Thank you for your purchase of the
PD6300 rate/totalizer.
describe some of the common setup
procedures for this meter.
This guide includes:
Basic Wiring for Meter..............
Program Pulse Input and Totalizer.......
Program Relays for Automatic Reset...
Program 4-20 mAAnalog Output.........
Return Meter to Factory Defaults.........
For additional information about the
PD6300rate/totalizernotcovered
in this quick start guide, please consult
the instruction manual included on the
CD or available at www.predig.com.
Menu Button – Use this button to
access Programming Mode and to
return to Run Mode.
Note: If you think you have made a mistake while
programming the meter, use this button to
return the meter to Run Mode without saving.
Right/F1 Button – Use this button to
change the selected digit while input-
ting a numeric value in Programming Mode.
Up/F2 Button – Use this button to
increment the selected digit while
inputting a numeric value in Programming
Mode.
Enter/F3 Button – Use this button to
access or accept a menu item while
in Programming Mode.
2
3
4
6
7
8
P
R
V
U
S
ERIES
®
233 South Street
Hopkinton MA 01748-2208 USA
Tel. (508) 655-7300 www.predig.com
MeterView Pro
USB Install
PD6300 Pulse Input Rate/Totalizer
Quick Start Guide

2
PD6300 Rate/Totalizer Quick Start Guide
onboard USB. The meter is powered by the USB connection, so there is no need to wire
anything prior to programming the meter.
®Pro
Connect the provided USB cable to the
meter and the computer as shown. The
computer will automatically install the driver
software it needs to talk to the meter.
Note: Only one meter may be connected at a time.
with the meter software.
Once the driver is installed, anAutoPlay dialog
should appear for the drive “MAINSTAL.” Click
If the computer does not display anAutoPlay
dialog for the drive “MAINSTAL,” you should
open My Computer and double-click on the
drive labeled “MAINSTAL.”
The program will open a few windows and
install two programs on your computer. Simply
follow the onscreen instructions until you see
one of the dialogs in step 4.
Note: If you receive a User Account Control
warning, click “Yes.”
If there is an update available, click the
“Update” button to install the new version.
-
ming your meter.
Note:-
ware, you will be asked if you want to update
This way, you will always have the most cur-
rent version on the meter for future installs.
Note:
1 2
34

3
-
nectors. Connect your wires to the provided connectors and plug into the meter as indicated.
Basic Wiring for Meter
4-20 mA Output Wiring1
Relay Connections2
AC and DC
Loads Protection
Loads Protection
F4 Digital Input Connection
1
2
Consult the PD6300 instruction
manual located on the included CD
or available online at www.predig.com
for additional wiring diagrams.
Pulse Input Wiring
power supply.
power supply.
Wiring for a self-powered magnetic pickup coil
Active
Passive
12-35 VDC
Power
Supply
+
4-20 mA
Input Meter
-+
RI- I+ 13 2
RELAY1
3 2 1
24 V
-
4-20 mA Input
Remote Display,
Chart Recorder, Etc.
-
+
RI- I+
MA OUT
13 2
RELAY1
3 2 1
24 V
MA OUT
C NONO NC NC C
RELAY4 RELAY3
4 36 5 2 1
C NONO NC NC C
RELAY2 RELAY1
4 36 5 2 1
C
R
C
R
P- COMP+ V+ mA+
3 41 2 5
F4
6
AC or DC
POWER
Required External Fuse:
5 A max, 250 V Slow Blow
POWER
+-
Flowmeter
(Pulse Output)
P- COMP+ S+ S-
3 41 2 5
F4 6
mV PNP NPN
SWITCH
INPUT SIGNAL
External
Power
Supply
Flowmeter
(Pulse Output)
+
-
P- COMP+ S+ S-
3 41 2 5
F4 6
INPUT SIGNAL
mV PNP NPN
SWITCH
Flowmeter
(Magnetic
Pickup Coil)
P- COMP+ S+ S-
3 41 2 5
F4 6
INPUT SIGNAL
mV PNP NPN
SWITCH
PD6300 Rate/Totalizer Quick Start Guide

4
Program Pulse Input and Totalizer
Program the
For example:
it will transmit 210 pulses, then you should enter the value 210.000 at the FActor
setup procedure.
Note: K-Factors are almost always given in U.S. gallons. Make certain that you take the unit of measure used
Press to
enter Programming
Mode, press to
access the SEtup
Press to dis-
play the
dec pt (Decimal
to access.
Press until the
desired decimal
point location is dis-
played and press to accept. Continue to
press to assign the decimal point loca-
tion to the subsequent parameters.
Press to select
the parameter for
which you want to
assign the decimal point and press .
On the Programming tab,
under Input Calibration, select
-
Select the desired decimal
point location for Rate,
Total and Grand Total.
Click the Send
Meter Data button
to send your programmed settings to the
meter.
Under Totalizer
Options, select the
appropriate time base
for your rate measurement (such as gallons
per second
Select whether the
total should reset
automatically or
manually. If Auto is selected, use the Time
Delay
To-
tal Conv. Factor, you
may enter a multiplier by which the rate will
be factored before being added to the total.
1 2
6
3 4
5
1 2
34
PD6300 Rate/Totalizer Quick Start Guide

