Table of Parameters
The following Modbus TCP-specific configuration settings are available in the SIPROTEC 4 device. For
further Information to the Modbus TCP mapping file see chapter 2).
Table 1-1 Modbus TCP-Specific Settings
Parameter Default
Setting
Setting Range Description
Slave Address 1 1 to 247 Modbus TCP station address of
the device
TCPPortNumber 502,
504
100 to 65535
TcpPortNumber1 = 502
TcpPortNumber2 = 504
The TCP ports to listen on
EnableTimeSynchronization 0 0,1
1 = Enable Modbus-IP time sync.
0 = Disable Modbus-IP time sync.
Enable Modbus-IP time synchro-
nization
CoilBroadcastMsg 1 0,1
0 = no
1 = yes
Accept broadcast messages for
Coil Status Register using func-
tions Force Single Coil and Force
Multiple Coils
HoldingBroadcastMsg 1 0,1
0 = no
1 = yes
Accept broadcast messages for
Holding Register using functions
Preset Single Register and Preset
Multiple Regs
UseSetTimeAndDateReg 0 0,1
1 = Use Set Date and Time
register for acceptance of
previous written time synchroniza-
tion data.
0 = time synchronization data are
valid at the time of writing.
Two methods of data acceptance
for time synchronization of the
SIPROTEC 4 device via Modbus
are possible.
SingleBitDoubleCmdCtrl 0 0,1
1 = using functions Force Single
Coil or Force Multiple Coils.
0 = using function Force Multiple
Coils only
Control mode of double
commands.
ExceptionMsgAtInvalidData 0 0,1
1 = yes; only Read Input Register
and write commands are
executed.
0 = no; a bit in the Diagnostics
Register indicates Data Invalid.
Respond with Modbus exception
SLAVE_DEVICE_BUSY to
Modbus TCP master during the
period of Data Invalid error.
NOTE
The settings above are valid for all Modbus TCP connections in the same way; they cannot be configured
individually for each Modbus TCP connection or for each connected Modbus TCP master..
During startup of the Ethernet module, the configuration of all Modbus TCP parameters is checked. If a
parameter value is detected outside the valid range, an error-log entry is issued on the EN100+ module
and the parameter is set to its default value (see
Figure 5-2
).
1.4
Characteristic of the ModbusTCP Module
1.4 Table of Parameters
16 SIPROTEC 4, Modbus TCP Profile, Manual
C53000-L1840-C582-1, Edition 07.2015