Presys DMY-2030-CC User manual

Digital Indicator
for Load Cell DMY-2030-CC
EM0359-00
®
Technical Manual
Q
Y
U
T
A
L
I
E
N
T
M
S
E
Y
G
S
A
T
N
E
A
M
M
presys
presys
Digital Indicator
presys
Digital Indicator
for Load Cell
presys
for Load Cell
presys
presys
presys
presys

CAUTION!
In case of failure, the instrument can present an AC voltage level in its metal box,
which for safety reasons must always be connected to an effective ground point. To
this end a suitable terminal is provided on the back of the box identified as GND. Never
connect this terminal to the neutral terminal of power supply.
It is recommended the use of an external fuse (2 A) on the power input of the
instrument. There is an internal fuse.
Operation of relays - Important Note!
When the instrument has relay module for alarm or control, you must follow the
instructions in this manual in the maintenance section on the snubber use.
The snubber is a protection against noise coming from the opening / closing of
the relay contacts, but depending on the application may be necessary to remove this
snubber!
CAUTION!
The instrument described in this manual is a device for use in specialized
technical area. The user is responsible for the configuration and selection of values for
the instrument parameters. The manufacturer warns of the risks of occurrences with
damage to both the person and the property resulting from the incorrect use of the
instrument. The information and specifications in this manual are subject to change
without previous notice.
The warranty conditions are available in our sites:
www.presys.com.br/warranty
presys
In case of failure, the instrument can present an AC voltage level in its metal box,
presys
In case of failure, the instrument can present an AC voltage level in its metal box,
which for safety reasons must always be connected to an effective ground point. To
presys
which for safety reasons must always be connected to an effective ground point. To
this end a suitable terminal is provided on the back of the box identified as GND. Never
presys
this end a suitable terminal is provided on the back of the box identified as GND. Never
It is recommended the use of an external fuse (2 A) on the power input of the
presys
It is recommended the use of an external fuse (2 A) on the power input of the
Operation of relays - Important Note!
presys
Operation of relays - Important Note!
When the instrument has relay module for alarm or control, you must follow the
presys
When the instrument has relay module for alarm or control, you must follow the
instructions in this manual in the maintenance section on the snubber use.
presys
instructions in this manual in the maintenance section on the snubber use.
The snubber is a protection against noise coming from the opening / closing of
presys
The snubber is a protection against noise coming from the opening / closing of
the relay contacts, but depending on the application may be necessary to remove this
presys
the relay contacts, but depending on the application may be necessary to remove this
CAUTION!
presys
CAUTION!
The instrument described in this manual is a device for use in specialized
presys
The instrument described in this manual is a device for use in specialized
technical area. The user is responsible for the configuration and selection of values for
presys
technical area. The user is responsible for the configuration and selection of values for
the instrument parameters. The manufacturer warns of the risks of occurrences with
presys
the instrument parameters. The manufacturer warns of the risks of occurrences with
damage to both the person and the property resulting from the incorrect use of the
presys
damage to both the person and the property resulting from the incorrect use of the
instrument. The information and specifications in this manual are subject to change
presys
instrument. The information and specifications in this manual are subject to change
without previous notice.
presys
without previous notice.
The warranty conditions are available in our sites:
presys
The warranty conditions are available in our sites:
presys
presys
presys
www.presys.com.br/warranty
presys
www.presys.com.br/warranty
presys
presys
presys

PRESYS Instruments DMY-2030-CC
EM0359-00
TABLE OF CONTENTS
1.0 - Introduction ............................................................................................................1
1.1 - Description............................................................................................................1
1.2 - Order Code...........................................................................................................2
1.3 - Technical Specifications........................................................................................3
2.0 - Installation ..............................................................................................................5
2.1 - Mechanical Installation..........................................................................................5
2.2 - Electrical Installation .............................................................................................5
2.3 - Input Signal Connection........................................................................................6
2.3.1 - Millivolt Input ......................................................................................................7
2.4 - Output Signal Connection.....................................................................................7
2.5 - Connection Diagram .............................................................................................9
2.6 - Communication...................................................................................................10
2.7 - Engineering Units................................................................................................10
3.0 - Operation ..............................................................................................................11
3.1 - Normal operation ................................................................................................11
3.2 - Configuration.......................................................................................................13
4.0 - Maintenance..........................................................................................................23
4.1 - Indicator Hardware..............................................................................................23
4.2 - Snubber Use for Relay........................................................................................24
4.3 - Installation of Optional Modules..........................................................................25
4.4 - Calibration...........................................................................................................27
4.5 - Hardware Maintenance Instructions....................................................................29
presys
............................................................................................................
presys
............................................................................................................
............................................................................................................
presys
............................................................................................................
1
presys
1
...........................................................................................................
presys
...........................................................................................................
2
presys
2
........................................................................................
presys
........................................................................................
3
presys
3
..............................................................................................................
presys
..............................................................................................................
5
presys
5
..........................................................................................
presys
..........................................................................................
.............................................................................................
presys
.............................................................................................
........................................................................................
presys
........................................................................................
......................................................................................................
presys
......................................................................................................
.....................................................................................
presys
.....................................................................................
.............................................................................................
presys
.............................................................................................
...................................................................................................
presys
...................................................................................................
................................................................................................
presys
................................................................................................
..............................................................................................................
presys
..............................................................................................................
3.1 - Normal operation
presys
3.1 - Normal operation
................................................................................................
presys
................................................................................................
3.2 - Configuration
presys
3.2 - Configuration
.......................................................................................................
presys
.......................................................................................................
4.0 - Maintenance
presys
4.0 - Maintenance
..........................................................................................................
presys
..........................................................................................................
4.1 - Indicator Hardware
presys
4.1 - Indicator Hardware
..............................................................................................
presys
..............................................................................................
4.2 - Snubber Use for Relay
presys
4.2 - Snubber Use for Relay
........................................................................................
presys
........................................................................................
4.3 - Installation of Optional Modules
presys
4.3 - Installation of Optional Modules
4.4 - Calibration
presys
4.4 - Calibration
...........................................................................................................
presys
...........................................................................................................
4.5 - Hardware Maintenance Instructions
presys
4.5 - Hardware Maintenance Instructions