5
Press to ac-
cess t tb (Total
Note: The time base for rate can be in units per
second, per minute, per hour, or per day.
Press to select
the appropriate time
base and press
to accept.
Press to ac-
cess t CF (Total
Note: The conversion factor for total calculation is
the number by which the rate will be multiplied
before being added to the total.
Press until the
desired decimal
point location for
the conversion factor is displayed and press
to accept.
Use to change
which digit is
selected and to
increment the digit. Press when done.
Note: Aconversion factor of 1.0 disables this feature.
Press to ac-
cess the t rSt
Note: This menu allows you to set automatic or
manual total reset. If you would like to be able
to reset the total using one of the function keys
then this must be set to nmAn
Press to
select either nmAn
Auto
to accept. Press
to return the meter to Run Mode.
Note: If Auto
menu will be displayed: t dLy
which is the delay time before the total is re-
set. Arelay assigned to total will reset the total
value once its set point has been reached.
Use to change
which digit is
selected and
to increment the selected digit. Press
when done.
Press to
access the ProG
Press to ac-
cess the FActor
This is where you will enter the K-Factor
Press to ac-
cess the InCAL
menu.
Press until the
desired decimal
point location for
your K-Factor is displayed and press .
Note: Time base, conversion factor and reset may
also be set for the grand total. These menus
are Gt tb, Gt CF, and Gt rSt and are ac-
cessible directly following the total menus.
10
11 12
13 14
15 16
9
5
87
6
PD6300 Rate/Totalizer Quick Start Guide

6
Program Relays for Automatic Reset
Program the
relays at reset points.
Note: Only relays assigned to rateset point is higher than
the reset point, the relay will be a high alarm. If the set point is than the reset point, the
relay will be a .
Press to
enter Programming
Mode, press to
access the SEtup
Press until
the relay
menu is displayed
and then press to access.
Press until the
appropriate relay
number is displayed
(rly 1-8press to access.
Press to accept
Auto (Automatic
Press to access
the Act (Relay Ac-
Press to access
the ASSiGn (Relay
Press until the
relay number you
wish to assign a
parameter to is displayed (ASiGn 1-8
then press to access.
Press until the
appropriate param-
eter (i.e. rate, total,
and then press
to accept. Continue to assign additional
relays to subsequent parameters.
Select “Auto” from the
Action drop down list.
Note: See PD2-6200
Instruction Manual
for details on addi-
tional relay actions.
Enter the set and
reset point values in
Click the Send Me-
ter Data button to send your programmed
settings to the meter.
On the Relays tab, in
the desired relay sec-
tion, assign the relay
to a desired parameter
(i.e. rate, total, grand total, or Modbus®
2
3 4
1
1 2
6
8
7
3 4
5
PD6300 Rate/Totalizer Quick Start Guide

7
Press to access
the rst (Relay Re-
Note: The reset menu will only be displayed is the
relay has been assigned to rate
totalGtotal
relays do not have reset points.
Use to change
which digit is
selected and
to increment the selected digit. Press
when done to accept the new set point
value. Press to return to Run Mode.
Note: If you need to program more relays, simply repeat steps 6-12 for each additional relay. Up to
meter. Consult the PD6300 Instruction
Manual for information on additional relay action types.
Press to access
the set (Relay Set
Use to change
which digit is
selected and to
increment the digit. Press when done.
Program 4-20 mA Analog Output
Program the meter to output an analog signal based on its display value. This signal
is commonly output to a PLC or chart recorder.
Note: By default, the analog output will transmit the rate value as it is displayed on the meter. It is pos-
sible to output the total, grand total or some other value. Please refer to the steps on the following
page for information on setting the output source.
On the Setup tab,
under Analog Out
Scale, enter your
Click the Send
Meter Data button to send your programmed
settings to the meter.
12
Press to
enter Programming
Mode, press to
access the SEtup
Press until the
aout
menu is displayed
and then press to access.
Press to access
the dis 1 (Display
This is the
display value at which the low range of the
output will be transmitted.
Use to change
which digit is
selected and
to increment the selected digit. Press
when done to accept the new display value.
11 12
10
9
1 2
3 4
PD6300 Rate/Totalizer Quick Start Guide

LIM6300QS_B - 10/158
Press to access
the Out 1 (Output
This is the
output signal which represents diS 1.
The default value of
04.000
for most applications. Press to accept.
Press to access
the dis 1 (Display
This is the
display value at which the high range of the
output will be transmitted.
Use to change
which digit is
selected and
to increment the selected digit. Press
when done to accept the new display value.
Press to access
the Out 2 (Output
This is the
output signal which represents diS 2.
The default value of
20.000
for most applications. Press to accept.
Press to return to Run Mode.
Return Meter to Factory Defaults
If a mistake has been made while programming the meter and it is unclear where the error
occurred, the best option may be to perform a factory reset of the meter and begin again.
These steps show how to perform a factory reset of the meter.
On the Advanced Features
tab, in the bottom left-hand corner, click the
Reset Meter Factory Defaults button.
-
dow that appears, click
OK. The meter will reset to factory defaults.
12
Press and hold
enter the Advanced
Features Menu.
Press until the
diAG
menu is displayed.
Press and hold
until the meter
rESEt
to reset the
meter to factory defaults.
The meter will
segments and then
display ProcES
been reset to its defaults.
5
7
6
8
9 10
1 2
3 4
PD6300 Rate/Totalizer Quick Start Guide
Other manuals for PROVU Series
2
This manual suits for next models
1
Table of contents
Other Precision Digital Corporation Cash Counter manuals

Precision Digital Corporation
Precision Digital Corporation PD6363 Series User manual

Precision Digital Corporation
Precision Digital Corporation PROVU PD6300 Series User manual

Precision Digital Corporation
Precision Digital Corporation PD6820 User manual

Precision Digital Corporation
Precision Digital Corporation Vantageview PD6720 User manual

Precision Digital Corporation
Precision Digital Corporation PD6820 User manual