Offset
-1999 to 9999
(Default : 0)
0.5 to 25.0 Seconds
(in steps of 0.5 Seconds)
(Default : 1.0 sec.)
SENSOR BREAK OUTPUT POWER
(Available for PID control only)
In case of Thermocouple / RTD broken or disconnected, the
controller outputs this power value under open loop condition.
-100 to 100
(Default : 0.0)
DIGITAL FILTER FOR PV
Sets the time constant, in seconds, for the low-pass digital filter
applied to the measured PV. The filter helps smoothing/averaging
the signal input and removing the undesired noise.
SETPOINT HIGH LIMIT
Sets maximum permissible control setpoint value.
Setpoint Low to
Max. Range for the
selected Input Type
(Default : 1300)
SENSOR BREAK (OPEN) STRATEGY
This parameter allows the user to decide the level at which the PV
is required to be maintained upon detecting the sensor break
(open) condition while the controller is operating in Auto or Profile
mode.
Sensor Break
Output Power
Hold
(Default : Sensor Break
Output Power)
User Manual
neuro 102

16
Table 6.2
Resolution
Option What it means Range (Min. to Max.)
Type J Thermocouple
Type K Thermocouple
Type T Thermocouple
0 to +960°C / +32 to +1760°F
-200 to +1376°C / -328 to +2508°F
-200 to +385°C / -328 to +725°F
Type R Thermocouple
0 to +1770°C / +32 to +3218°F
Fixed
1°C / 1°F
0 to 20mA DC current
4 to 20mA DC current
0 to 50mV DC voltage
0 to 200mV DC voltage
0 to 1.25V DC voltage
0 to 5.0V DC voltage
0 to 10.0V DC voltage
1 to 5.0V DC voltage
3-wire, RTD Pt100
-1999 to +9999 units
-199 to +600°C / -328 to +1112°F
-199.9 to 600.0°C / -199.9 to 999.9°F
or
User settable
1°C / 1°F
or
0.1°C / 0.1°F
User settable
1 / 0.1 / 0.01/
0.001 units
Type N Thermocouple
Type B Thermocouple
Type S Thermocouple
0 to +1300°C / +32 to +2372°F
0 to +1825°C / +32 to +3092°F
0 to +1765°C / +32 to +3209°F
Reserved for customer specific Thermocouple type not listed
above. The type shall be specified in accordance with the ordered
(optional on request) Thermocouple type.
User Manual
neuro 102

17
SUPERVISORY PARAMETERS
The supervisory level responsibilities include exercising control over operator, making process related decisions and
controlling the availability of process data for remote use. The PAGE-13 parameters allow implementation supervisory level
decisions. The Table 7.1 below list supervisory parameters.
Table 7.1
Section 7
Settings
(Default Value)
SELF-TUNE COMMAND
(Available for PID control only)
Set to ‘Yes’ to initiate a new tuning cycle or set to ‘No’ to abort a
tuning operation in progress.
Parameter Description
OVERSHOOT INHIBIT
(Available for PID control only)
Enabling this feature controls the PV rise or fall upon process
start-up in order to reach the control setpoint with as minimum
overshoot as possible.
1.0 to 2.0
(Default : 1.2)
OVERSHOOT INHIBIT FACTOR
(Available for PID control with Overshoot Inhibit enabled )
This parameter adjusts the effectiveness of the Overshoot Inhibit
feature. Increase the value if the overshoot is curbed but the PV
takes longer to reach the SP. Decreases the value if the overshoot
persists.
(Default : Disable)
Disable
Enable
(Default : No)
No
Yes
MANUAL(HAND) MODE
Supervisory permission for Manual mode operation. Set to
‘Enable’ for permission.
SP ADJUSTMENT ON OPERATOR PAGE
Supervisory permission for control setpoint editing on Operator
Page. Set to ‘Enable’ for permission.
SP ADJUSTMENT ON LOWER READOUT
Supervisory permission for control setpoint editing on Lower
Readout. Set to ‘Enable’ for permission.
ALARM SP ADJUSTMENT
ON OPERATOR PAGE
Supervisory permission for Alarm setpoint adjustments on
Operator Page. Set to ‘Enable’ for permission.
STANDBY MODE
Supervisory control over availability of Standby (entry / exit)
command on Operator Page. ‘Enable’ for availability.
(Default : Enable)
Disable
Enable
(Default : Disable)
Disable
Enable
(Default : Disable)
Disable
Enable
(Default : Disable)
Disable
Enable
(Default : Enable)
Disable
Enable
User Manual
neuro 102

18
Settings
(Default Value)
Parameter Description
PROFILE ABORT COMMAND
ON OPERATOR PAGE
Supervisory control over availability of Profile Abort command on
Operator Page. ‘Enable’ for availability. (Default : Disable)
Disable
Enable
AUXILIARY SETPOINT OR SERIAL
COMM.OPTION SELECTION
This parameter allows the user to configure the controller in either
Auxiliary Setpoint or Serial Communication mode options. When
the ‘Auxiliary Setpoint’ option is selected, the controller treats the
Auxiliary Setpoint (ASP) same as control (main) Setpoint (SP) and
attempts to maintain PV at the Auxiliary Setpoint upon detecting
the potential free contact closure of external switch/Relay or a
TTL-compatial voltage level below 0.5 Volts by the Hardware
module.
When the ‘Serial Communication’ option is selected, the Following
param ete rs ar e ava ila ble a nd ap pli cable fo r Ser ial
Communication Function if the respective hardware module is
fitted.
BAUD RATE
Communication speed in ‘Bits per Second’. Set the value to match
with the host baud rate.
CONTROLLER ID NUMBER
Unique numeric code assigned to the controller for identification
by the host. Set the value as required by the host.
COMMUNICATION WRITE ENABLE
Setting to ‘No’ disallows the host to set or modify any parameter
value. The value however can be read by the host.
1 to 127
(Default : 1)
(Default : 9.6)
(Default : None)
None
Auxiliary
Setpoint
Serial Comm.
(Default : No)
No
Yes
4800
9600
1200
2400
User Manual
neuro 102
Table of contents
Other PPI Controllers manuals

PPI
PPI Epsilon 48 User manual

PPI
PPI neuro 102L Plus User manual

PPI
PPI neuro 105 User manual

PPI
PPI HumiTherm-c Series User manual

PPI
PPI neuro 202 User manual

PPI
PPI Clavex Pro User manual

PPI
PPI HumiTherm Plus User manual

PPI
PPI Zenex Plus User manual

PPI
PPI neuro 105 User manual

PPI
PPI claveX Series User manual
Popular Controllers manuals by other brands

ENDA
ENDA EUC942 manual

Morningstar
Morningstar ProStar MPPT Series quick start guide

IFM Electronic
IFM Electronic Ecomat 100 ecomatmobile SmartController... System manual

SIMON RWA
SIMON RWA EA-KN-20-XS Manual for installation and use

HERSILL
HERSILL OXYMO P15 Directions for use

Gamma Vacuum
Gamma Vacuum SPCe instruction manual