www.pulsar.pl PSACH01244
Operating specifications (tab.5).
10%...90% without condensation
Vibrations during operation
Impulse waves during operation
Vibrations and impulse waves during transport
2. Installation.
2.1 Requirements
AC/AC power supply is to be mounted by a qualified installer, holding relevant permits and licenses
(required in installation country) to connect (interfere) with ~230 V mains supply. Unit should be mounted in
confined spaces, in accordance, with normal relative humidity (RH=90% maximum) and temperature from -25°C to
+40°C (table 5). PSU shall work in a vertical or horizontal position.
Before mounting the PSU module, perform a load balance. During normal operation, total current drawn by
the receivers cannot exceed I=4 A@~24 V.
As the PSU is designed for a continuous operation and is not equipped with a power-switch, therefore an
appropriate overload protection shall be guaranteed in the power supply circuit. Moreover, the user shall be
informed about the method of unplugging (usually through assigning an appropriate fuse in the fuse-box). Electrical
system shall follow valid standards and regulations.
2.2 Installation procedure.
CAUTION!
Before installation, cut off voltage in 230V power-supply circuit. To switch power off, use an
external switch, in which distance between contacts of all poles in disconnection state is not
less than 3 mm.
It is required to install in the supply circuits, in addition to power supply, circuit breaker with 6 A
nominal current.
1). Mount PSU in a selected location and connect wires (tighten cable glands).
2). Connect power cables (~230 V) to L-N clips of PSU. Connect the ground wire to the terminal marked by the
earth symbol . Use a three-core cable (with a yellow and green PE protection wire) to make the connection.
Lead the cables to the appropriate terminals of the connection board through the bushing.
Shock protection circuit shall be performed with a particular care, i.e. yellow and green wire
coat of power cable shall stick to one side of terminal marked with earth symbol in PSU
enclosure. Operation of power supply without a properly made and fully operational shock
protection circuit is UNACCEPTABLE! It can result in device damage or an electric shock.
4). Connect conductors of consumers to terminals U1-0V and/or U2-0V of terminal box on power-supply unit
(balance of power-supply load shall be performed).
5). Restore mains power ~230 V.
6). Once tests and control operation have been completed, close PSU.
3. Operating status indication.
3.1 Technical outputs.
The PSU is equipped with indication outputs allowing transmitting the information of casing sabotage (casing
opening).
TAMPER: output indicates opening the power-supply unit, output as volt-free contacts which indicate
power-supply unit door status, unit closed: NC, unit opened: NO.