PRESYS Instruments DMY-2030-CC
Introduction
Page 1
1.0 - Introduction
1.1 - Description
The DMY-2030-CC Indicator monitors one input of mVdc signal,within the range
from -30 mV to +30 mV, provided by a load cell.A 10Vdc voltage source,isolated from
the output and with short-circuit protection,is provided to power the load cell.
It can communicate with computers by means of an optional communication
module RS-232 or RS-422/485.
All configuration data is protected by password and is stored in a non-volatile
memory.
According to its modularity design concept, the Indicator accepts up to three
output modules. One can make use of one retransmitter output (4-20mA, 1-5V, 0-10V) or
one SPST alarm module and up to two SPDT alarm modules (also solid state relay or
open collector voltage). The alarm outputs can be configured independently to operate
with latch, what requires the acknowledgement of the operator, by means of the front
panel Keys, in order to deactivate the outputs after the process variable returns to normal
condition. The outputs are electrically isolated from inputs.
Fig. 1 - DMY-2030-CC Indicator front panel
The front panel has a high visibility display configurable up to 4 ½ digits to show
the process variable. The leds are used as a visual indication of alarms. During
configuration, the display shows mnemonics and parameter values.
It accepts 75 to 264Vac or 100 to 360Vdc (with any polarity) power supply.
The instrument has extruded aluminum case which avoids electrical noise,
electromagnetic interference, radiofrequency interference, etc., and its robust
construction makes it tough enough for the most hostile environment.
presys
within the range
presys
within the range
A 10Vdc voltage source
presys
A 10Vdc voltage source
,
presys
,
isolated from
presys
isolated from
is provided to power the load cell.
presys
is provided to power the load cell.
It can communicate with computers by means of an optional communication
presys
It can communicate with computers by means of an optional communication
All configuration data is protected by password and is stored in
presys
All configuration data is protected by password and is stored in
a non
presys
a non
-volatile
presys
-volatile
According to its modularity design concept, the Indicator accepts up to three
presys
According to its modularity design concept, the Indicator accepts up to three
output modules. One can make use of one retransmitter output
presys
output modules. One can make use of one retransmitter output
(4
presys
(4
-20mA, 1-5V, 0-10V) or
presys
-20mA, 1-5V, 0-10V) or
one SPST alarm module and up to two SPDT alarm modules (also solid state relay or
presys
one SPST alarm module and up to two SPDT alarm modules (also solid state relay or
open collector voltage). The alarm outputs can be configured independently to operate
presys
open collector voltage). The alarm outputs can be configured independently to operate
with latch, what requires the acknowledgement of the operator, by means of the front
presys
with latch, what requires the acknowledgement of the operator, by means of the front
Keys, in order to deactivate the outputs after the process variable returns to normal
presys
Keys, in order to deactivate the outputs after the process variable returns to normal
condition. The outputs are electrically isolated from inputs.
presys
condition. The outputs are electrically isolated from inputs.
presys
Fig. 1
presys
Fig. 1
- DMY-
presys
- DMY-
2030
presys
2030
-
presys
-
CC
presys
CC
The front panel has a high visibility display configurable up to 4 ½ digits to show
presys
The front panel has a high visibility display configurable up to 4 ½ digits to show
the process variable. The leds are used as a visual indication of alarms. During
presys
the process variable. The leds are used as a visual indication of alarms. During
configuration, the display shows mnemonics and parameter values.
presys
configuration, the display shows mnemonics and parameter values.
It accepts 75 to 264Vac or 100 to 360Vdc (with any polarity) power supply.
presys
It accepts 75 to 264Vac or 100 to 360Vdc (with any polarity) power supply.
The instrument has extruded aluminum case which avoids electrical noise,
presys
The instrument has extruded aluminum case which avoids electrical noise,
electromagnetic interference, radiofrequency interference, etc., and its robust
presys
electromagnetic interference, radiofrequency interference, etc., and its robust
construction makes it tough enough for the most hostile environment.
presys
construction makes it tough enough for the most hostile environment.

PRESYS Instruments DMY-2030-CC
Introduction
Page 2
1.2 - Order Code
DMY -2030 -CC
-
-
-
-
-
-
A
B
C
D
E
F
Field A
Output 1
0
Notused
1
4to 20 mA
2
1to 5 V
3
0to 10 V
4
SPST Relay
5
Open collector voltage
6
Solid state relay
Field B
Output 2
0
Notused
1
SPDT Relay
2
Open collector voltage
3
Solid state relay
Field C
Output 3
Same code of Output 2
Field D
Power Supply
1
75 to 264 Vac50/60Hz or 100 to 360 Vdc (any polarity)
2
24 Vdc
3
12 Vdc
4
Others,under consult
Field ECommunication
0
Not used
1
RS-232
2
RS-485
3
RS-422
Field F
Case Protection Grade
0
General usage, protected place
1
Front aspersion-proof
2
Weather-proof
Note 1- The input type, indication and relay usage as alarms are, among other
things, items that the user can program through the front keys (if wanted, specify these
information so that all the configuration can be made by PRESYS).
presys
F
presys
F
presys
Open collector voltage
presys
Open collector voltage
Solid state relay
presys
Solid state relay
Output
presys
Output
3
presys
3
Same code
presys
Same code
of Output
presys
of Output
2
presys
2
Power Supply
presys
Power Supply
75
presys
75
to
presys
to
264 Va
presys
264 Va
c
presys
c
50/60Hz o
presys
50/60Hz o
r 100 to
presys
r 100 to
24 V
presys
24 V
d
presys
d
c
presys
c
3
presys
3
12 V
presys
12 V
dc
presys
dc
4
presys
4
Others
presys
Others
,
presys
,
under consult
presys
under consult
Field
presys
Field
E
presys
E
Co
presys
Co
m
presys
m
munica
presys
munica
tion
presys
tion
0
presys
0
N
presys
N
ot used
presys
ot used
1
presys
1
RS
presys
RS
-
presys
-
232
presys
232
2
presys
2
RS
presys
RS
-
presys
-
485
presys
485
3
presys
3
RS
presys
RS
-
presys
-
422
presys
422
Field
presys
Field
F
presys
F
Case Protection Grade
presys
Case Protection Grade
0
presys
0
1
presys
1
2
presys
2
1
presys
1

