Protecta EuroProt+ User manual

PROTECTION, AUTOMATION AND
CONTROL FOR POWER INDUSTRY
DOCUMENT ID: PP-06-22516
LAST VERSION: 1.0
2022-02-21, BUDAPEST
Installation Manual
EUROPROT+
A
PPLICATION GUIDE

2 Installation Manual
www.protecta.hu
VERSION INFORMATION
VERSION INFORMATION
VERSION DATE MODIFICATION COMPILED BY
1.0 2022-02-21 First edition Hanti

3 Installation Manual
www.protecta.hu
CONTENTS
CONTENTS
1 Introduction ........................................................................................................................... 4
2 Equipment handling .............................................................................................................. 4
2.1 Unpacking ...................................................................................................................... 4
2.2 Visual inspection ............................................................................................................ 5
2.3 Storage .......................................................................................................................... 5
3 Mounting ............................................................................................................................... 5
3.1 Tools for mounting ......................................................................................................... 5
3.2 Environmental conditions .............................................................................................. 5
3.3 Mounting location .......................................................................................................... 5
3.4 Mounting the device ...................................................................................................... 6
3.5 Safety aspects ............................................................................................................... 6
3.5.1 Earth connections .................................................................................................. 6
3.5.1.1 Protective earth ............................................................................................. 6
3.5.1.2 Stranded wires ............................................................................................... 6
3.5.1.3 Cable screen connection ............................................................................... 7
3.5.1.4 CT and VT circuits ......................................................................................... 7
3.5.2 Connections of the device ..................................................................................... 7
3.5.3 Optical ports .......................................................................................................... 7
3.5.4 Removing and changing modules ......................................................................... 8
4 Wiring .................................................................................................................................... 8
4.1 Tools for connecting ...................................................................................................... 8
4.2 Connectors .................................................................................................................... 9
5 Deinstallation and Repair...................................................................................................... 9
5.1 Deinstallation ................................................................................................................. 9
5.2 Repair ............................................................................................................................ 9
5.3 Disposal ......................................................................................................................... 9

4 Installation Manual
www.protecta.hu
USED SYMBOLS
USED SYMBOLS
Symbols on devices: Symbols in this document:
Test voltage: 2 kV
Protective conductor terminal
Do not dispose of this device
Caution, risk of electric shock
Caution, hot surface
Caution, refer to the documentation
Do not dispose of this device
1 Introduction
This manual is intended to provide instruction for proper device installation, which includes
mechanical mounting and electrical wiring. Furthermore, the information provided here will
strongly support commissioning, maintenance, and deinstallation work as well. This document’s
targeted user groups are skilled electrical professionals executing installation works and
commissioning with EuroProt+ devices.
Given that the EuroProt+ product family has a modular design, the instructions provided here can
cover all configurations. Therefore, this manual shall be used in conjunction with the “EuroProt+
Hardware description” document, which includes essential information about all hardware
components of the product.
2 Equipment handling
2.1 Unpacking
Inspect the package for transport damages. Carefully remove the packing material without
applying excessive force.

5 Installation Manual
www.protecta.hu
MOUNTING
2.2 Visual inspection
Identify the product by reading the order code. This can be found on the device nameplate located
mostly on the right side of the device in the top right corner and shall be identical to your order.
Picture 2-2 Device nameplate
The protection device may have loose items packed in a different box based on the configuration.
Check, that these items are also included in the shipment.
Visually inspect all unpacked items for damages, water ingress, or any sign of external impact. If
you discover any transport damage, please notify Protecta Ltd. first and do not start any further
work on the equipment.
2.3 Storage
If temporary storage is required before installation, please store the device in its original packing
in a dry and clean place. The required environmental conditions can be found in the “General
data” section of the “EuroProt+ Hardware description” document.
3 Mounting
3.1 Tools for mounting
The tools and screws necessary for mounting depend on the method of the mounting, see the
“Mounting methods” section of the “EuroProt+ Hardware description” document.
Assuming the panel or cubicle is ready for installation of the device, screwdrivers matching the
screws used, plyers, wrenches, etc. are necessary. For safety aspects, mechanical protective
gloves shall be used to avoid injuries.
3.2 Environmental conditions
Make sure, that the mounting location fulfils environment requirements stated in the “General
data” section of the “EuroProt+ Hardware description” document. The IP protection class of the
device shall fit the surrounding environment at the place of installation. It is also important to have
space around the device to support conventional cooling (See 3.3).
3.3 Mounting location
Before mounting the device make sure, that suitable space is available in the location of
installation. Cutouts shall fit the device rack dimensions and it is recommended to leave 80mm
free space behind the IED for the wiring.
The minimum distance between an EP+ device and its wire channel must be at least 3 cm.
The minimum distance between two EP+ devices must be at least 10 cm.

