
POWER
VT®WATER
HEATER
GAS BURNER START
-UP
(Refer
to
Figure
19-6,
page
11
to
identify burner parts)
WARNING:
START~UP
SHOULD ONLY BE PERFORMED BY AQUALIFIED TECHNICIAN.
1.
Remove enclosure panel cover
on
.
thE;
water
heater to expose control circuit. Awiring
dLsgram,
included
in
this packet, will show the :.ontrols
used in our circuitry.
2.
Visually check that all components are
int~"\ct
and
no
damage has occurred during transit
3. Check all connections within the control cabinet.
Aloose connection could cause intermittent
shutdowns.
4.
Some burners will
use
direct spark ignition
They
may use asingle gas pressure regulator and gas
valve or multiple valves
and
regulators. 01' a
call
for heat, the motor starts,
gas
primary.
control
is
energized, the air vent damper opens
and
after a
short delay (pre-purge), the
gas
valve(s)
opens
and ignition should occur.
NOTE: Do
not
tamper
with
or
readjust program
dipswitch
settings. This
will
cause the control to
become inoperable. Damage resulting from
tampering will be excluded from coverag( under
the warranty
of
this
unit.
5. Connect atest meter to the control for
p~ading
the flame response signal.
NOTE: Some
controls
read the flame
si~lflal
in
micro
amps
and
some
in
volts
DC.
The Mseries
control
has
two
terminals marked
for
reading
volts
in DC.
CAUTION:
Be
sure
the tank
is
filled with
water. Dry
firing
can destroy the water
heater.
6.
Check the gas pressure before start-up,
u$ing
a
U-tube manometer or a 0 to 28" W.C.
pre.ssure
gauge for inlet gas pressure. (This is the
pressure measured before all components
in
the
gas train.) The manometer must stay connected
throughout the testing,
as
the inlet pressure must
be
monitored. during the firing of the
burner.
Record static pressure; it must not exceed 14"
W.C.
Pressures above this could cause damage
to the diaphragm
in
the gas valve or
pr€:ssure
regUlator.
7.
Connect amanometer
to
the manifold test port at
the shutoff valve closest to the burner.
Tl.lrn
off
main gas shutoff valve. Turn unit
on
using the
rocker switch
on
the side of the control enclosure
assembly. If the operating control switches
are
closed, the burner blower should come
on
and
pre-purge begins.
8. If nothing happens, check the control; if it is not
in
the
tripped position, reset it
by
pushing the flame
safeguard reset button. The burner should pre-
purge at least thirty seconds.
9.
When the blower motor starts, the air damper will
open
and
the airflow
prOVing
light
or;
the
MEC120 should be
on.
This indicates apositive
airflow condition. If the air proving light is not on,
check the air-proving switch for operation. To
adjust the air-proving switch,
turn
the adjustment
screw counter-clockwise until the air proving light
comes
on,
then turn the screw one turn counter-
clockwise. If
the
gas valves open and close
intermittently during normal operation, turn screw
one
half turn counter-clockwise until this
condition ceases. This procedure should
be
followed with every burner.
This section is
for
single-stage and two-stage
firing: After purging
is
complete, terminal 3on
the flame control energizes the pilot valve and
terminal 4energizes the ignition transformer. The
pilot
is
then
established. The
VDC
reading
on
the
meter should
read
asteady 6-10
VDC;
6VDC
is
{he
minimum flame signal for it
to
operate
reliably. If the pilot fails to light during the initial
period, it
is
probably due to air
in
the line. The
control will lockout and require reset.
Once the flame is established, the ignition
transformer will de-energize
and
terminal 5will
energize the main valve. At this point the water
heater
is
operating at maximum firing rate (high
fire).
In
order
to
insure the water heater is
operating at the rated input,
it
is
necessary to
check the manifold gas pressure (measured at
the pressure
tap
on
the gas valve closest to
burner). The manifold gas pressure should be
adjusted at main gas regulator to the factory
recommended pressure shown on tag
attached to gas train. Do not screw the
adjusting nut of the regUlator
in
beyond point
where no further Increase in manifold pressure
is noted.
PV500-19 04-2005 12 Section 19