PRESYS Instruments DMY-2030-CC
Introduction
Page 3
Note 2 - Other hardware and software features can be available under previous
consult.
Code Example:
1) DMY-2030-CC - 0 - 1 - 0 - 1 - 0 - 0
This code defines a DMY-2030-CC indicator with one SPDT relay which can be
used as a high, low or deviation alarm, 75 to 264Vac or 100 to 360Vdc power supply,
protected field usage.
1.3 - Technical Specifications
Input: One input for -30 to +30 mVdc.Input impedance of 10 M.
Outputs:
One 4 to 20mA, 1 to 5Vdc or 0 to 10Vdc analog retransmitter optional module
galvanically isolated up to 300Vac from power supply and input.
Alarm with a SPST relay rated for 3A at 220Vac.It is possible to use one
optional alarm module by replacing the retransmitter output.
Alarms with SPDT relays rated for 3A at 220Vac.It is possible to use up to 2
optional alarm modules.
Logic signal, open collector transistor, 24Vdc, 40mA max. with isolation.
Solid state relay rated for 2A at 250Vac with isolation.
10Vdc voltage source module to power the load cell.
Load cell voltage source:
10 Vdc/100 mA maximum, isolated from outputs, with short-circuit protection.
Serial Communication:
RS-232 or RS-485, with 50Vdc isolation, as an optional module connected to the
CPU board. MODBUS®- RTU Communication Protocol.
Indication:
Standard indication within the -9999 to 19999 range.
Configuration:
By front panel push-buttons and internal jumpers (for outputs).
Sampling rate:
64ms sampling rate, for the indication of input in -9999 to 19999 range. The
display is updated each 0.2 second.
Accuracy:
0.1% of full scale for the mV input.
0.5% of full scale for analog retransmitter output and 750maximum load.
Thermal stability:
0.005% / C of span with reference of 25C ambient temperature.
Power supply:
Universal 75 to 264Vac or 100 to 360Vdc (any polarity), 10W nominal; 24Vdc,
12Vdc and other values are optional.
presys
-CC indicator with one SPDT relay which can be
presys
-CC indicator with one SPDT relay which can be
used as a high, low or deviation alarm, 75 to 264Vac or 100 to 360Vdc power supply
presys
used as a high, low or deviation alarm, 75 to 264Vac or 100 to 360Vdc power supply
Input impedance of
presys
Input impedance of
10
presys
10
M
presys
M
presys
.
presys
.
One 4 to 20mA, 1 to 5Vdc or 0 to 10Vdc analog retransmitter optional module
presys
One 4 to 20mA, 1 to 5Vdc or 0 to 10Vdc analog retransmitter optional module
galvanically isolated up to 300Vac from power supply and input.
presys
galvanically isolated up to 300Vac from power supply and input.
Alarm with a SPST relay rated for 3A at 220Vac
presys
Alarm with a SPST relay rated for 3A at 220Vac
.
presys
.
It is possible to use one
presys
It is possible to use one
optional alarm module by replacing the retransmitter output.
presys
optional alarm module by replacing the retransmitter output.
Alarms with SPDT relays rated for 3A at 220Vac
presys
Alarms with SPDT relays rated for 3A at 220Vac
.
presys
.
It is possible to use up to 2
presys
It is possible to use up to 2
optional alarm modules.
presys
optional alarm modules.
Logic signal, open collector transistor, 24Vdc, 40mA max. with isolation.
presys
Logic signal, open collector transistor, 24Vdc, 40mA max. with isolation.
Solid state relay rated for 2A at 250Vac with isolation.
presys
Solid state relay rated for 2A at 250Vac with isolation.
10Vdc voltage source module to power the load cell.
presys
10Vdc voltage source module to power the load cell.
Load cell voltage source:
presys
Load cell voltage source:
Vdc/100 mA maximum, isolated from outputs, with short-circuit protection.
presys
Vdc/100 mA maximum, isolated from outputs, with short-circuit protection.
Serial Communication:
presys
Serial Communication:
-232 or RS-485, with 50Vdc isolation, as an optional module connected to the
presys
-232 or RS-485, with 50Vdc isolation, as an optional module connected to the
CPU board. MODBUS
presys
CPU board. MODBUS
®
presys
®
- RTU Communication Protocol.
presys
- RTU Communication Protocol.
®- RTU Communication Protocol.
®
presys
®- RTU Communication Protocol.
®
ication:
presys
ication:
Standard indication within the -9999 to 19999 range.
presys
Standard indication within the -9999 to 19999 range.
Configuration:
presys
Configuration:
By front panel push-buttons and internal jumpers (for outputs).
presys
By front panel push-buttons and internal jumpers (for outputs).
Sampling rate:
presys
Sampling rate:
64ms sampling rate, for the indication of input in -9999 to 19999 range. The
presys
64ms sampling rate, for the indication of input in -9999 to 19999 range. The
display is updated each 0.2 second.
presys
display is updated each 0.2 second.
Accuracy:
presys
Accuracy:
presys
0.1% of full scale for the mV input.
presys
0.1% of full scale for the mV input.
presys
presys
0.5% of full scale for analog retransmitter output and 750
presys
0.5% of full scale for analog retransmitter output and 750
Thermal stability:
presys
Thermal stability:
presys
presys
0.005% /
presys
0.005% /
Power supply:
presys
Power supply:
Universal 75 to 264Vac or 100 to 360Vdc (any polarity), 10W nominal; 24Vdc,
presys
Universal 75 to 264Vac or 100 to 360Vdc (any polarity), 10W nominal; 24Vdc,

PRESYS Instruments DMY-2030-CC
Introduction
Page 4
Operating Ambient:
0 to 50C temperature and 90% maximum relative humidity.
Dimensions:
1/8DIN (48 x 96mm) with 162mm depth, panel cut of 45 x 92mm.
Weight:
0.5kg approx.
Warranty:
One-year warranty.
presys