6 Installation Manual
www.protecta.hu
MOUNTING
3.4 Mounting the device
The EuroProt+ product line utilizes different rack sizes and depending on that different mounting
methods. An overview of the rack sizes with dimensions and mounting methods can be found in
the “Mounting methods” section of the “EuroProt+ Hardware description” document.
During the installation make sure that the shortest possible length for PE (Protective Earth) cable
routing is applied.
3.5 Safety aspects
3.5.1 Earth connections
3.5.1.1 Protective earth
The device shall be connected to the station earth system with a minimum of 2,5 mm2 cross-
section solid or stranded wire. A 6,3 mm (1/4 inch) female flat connector (according to IEC 61210)
shall be used crimped to the earthing wire. During the installation make sure that the shortest
possible length for PE (Protective Earth) cable routing is applied.
The earth connection of the device is situated at all kinds of Power supply modules. In the case
of more Power supply modules, all of them shall be earthed.
The protective earth connections should not be removed when the equipment is energized.
Picture 3-5-1-1 Earth connection point of the device at the Power supply module
3.5.1.2 Stranded wires
Soft soldering of stranded wires is not allowed due to the cold flow of the solder material.
Loose strands of stranded wires can cause fire risk or electric shock. Insulated crimp terminals
shall be used.

7 Installation Manual
www.protecta.hu
MOUNTING
3.5.1.3 Cable screen connection
The screen of the telecommunication cables connected directly to the device shall be terminated
to the earthing connection point of the corresponding module.
Picture 3-5-1-3 An example of the cable screen connection
3.5.1.4 CT and VT circuits
The CT and VT circuits to be connected to the device shall be connected to the station earth
system.
3.5.2 Connections of the device
Before connecting the wires, make sure that all voltage levels correspond to the device ratings.
It is particularly important by the power supply, trip and binary input, CT and VT module
Use only the connectors provided to the device or identical ones.
The CT connectors shall be fixed with screws provided. During the operation of the device, the
CT connectors can be disconnected only after the CT circuits having short-circuited.
3.5.3 Optical ports
Take adequate measures to protect your eyes and do not view directly into optical ports.

8 Installation Manual
www.protecta.hu
WIRING
The fiber optics cables are vulnerable. Sharp bending can damage them. The minimum bending
radius can be between 15 cm and 25 cm approximately, depending on the type and the material
of the cable. For details see the datasheets of the fiber optics cables to be installed. The fiber
shall not be twisted or bent. When connecting or disconnecting the cable always hold the
connector, not the cable.
3.5.4 Removing and changing modules
Before removing and changing modules first the power supply voltage of the device shall be
disconnected. Then all the energizing quantities connected to each module of the device shall be
disconnected. Before removing the connectors of the CT modules, the CT circuits shall be short-
circuited and disconnected.
The protective earth connection can be disconnected last if it is necessary (e.g. when removing
a Power supply module).
The devices contain components that are sensitive to electrostatic discharges. ESD wrist strap
shall be worn during any operations with modules.
Some of the modules can operate at high internal temperatures. Remove these modules carefully
to avoid any burn injury. Take care of the possible high temperature at each module.
The modules have got sharp edges. Remove them carefully to avoid injury.
After changing a module, it shall be fixed with the screws provided with a torque of 0,5 Nm. Use
Philips 2 screwdriver.
4 Wiring
4.1 Tools for connecting
Screwdrivers for the connectors: blade 0,6/3,5 mm, 0,4/2,5 mm.
Cutter, stripper, crimper tools to prepare the connecting end of the wires.

9 Installation Manual
www.protecta.hu
DEINSTALLATION AND
REPAIR
4.2 Connectors
The “Connectors” section of the “EuroProt+ Hardware description”
provides information about the required conductor dimensions and connecting methods. The
“Connectors” table shall be used together with the other sections describing the different modules.
5 Deinstallation and Repair
5.1 Deinstallation
Before removing the device make sure, that all incoming power supply and control voltages are
switched off. The earth connection of the device shall be disconnected last.
5.2 Repair
Thanks to its modular design, many hardware problems can be fixed by replacing single modules.
By executing this procedure note, that the printed board’s surface may get hot during normal
operation.
In addition, attention shall be paid to the sharp edges of the modules to avoid minor injuries on
the hand.
5.3 Disposal
Removed IEDs shall be handed over to a local electronic waste handler for proper disposal and
recycling.

10 Installation Manual
www.protecta.hu
DEINSTALLATION AND
REPAIR
Table 5-3 Disposal of the components and parts
IED
P
ARTS
M
ATERIAL
M
ETHOD OF DISPOSAL
Enclosure Metal sheets, fastening
elements
Aluminum, steel Separation and
recycling
Modules
Metallic parts, fastening
elements
Aluminum, steel Separation and
recycling
Mounted PC boards Plastic, various
electronic elements
Separation and
recycling
Connectors Plastic, various metals Separation and
recycling
Transformers, coils Iron, copper, plastic,
paper
Separation and
recycling
Relays Iron, copper, plastic,
other metals
Separation and
recycling
Package
Box Cardboard Recycling
Attachments
Manuals, certificates Paper Recycling
Other manuals for EuroProt+