Introduction .............................................................................................3
Description...............................................................................................3
1. Rada Pulse Control Box...................................................................3
2. Rada Pulse Sensors.........................................................................3
3. Solenoid Valves................................................................................5
4. Accessories ......................................................................................6
Safety : Warnings ....................................................................................7
Pack Contents .........................................................................................8
Dimensions ............................................................................................12
Specications ........................................................................................16
1. Rada Pulse Control Box.................................................................16
2. Rada Pulse Sensors.......................................................................16
3. Solenoid Valves..............................................................................18
Installation .............................................................................................20
General...............................................................................................20
1. Install the Control Box ....................................................................21
2. Install the Sensors..........................................................................23
2.1 Rada Pulse 120 and 122 Sensors .......................................23
2.2 Rada Pulse129 Sensor ........................................................ 24
2.3 Rada Pulse LR Sensor.........................................................26
2.4 Rada Pulse 124, 125 and 126 Ceiling Sensors ...................28
3. Install the Solenoid Valves .............................................................30
3.1 Rada SV1015 (HP) Solenoid Valve......................................30
3.2 SV2022/SV2028 Solenoid Valve..........................................31
3.3 SV3022 Solenoid Valve........................................................32
4. 3MTM Connectors ............................................................................33
Commissioning / Programming ...........................................................34
Installation Check...............................................................................34
Commission the System.....................................................................34
Final Commissioning - Walk Test .......................................................35
Maintenance...........................................................................................36
Fault Diagnosis......................................................................................42
Spare Parts ............................................................................................43
Customer Care.........................................................................Back Page

3
The Rada Pulse range of electronic products combine to produce a controlled
washroom environment offering a high degree of energy and water conservation. A
single Rada Pulse Control Box controls showering, hand washing and urinal ushing
with up to 10 outlets in any conguration. Each outlet operates via a no touch sensor,
ensuring maximum hygiene in the washroom.
The system is unique in the way that it is programmed remotely, via a hand held
programmer, which is plugged into the control box to set up or adjust the ow settings
of each individual outlet.
INTRODUCTION
1. Rada Pulse Control Box
The core of the system is the Rada Pulse Control Box containing a transformer
and a PCB. One control box can control up to ten outlets in any conguration e.g.
5 showers, 3 washbasins, 1 urinal and 1 W.C.
The Rada Pulse Control Box is designed to interface with Rada Pulse Sensors and
Rada Pulse Solenoid Valves which control the system functions.
Mounted in the Rada Pulse control box is a Printed Circuit Board to:
•Supply power to the remote mounted sensors.
•Operate remote mounted solenoid valves.
•Allow the operating functions to be programmed in through the hand held
programmer (refer to: 'Accessories').
•Provide a signal to allow the operation of auxiliaries via the Rada Pulse Relay
Box (refer to: 'Accessories') to automatically control lighting, extraction and
drainage pumps.
2. Rada Pulse Sensors
General
There are two generic types of no-touch sensors:
1. Active infrared sensors where a transmitted infrared beam of light is reected
back to the sensor by the proximity of a hand.
2. Ceiling Mounted passive infrared sensors where the sensor detects changes
in temperature in the detection area.
DESCRIPTION

4
2.1 Active Sensors
Rada Pulse 120/122 Sensors
The 120 sensor is a short range active sensor, and is designed to be installed within
a shower, W.C or basin area.
The 122 sensor is a long range active sensor, and is designed to be installed within
a urinal area.
All electrical connections are totally sealed, and the system operates at a very safe
low voltage.
The sensor is supplied with 3.0 metres of 2 core cable and is xed to the wall using
two xing screws (supplied). The screws are then concealed for security, by a chrome
plated cover.
Rada Pulse 129 Sensor
The 129 sensor is a short range active sensor, and is designed to be installed within
a shower, W.C or basin area.
All electrical connections are totally sealed, and the system operates at a very safe
low voltage.
The sensor is supplied with 3.0 metres of 2 core cable and is xed to the wall using
two xing screws (supplied). The sensor is housed within a chrome plated solid disc
with a recessed rear foam seal.
Rada Pulse LR Sensor
The LR sensor is a short range active sensor, and is designed to be installed within
a shower, W.C or basin area.
The LR Sensor is a chrome plated vandal resistant sensor designed to be recessed
or built within the wall surface, to allow for extra security.
All electrical connections are totally sealed, and the system operates at a very safe
low voltage.
The sensor is supplied with 3.0 metres of 2 core cable and is xed in the wall using
M6 xing studs (supplied).
2.2 Passive Sensors
Rada Pulse 124/125/126 Ceiling Sensor
The Rada Pulse Ceiling Sensor are passive sensors for the following applications:
Application Sensor Type
Washbasin 124
Single Urinal 125
Group Urinal 126
Note! Refer to section: 'Specications' for detection areas.