PRESYS Instruments DMY-2030-CC
Installation
Page 5
2.0 - Installation
2.1 - Mechanical Installation
The DMY-2030-CC Indicator front panel has 1/8DIN size (48 x 96mm).
It is fixed by the rails which press it against the back side of the panel.
After preparing a 45 x 92mm cut in the panel, remove the rails from the Indicator
and slide its rear through the cut until its front reaches the panel. Place the rails again in
the Indicator from the back of the panel and tighten the screws as shown in figure 2.
Fig. 2 - Dimensional drawing, panel cutout and side view
2.2 - Electrical Installation
DMY-2030-CC Indicator may be powered by voltage between 75 and 264Vac or
100 to 360Vdc, any polarity. Remember that the internal circuit is powered whenever the
instrument is connected to the external power supply.
presys
Indicator front panel has 1/8DIN size (48 x 96mm).
presys
Indicator front panel has 1/8DIN size (48 x 96mm).
It is fixed by the rails which press it against the back side of the panel.
presys
It is fixed by the rails which press it against the back side of the panel.
After preparing a 45 x 92mm cut in the panel, remove the rails from the Indicator
presys
After preparing a 45 x 92mm cut in the panel, remove the rails from the Indicator
and slide its rear through the cut until its front reaches the panel. Place the rails again in
presys
and slide its rear through the cut until its front reaches the panel. Place the rails again in
the Indicator from the back of the panel and tighten the screws as shown in figure 2.
presys
the Indicator from the back of the panel and tighten the screws as shown in figure 2.
presys
Fig. 2
presys
Fig. 2
presys
2.2 - El
presys
2.2 - El
ec
presys
ec
trical Installation
presys
trical Installation
DMY-
presys
DMY-

PRESYS Instruments DMY-2030-CC
Installation
Page 6
Input and output signals must be connected to the instrument only when it is
turned off.
Figure 3 shows the instrument rear terminals for connection of power supply,
ground, communication, process input and output signals.
Signal wiring must be kept far away from power wires.
Due to its metal case the instrument ground should be connected to earth ground.
Never connect the ground to neutral terminal.
Fig. 3 - Indicator terminals
2.3 - Input Signal Connection
The Indicator input can receive amV signal applied to terminals 2(+) and 3(-).
The input is enabled by software configuration (see section 3.2 on
Configuration).
In order to avoid noise in the wiring, use twisted pair cable and cross sensor
connection wire inside a metallic tube or use shielded cable. Make sure to connect only
one shield wire end either to board terminal or to sensor ground, as shown in the next
items.
WARNING: GROUNDING TWO SHIELD WIRE ENDS MAY CAUSE NOISE IN
THE INDICATOR.
presys
Due to its metal case the instrument ground should be connected to earth ground.
presys
Due to its metal case the instrument ground should be connected to earth ground.
presys
Fig. 3
presys
Fig. 3
- Indicator terminals
presys
- Indicator terminals
2.3 - Input Signal
presys
2.3 - Input Signal
Co
presys
Co
n
presys
n
ne
presys
ne
ction
presys
ction
The Indicator input can receive
presys
The Indicator input can receive
a
presys
a
mV signal
presys
mV signal
The input is enabled by software configuration (see section 3.2 on
presys
The input is enabled by software configuration (see section 3.2 on
Configuration).
presys
Configuration).
In order to avoid noise in the wiring, use twisted pair cable and cross sensor
presys
In order to avoid noise in the wiring, use twisted pair cable and cross sensor
presys
connection wire inside a metallic tube or use shielded cable. Make sure to connect only
presys
connection wire inside a metallic tube or use shielded cable. Make sure to connect only
one shield wire end either to board terminal or to sensor ground, as shown in the next
presys
one shield wire end either to board terminal or to sensor ground, as shown in the next
items.
presys
items.
WARNING: GROUNDING TWO SHIELD WIRE ENDS MAY CAUSE NOISE IN
presys
WARNING: GROUNDING TWO SHIELD WIRE ENDS MAY CAUSE NOISE IN
presys
THE INDICATOR.
presys
THE INDICATOR.

PRESYS Instruments DMY-2030-CC
Installation
Page 7
2.3.1 - Millivolt Input
Voltage signal in the range -30to +30 mVdc is applied to terminals 2(+) e 3(-).The
connections are shown in figure 4.
Fig. 4- Voltage signal connection
2.4 - Output Signal Connection
The Indicator can have up to three optional output modules: outputs 1 to 3. Output
1 is used as a retransmitter output (4 to 20mA, 1 to 5Vdc or 0 to 10Vdc) or alarm (SPST
relay, open collector voltage and solid state relay).Outputs 2 and 3 are used only as
alarm outputs (SPDT relay, open collector voltage and solid state relay). Figure 5 shows
the Indicator output types.
Note that the output terminals will present the corresponding signals only if
the optional modules are installed and the output is correctly configured. Refer to
section 3.2 on Configuration e 4.3 on Installation of Optional Modules for further
details.
presys
presys
Fig.
presys
Fig.
4
presys
4
- Voltage signal connection
presys
- Voltage signal connection
2.4 - Output Signal
presys
2.4 - Output Signal
Co
presys
Co
n
presys
n
ne
presys
ne
ction
presys
ction
The Indicator can have up to three optional output modules: outputs 1 to 3. Output
presys
The Indicator can have up to three optional output modules: outputs 1 to 3. Output
1 is used as a retransmitter output (4 to 20mA, 1 to 5Vdc or 0 to 10Vdc) or alarm
presys
1 is used as a retransmitter output (4 to 20mA, 1 to 5Vdc or 0 to 10Vdc) or alarm
relay, open collector voltage and solid state relay)
presys
relay, open collector voltage and solid state relay)
alarm outputs (SPDT relay, open collector voltage and solid state relay). Figure 5 shows
presys
alarm outputs (SPDT relay, open collector voltage and solid state relay). Figure 5 shows
the Indicator output types.
presys
the Indicator output types.
Note that the output terminals will present the corresponding signals only if
presys
Note that the output terminals will present the corresponding signals only if
the optional modules are installed and the output is correctly configured. Refer to
presys
the optional modules are installed and the output is correctly configured. Refer to
section 3.2 on Configuration e 4.3 on Installation of Optional Modules for further
presys
section 3.2 on Configuration e 4.3 on Installation of Optional Modules for further
details.
presys
details.

PRESYS Instruments DMY-2030-CC
Installation
Page 8
(*) Relay contact states presented for SAFE option selected (see section 3.2 on Configuration), instrument
powered on and non-alarm condition. Position of the contacts are changed in alarm condition (with SAFE option
selected) or when the instrument is turned off.
Fig. 5- Output Connection
presys
presys
(*) Relay contact states presented for SAFE option selected (see section 3.2 on Configuration), instrument
presys
(*) Relay contact states presented for SAFE option selected (see section 3.2 on Configuration), instrument
powered on and non-alarm condition. Position of the contacts are changed in alarm condition (with SAFE option
presys
powered on and non-alarm condition. Position of the contacts are changed in alarm condition (with SAFE option
presys
selected) or when the instrument is turned off.
presys
selected) or when the instrument is turned off.

PRESYS Instruments DMY-2030-CC
Installation
Page 9
2.5 - Connection Diagram
presys
presys

PRESYS Instruments DMY-2030-CC
Installation
Page 10
2.6 - Communication
DMY-2030-CC Indicator communicates with computers through RS-232 or
RS-485 and with use of a MODBUS protocol communication software, when the optional
communication module is installed and the communication parameters are configured.
Specific information on communication and signal connection is described in the
communication manual.
2.7 - Engineering Units
A label with several Engineering Units is supplied with each Indicator. Select the
one corresponding to the variable shown on the display and stick it to the front panel of
the Indicator.
presys
-485 and with use of a MODBUS protocol communication software, when the optional
presys
-485 and with use of a MODBUS protocol communication software, when the optional
communication module is installed and the communication parameters are configured.
presys
communication module is installed and the communication parameters are configured.
Specific information on communication and signal connection is described in the
presys
Specific information on communication and signal connection is described in the
A label with several Engineering Units is supplied with each Indicator. Select the
presys
A label with several Engineering Units is supplied with each Indicator. Select the
one corresponding to the variable shown on the display and stick it to the front panel of
presys
one corresponding to the variable shown on the display and stick it to the front panel of

PRESYS Instruments DMY-2030-CC
Operation
Page 11
3.0 - Operation
3.1 - Normal operation
The DMY-2030-CC Indicator has two modes of operation: normal operation and
configuration mode.
During normal operation, the Indicator monitors the inputs, verifies alarm
conditions and activates the outputs when necessary.
Configuration mode is used to select and configure all the Indicator parameters.
The normal operation mode, in which the Indicator is to be found most of the time,
is called level zero. In this level, the three front panel keys have the following functions:
Key Function
ENTER
Changes information shown on the display.
When the display shows the process
variable (PV), it goes to the maximum peak
value (MAX),if enabled.Next,it goes to
the minimum peak value (MIN), to the
setpoints of alarms 1 to 3 (SP1, SP2 and
SP3), if enabled,to the CONF mnemonic
(which allows one to enter the configuration
level)and to the process variable again.
Allows the acknowledgment of alarms
configured with latch function, after the
alarm condition returned to normal state.
UP
When CONF is shown, the display changes
to PASS and it requires the password for
changing from level zero to level one.
Gives access to the maximum and
minimum peak values or allows the reset of
these values.
When the process variable is shown, it
presents the mnemonics of the alarms
which require acknowledgment.
Increases the setpoint value of the alarm
shown.
DOWN
Resets the indication and the values of
maximum and minimum peaks and the
registered peak values.
Stores the value of the maximum or the
minimum peak depending on which value is
shown.Decreases the alarm setpoint value
shown.
presys
Indicator has two modes of operation: normal operation and
presys
Indicator has two modes of operation: normal operation and
During normal operation, the Indicator monitors the inputs, verifies alarm
presys
During normal operation, the Indicator monitors the inputs, verifies alarm
Configuration mode is used to select and configure all the Indicator parameters.
presys
Configuration mode is used to select and configure all the Indicator parameters.
The normal operation mode, in which the Indicator is to be found most of the time,
presys
The normal operation mode, in which the Indicator is to be found most of the time,
is called level zero. In this level, the three front panel keys have the following functions:
presys
is called level zero. In this level, the three front panel keys have the following functions:
Function
presys
Function
presys
presys
presys
Changes information shown on the display
presys
Changes information shown on the display
.
presys
.
When the display shows the process
presys
When the display shows the process
variable
presys
variable
(P
presys
(P
V
presys
V
)
presys
)
,
presys
,
it goes to the maximum peak
presys
it goes to the maximum peak
value (MAX)
presys
value (MAX)
,
presys
,
if enabled
presys
if enabled
.
presys
.
Next
presys
Next
,
presys
,
it
presys
it
goes
presys
goes
the
presys
the
m
presys
m
i
presys
i
nim
presys
nim
um peak
presys
um peak
value
presys
value
(
presys
(
MIN
presys
MIN
)
presys
)
,
presys
,
to
presys
to
setpoints of
presys
setpoints of
alarms 1 to 3
presys
alarms 1 to 3
(SP1, SP2
presys
(SP1, SP2
SP3),
presys
SP3),
if
presys
if
enabled
presys
enabled
,
presys
,
to the
presys
to the
CONF
presys
CONF
(
presys
(
which allows one to enter the configuration
presys
which allows one to enter the configuration
level
presys
level
)
presys
)
and to the process variable again
presys
and to the process variable again
A
presys
A
llows th
presys
llows th
e acknowledgment of alarms
presys
e acknowledgment of alarms
configured with latch function, after the
presys
configured with latch function, after the
alarm condition returned to normal state
presys
alarm condition returned to normal state
presys
presys
presys
presys
presys
UP
presys
UP
presys
presys
presys
presys
When
presys
When
CONF
presys
CONF
is shown,
presys
is shown,
to PASS and
presys
to PASS and
changing from level zero to
presys
changing from level zero to
G
presys
G
ives access to the maximum and
presys
ives access to the maximum and
minimum peak values
presys
minimum peak values
these values
presys
these values
presys
presys
presys
presys
presys
presys
presys
presys
D
presys
D
OWN
presys
OWN
presys
presys
presys
presys
presys
presys

PRESYS Instruments DMY-2030-CC
Operation
Page 12
The information sequence presented on the display is shown in figures 6 and 7
according to the configuration of the maximum and minimum peak register option
(REG option in the GENERAL configuration level):
Fig. 6- Information in the operation level when the peak register option is enabled.
Fig. 7- Information in the operation level when the peak register option is disabled.
The values of the maximum and minimum peaks of the process variable detected
in the input can be seen in the operation level:the MAX and MIN mnemonicsindicate the
maximum and minimum values, respectively.
The instrument allows the storage of five maximum and five minimum peak values
in its memory.
When the process variable indication is shown,the DOWN key can be used to
reset the value indicated (TARE function). Such adjustement is stored in the indicator
memory.
The value of the peak exhibited by MAX or MIN can be reset by pressing the UP
key,in case the REG option is disabled.When the process variable is shown and REG is
enabled,one must press DOWN to reset the maximum and minimum peak values and
apply the TARE function.
In order the see the registered maximum (minimum) peak values, when the REG
option is enabled,one must press the UP key when the value associated to MAX (MIN)
presys
presys
- Information in the operation level when the peak register option is
presys
- Information in the operation level when the peak register option is
enabled
presys
enabled
presys
Fig.
presys
Fig.
7
presys
7
- Information in the operation level when the peak register option is disabled.
presys
- Information in the operation level when the peak register option is disabled.
The values
presys
The values
of
presys
of
the maximum and minimum peaks of the process variable detected
presys
the maximum and minimum peaks of the process variable detected
of the maximum and minimum peaks of the process variable detectedof
presys
of the maximum and minimum peaks of the process variable detectedof
in the input
presys
in the input
can be
presys
can be
seen in the operatio
presys
seen in the operatio
maximum and minimum values, respectively
presys
maximum and minimum values, respectively
The instrument allows the storage of five maximum and five minimum peak values
presys
The instrument allows the storage of five maximum and five minimum peak values
presys
in its memory.
presys
in its memory.
When the process variable indication is shown
presys
When the process variable indication is shown
reset the value indicated (TARE function). Such adjustement is stored in the indicator
presys
reset the value indicated (TARE function). Such adjustement is stored in the indicator
memory.
presys
memory.
presys
The value of the peak exhibited by MAX or MIN can be reset by pressing the UP
presys
The value of the peak exhibited by MAX or MIN can be reset by pressing the UP
case the REG option is disabled
presys
case the REG option is disabled

PRESYS Instruments DMY-2030-CC
Operation
Page 13
is shown. In this way,one accesses a menu with five registers indicated by the
mnemonics MAX.1 to MAX.5 for the maximum peaks (MIN.1 to MIN.5 for the minimum
peaks).The first register of the menu, MAX.1 (MIN.1), refers to the most recently stored
value.When pressing the DOWN key for the maximum peak,the value of each register
is displaced to the next one,that is,MAX.1 receives the new value,while the previous
value of MAX.1 goes to MAX.2, the previous value of MAX.2 goes to MAX.3, and so on.
For the minimum peak,a similar process follows.
The registered values for both the maximum and the minimum peaks are reset
when the DOWN key is pressed during the exhibition of the process variable (the same
key used to apply the TARE function).
The normal operation and configuration modes present a “timer” which make the
display return to the process variable if it shows any other kind of information and no key
is pressed for 1 minute. It does not apply to the Calibration level (Calib. mnemonic). See
item 3.2 on Configuration.
3.2 - Configuration
In order to access the configuration mode the operator is required to provide a
password which avoids a non-authorized person to change any critical parameters of the
process. When UP is pressed, while CONF is shown in the normal operation mode, the
PASS warning is displayed and the user should press the UP, DOWN and ENTER keys
(exactly in this order) to access the configuration levels. If the user provides an incorrect
sequence of keys or if it takes more than 15 seconds for the password to be given, the
display returns immediately to the normal operation level. This procedure is shown in
figure 8.
Note: In the diagrams below, the rectangles represent
the display appearance after pressing the keys.
Fig. 8- Key sequence password
All configuration parameters are stored in the non-volatile memory and determine
the normal operation of the instrument. With these parameters the user can adjust the
instrument to his needs, when it is necessary to change the configuration from factory.
presys
while the previous
presys
while the previous
value of MAX.1 goes to MAX.2, the previous value of MAX.2 goes to MAX.3, and so on
presys
value of MAX.1 goes to MAX.2, the previous value of MAX.2 goes to MAX.3, and so on
The registered values for both the maximum and the minimum peaks are reset
presys
The registered values for both the maximum and the minimum peaks are reset
when the DOWN key is pressed during the exhibition of the process variable (the same
presys
when the DOWN key is pressed during the exhibition of the process variable (the same
normal operation and configuration modes present a “timer” which make the
presys
normal operation and configuration modes present a “timer” which make the
display return to the process variable if it shows any other kind of information and no key
presys
display return to the process variable if it shows any other kind of information and no key
is pressed for 1 minute. It does not apply to the Calibration level (Calib. mnemonic). Se
presys
is pressed for 1 minute. It does not apply to the Calibration level (Calib. mnemonic). Se
e
presys
e
In order to access the configuration mode the operator is required to provide a
presys
In order to access the configuration mode the operator is required to provide a
password which avoids a non-authorized person to change any critical parameters of the
presys
password which avoids a non-authorized person to change any critical parameters of the
process. When UP is pressed, while CONF is shown in the normal operation mode, the
presys
process. When UP is pressed, while CONF is shown in the normal operation mode, the
PASS warning is displayed and the user should press the UP, DOWN and ENTER keys
presys
PASS warning is displayed and the user should press the UP, DOWN and ENTER keys
(exactly in this order) to access the configuration levels. If the user provides an incorrect
presys
(exactly in this order) to access the configuration levels. If the user provides an incorrect
sequence of keys or if it takes more than 15 seconds for the password to be given, the
presys
sequence of keys or if it takes more than 15 seconds for the password to be given, the
display returns immediately to the normal operation level. This procedure is shown in
presys
display returns immediately to the normal operation level. This procedure is shown in
presys
Note: In the diagrams below, the rectangles represent
presys
Note: In the diagrams below, the rectangles represent
the display appearance after pressing the keys.
presys
the display appearance after pressing the keys.
presys
Fig.
presys
Fig.
All configuration parameters are stored in the non-volatile memory and determine
presys
All configuration parameters are stored in the non-volatile memory and determine
the normal operation of the instrument. With these parameters the user can adjust the
presys
the normal operation of the instrument. With these parameters the user can adjust the
instrument to his needs, when it is necessary to change the configuration from factory.
presys
instrument to his needs, when it is necessary to change the configuration from factory.

PRESYS Instruments DMY-2030-CC
Operation
Page 14
Configuration parameters are distributed in eight hierarchical levels shown in
figure 9.
Fig. 9- Parameter levels diagram
In order to move through the levels and access the parameters of any one of
them, use the front panel keys which have the following functions:
Key Description
UP
Moves to higher levels
DOWN
Moves to lower levels
ENTER
Enters the level
The Indicator allows the user to know what kind of input, alarms or output are
configured without need to access a specific parameter level. The mnemonics
corresponding to the level and to the configuration chosen move on the display
continuously, as soon as one reaches one of the levels (except Calib. and RS).
presys
presys
Fig.
presys
Fig.
9
presys
9
- Parameter levels diagram
presys
- Parameter levels diagram
In order to move through the levels and access the parameters of any one of
presys
In order to move through the levels and access the parameters of any one of
them, use the front panel keys which have the following functions:
presys
them, use the front panel keys which have the following functions:
Key
presys
Key
presys
presys
presys
presys
presys
presys
UP
presys
UP
Moves to higher levels
presys
Moves to higher levels
presys
presys
presys
presys
presys
presys
DOWN
presys
DOWN
Moves to lower levels
presys
Moves to lower levels
presys
presys
presys
presys
presys
presys
ENTER
presys
ENTER
presys
presys
presys
presys
presys
presys
The Indicator allows the user to know what kind of input, alarms or output are
presys
The Indicator allows the user to know what kind of input, alarms or output are
configured without need to access a specific parameter level. The mnemonics
presys
configured without need to access a specific parameter level. The mnemonics
presys
corresponding to the level and to the configuration chosen move on the display
presys
corresponding to the level and to the configuration chosen move on the display
continuously, as soon as one reaches one of the levels (except Calib. and RS).
presys
continuously, as soon as one reaches one of the levels (except Calib. and RS).

PRESYS Instruments DMY-2030-CC
Operation
Page 15
Inside each level, the front panel keys have the following functions:
Key Description
UP
Moves the options in increasing direction
DOWN
Moves the options in decreasing direction
ENTER
Confirm or advance options inside a level, if the display
does not show ESC. When ESC is shown, it returns one or
more positions.
When accessing any parameter of a configuration level, the Indicator directly shows
the option or value corresponding to the current configuration of the parameter. In case a
value is presented, use the UP and DOWN keys to change each digit and press ENTER
to move to the next one. When configuring the options of a parameter, the UP and
DOWN keys are used to move through the options and the ENTER key, to confirm the
choice.
The hierarchical levels are presented in sequence. The options of each level are
explained step by step with all their corresponding parameters.
Level 1 - Input
The mV input is configured by means of the parameters of the input level
indicated below:
Fig. 10 - INPUT level options
presys
presys
Confirm or advance options inside a level, if the display
presys
Confirm or advance options inside a level, if the display
does not show ESC. When ESC is shown, it returns o
presys
does not show ESC. When ESC is shown, it returns o
ne or
presys
ne or
presys
presys
presys
presys
When accessing any parameter of a configuration level, the Indicator directly shows
presys
When accessing any parameter of a configuration level, the Indicator directly shows
the option or value corresponding to the current configuration of the parameter. In case a
presys
the option or value corresponding to the current configuration of the parameter. In case a
value is presented, use the UP and DOWN keys to change each digit and press ENTER
presys
value is presented, use the UP and DOWN keys to change each digit and press ENTER
to move to the next one. When configuring the options of a parameter, the UP and
presys
to move to the next one. When configuring the options of a parameter, the UP and
DOWN keys are used to move through the options and the ENTER key, to confirm the
presys
DOWN keys are used to move through the options and the ENTER key, to confirm the
The hierarchical levels are presented in sequence. The options of each level are
presys
The hierarchical levels are presented in sequence. The options of each level are
explained step by step with all their corresponding parameters.
presys
explained step by step with all their corresponding parameters.
presys
The mV input is configur
presys
The mV input is configur
ed
presys
ed
by means of the
presys
by means of the
par
presys
par
amete
presys
amete
rs
presys
rs
of the input level
presys
of the input level
presys

PRESYS Instruments DMY-2030-CC
Operation
Page 16
The table below refers to the ranges of the parameters shown in figure 10.
Mnemonic Parameter Range
Factory
Value
Units
LIM LOW
input signal associated
to Eng Low
-100.0 to 100.0 0.0 %
LIM HIGH
input signal associated
to Eng High
-100.0 to 100.0 100.0 %
ENG LOW
display indication
associated to the input
zero scale
-9999 to 20019 0.0 EU*
ENG HIGH
display indication
associated to the input
full scale
-9999 to 20019 100.0 EU
OFFSET
constant added to
display indication
-9999 to 30000 0 EU
FILTER
time constant of 1st
order digital filter
0.0 to 25.0 0.0 seconds
(*) EU–Engineering Unit
The input scale is configured by choosing the 30 mV mnemonic. Define two points
P1 (Lim Low, Eng Low) and P2 (Lim High, Eng High), as shown in figure 11. Lim Low
(given in %) corresponds to the electrical signal value associated with the display
indication Eng Low, and Lim High (%) corresponds to the to the electrical signal value
associated with the display indication Eng High. The Lim Low and Lim High parameters
are associated with the porcentage of full scale,that is,-100.0% and 100% correspond to
-30mV and 30mV, respectively.
Fig. 11- Configuration of the 30 mV input
presys
%
presys
%
presys
100.0
presys
100.0
%
presys
%
presys
presys
presys
presys
presys
0.0
presys
0.0
E
presys
E
U
presys
U
*
presys
*
presys
presys
presys
presys
presys
presys
presys
20019
presys
20019
100.0
presys
100.0
E
presys
E
U
presys
U
presys
presys
presys
presys
presys
presys
presys
presys
presys
9999
presys
9999
to
presys
to
30000
presys
30000
0
presys
0
E
presys
E
U
presys
U
presys
presys
presys
presys
presys
presys
presys
presys
presys
0.0
presys
0.0
to
presys
to
25.0
presys
25.0
0.0
presys
0.0
se
presys
se
conds
presys
conds
presys
presys
presys
presys
presys
presys
presys
presys
presys
presys
presys
presys
presys
presys
The input scale is configured by choosing the
presys
The input scale is configured by choosing the
30
presys
30
mV
presys
mV
mnemonic. Define two points
presys
mnemonic. Define two points
P2 (Lim High, Eng High), as shown in figure
presys
P2 (Lim High, Eng High), as shown in figure
%) corresponds to the electrical signal value associated with the display
presys
%) corresponds to the electrical signal value associated with the display
High
presys
High
(%
presys
(%
)
presys
)
corresponds to the to the electrical signal value
presys
corresponds to the to the electrical signal value
associated with the display indication Eng High. The
presys
associated with the display indication Eng High. The
Lim
presys
Lim
Low
presys
Low
and
presys
and
are associated with the porcentage of full scale
presys
are associated with the porcentage of full scale
,
presys
,
that is
presys
that is
,
presys
,
-100.0% and 100% correspond
presys
-100.0% and 100% correspond
presys
30mV, respectiv
presys
30mV, respectiv
ely
presys
ely
.
presys
.
presys

PRESYS Instruments DMY-2030-CC
Operation
Page 17
DEC.PT - sets the decimal point position for the visualization of Engineering units
in the display. There are up to four decimal places.
OFSET (as is shown in the display) - allows the user to enter an off-set value in
Engineering Units to be added to the measured variable.
FILTER - this parameter provides the time constant of a first order digital filter
associated to the selected input (range from 0.0 to 25.0 s). In order to disable the filter, set
the parameter to zero.
Levels 2,3 and 4 - Alarms
The Indicator accepts up to three alarm modules: relays 1, 2 and 3. The alarm
conditions of alarms 2 and 3 can also be visualized by the couple of leds on the front
panel, LED 1 and LED 2, respectively.
The ALAR.1 mnemonic corresponds to the configuration of relay 1(output 1),
ALAR.2 to relay 2(output 2), and ALAR.3 to relay 3(output 3). The connectors on the
Power Supply Board corresponding to each one of the relays are listed below:
Relay
Board Connectors
1
MOD1 (Output 1)
2
MOD3 (Output 2)
3
MOD4 (Output 3)
Refer to section 4.3 on the Installation of Optional Modules for further details.
Each module can be configured as a high alarm (HI mnemonic), low alarm (LO),
or deviation alarm of the process variable from the setpoint (DEV), or be disabled (NO
mnemonic).
When configuring the high or low alarm it is necessary to set its setpoint SP and
hysteresis HYST. The deviation alarm requires the configuration of the setpoint SP, the
deviation parameter DV to determine the values above and below the setpoint where the
alarm is activated (SP-DESV and SP+DESV), and the hysteresis HYST (in U.E., from 0
to 30000) to define the band (between SP-DESV+HIST and SP+DESV-HIST) of return to
the normal or non-alarm condition. One can also use the LATCH and DELAY functions
for each alarm.
presys
OFSET (as is shown in the display) - allows the user to enter an off-set value in
presys
OFSET (as is shown in the display) - allows the user to enter an off-set value in
this parameter provides the time constant of a first order digital filter
presys
this parameter provides the time constant of a first order digital filter
In order to disable the filter, set
presys
In order to disable the filter, set
The Indicator accepts up to three alarm modules: relays 1, 2 and 3. The alarm
presys
The Indicator accepts up to three alarm modules: relays 1, 2 and 3. The alarm
conditions of alarms 2 and 3 can also be visualized by the couple of leds on the front
presys
conditions of alarms 2 and 3 can also be visualized by the couple of leds on the front
The ALAR.1 mnemonic corresponds to the configuration of relay
presys
The ALAR.1 mnemonic corresponds to the configuration of relay
1
presys
1
(output 1),
presys
(output 1),
ALAR.3 to relay
presys
ALAR.3 to relay
3
presys
3
(output 3). The connectors on the
presys
(output 3). The connectors on the
Power Supply Board corresponding to each one of the relays are listed below:
presys
Power Supply Board corresponding to each one of the relays are listed below:
ay
presys
ay
Board Connectors
presys
Board Connectors
presys
presys
presys
presys
presys
presys
1
presys
1
MOD1 (
presys
MOD1 (
Output
presys
Output
1)
presys
1)
presys
presys
presys
presys
presys
presys
2
presys
2
MOD3 (
presys
MOD3 (
Output
presys
Output
2)
presys
2)
presys
presys
presys
presys
presys
presys
3
presys
3
MOD4 (Output
presys
MOD4 (Output
3)
presys
3)
presys
presys
presys
presys
presys
presys
presys
presys
presys
presys
presys
Refer to section 4.3
presys
Refer to section 4.3
on
presys
on
the Installation of Optional Modules for further details.
presys
the Installation of Optional Modules for further details.
Each module can be configured as a high alarm (HI mnemonic), low alarm (LO),
presys
Each module can be configured as a high alarm (HI mnemonic), low alarm (LO),
deviation alarm of the process variable from the setpoint (DEV), or be disabled (NO
presys
deviation alarm of the process variable from the setpoint (DEV), or be disabled (NO
mnemonic).
presys
mnemonic).
When configuring the high or low alarm it is necessary to set its setpoint SP and
presys
When configuring the high or low alarm it is necessary to set its setpoint SP and
hysteresis HYST. The deviation alarm requires the configuration of the setpoint SP, the
presys
hysteresis HYST. The deviation alarm requires the configuration of the setpoint SP, the
deviation parameter DV to determine the values above and below the setpoint where the
presys
deviation parameter DV to determine the values above and below the setpoint where the
alarm is activated
presys
alarm is activated
(SP
presys
(SP
-DESV and SP+DESV), and the hysteresis HYST (in U.E., from 0
presys
-DESV and SP+DESV), and the hysteresis HYST (in U.E., from 0
to 30000) to define the band (between SP-DESV+HIST and SP+DESV-HIST)
presys
to 30000) to define the band (between SP-DESV+HIST and SP+DESV-HIST)
the normal or non-alarm condition. One can also use the LATCH and DELAY functions
presys
the normal or non-alarm condition. One can also use the LATCH and DELAY functions
for each alarm.
presys
for each alarm.
Table of contents
Other Presys Measuring Instrument manuals

Presys
Presys DMY-2030-F User manual

Presys
Presys TA-25NL User manual

Presys
Presys DMY-2030-TOT Light User manual

Presys
Presys DMY-2015 User manual

Presys
Presys PROFI BUS DMY-2015-PB User manual

Presys
Presys DMY-2011 User manual

Presys
Presys DMY-2030 Light User manual

Presys
Presys DCY-2058 User manual

Presys
Presys TE-25N User manual

Presys
Presys DMY-2030 Light User manual
Popular Measuring Instrument manuals by other brands

Thermo Scientific
Thermo Scientific RadEye GF operating instructions

ATAGO
ATAGO PAL-Easy ACID40 instruction manual

CoaguSense
CoaguSense Coag-Sense user manual

Precision Digital Corporation
Precision Digital Corporation Survivor PD662 instruction manual

Sony
Sony MAV-555A installation manual

SPS
SPS SD1 instruction manual