5
3. Solenoid Valves
Rada SV1015 (HP) Solenoid Valve (Direct Acting)
A 1/2" servo assisted solenoid valve, made from WRC approved PA66 Reinforced
Fibreglass, tted with 15 mm compression connections. Flat-faced inserts are
supplied for 1/2" BSP union inlet or outlet connections. An isolating ball valve is
tted to the inlet to allow the water supply to be isolated. A ow direction arrow on
the valve facilitates correct installation.
Rada SV2022 Solenoid Valve (Indirect Acting)
A 3/4" servo assisted solenoid valve made from brass with 3/4" BSP female
connections. A ow direction arrow on the valve facilitates correct installation.
Rada SV2028 Solenoid Valve (Indirect Acting)
A 1" servo assisted solenoid valve made from brass with 1" BSP female connections.
The valve is marked "IN" on the end to connect the inlet water supply.
Rada SV3022 Solenoid Valve (Direct Acting)
A 3/4" lift assisted solenoid valve made from brass with 3/4" BSP female
connections.
A ow direction arrow on the valve facilitates correct installation.

6
4. Accessories
4.1 Rada Pulse Relay Box
The Rada Pulse Relay Box is designed to be connected to the auxiliary outputs of the
Rada Pulse Control Box. It provides three switched power relays to enable the Pulse
system to be used in conjunction with equipment such as pumps, lights and fans.
All three relay outputs are fuse protected. The Rada Pulse Hand Held Programmer
is required to enable these functions to be used.
4.2 Rada Pulse Hand Held Programmer
The Rada Pulse Hand Held Programmer is required to modify the default settings
within the Rada Pulse Control Box. The programmer has an extendable lead which
plugs into a socket in the top of the Control Box.
The programmer has a two line (alpha numeric) backlit display and push buttons to
allow the user to navigate through the menu choices and set the conguration data.
Parameters such as activation time, delay time and post ush waiting time etc, can
be programmed for each outlet.
The controller is multilingual and the user can select the appropriate language via
the menu system.
4.3 Rada Disable Key Switch
The Rada Disable Key Switch is a key operated isolation switch designed to be used
with the Rada Pulse Control Box. The unit is wired directly to the Pulse Control Box
and disables the system for cleaning and maintenance.
4.4 Rada Pulse Key Switch
The Rada Pulse Key Switch is a key operated isolation switch designed to be used
with the Rada Pulse Control Box. The unit replaces a sensor for the purpose of
manually turning on the system e.g. group showering.
4.5 Rada Mounting Plate 129
The mounting plate is intended to be used when mounting the Rada Pulse 129
sensor onto difcult walls or surfaces, or where extra security screws need to be
used (not supplied).
The mounting plate is a plated brass ring, pre-drilled, to allow secure xing of the
Rada Pulse 129 sensor. The plate is drilled to allow wall installation or xing onto a
junction box, and is supplied with 2 x M5 x 12 mm stainless steel screws, to secure the
Rada Pulse 129 sensor (Wall screws and junction box screws are not supplied).

7
The installation and maintenance of these products must be carried out in accordance
with the instructions given in this manual, and must be conducted by designated,
qualied and competent personnel.
Installations must comply with all current building, water, plumbing and electrical
regulations and guidelines.
The products are not designed to be vandal-resistant, subjected to extremes of
temperature, unauthorised tampering or wilful abuse.
Rada products are precision-engineered and should give continued superior and
safe performance, provided:
1. They are installed, commissioned, operated and maintained in accordance with
the recommendations given in this Manual.
2. Periodic attention is given, as necessary, to maintain the product in good functional
order. Recommended guidelines are given in section: 'Maintenance'.
SAFETY : WARNINGS

8
4 x Sealing Washers (not illustrated)
PACK CONTENTS
Tick the appropriate boxes to familiarise yourself with the part names and to
conrm that the parts are included.
2. Rada Pulse Sensors
2.1 Rada Pulse 120/122 Sensor
1 x Rada Pulse 120 or 122 Sensor, complete with 3 metres of 2 core cable
2 x Wall Plugs
2 x Fixing Screws
1 x 2.5 mm
Hexagon Wrench
1 x Plug-in
Connector
1 x Cable Gland
2 x 3MTM Connectors
1. Rada Pulse Control Box
Documentation
1 x Installation Template
1 x Rada Pulse Control Box
4 x Fixing Screws (not illustrated)
4 x Wall Plugs (not illustrated)

9
1 x Rada Pulse LR Sensor,
complete with 3 metres of 2 core cable
1 x Rada Pulse LR
Sensor Backplate
2.2 Rada Pulse 129 Sensor
2.3 Rada Pulse LR Sensor
1 x Rada Pulse 129 Sensor,
complete with 3 metres of 2 core cable
2 x Fixing Screws
2 x Wall Fixings
1 x 2.5 mm Hexagon
Wrench
1 x Plug-in Connector
1 x Plug-in Connector
1 x Cable Gland
1 x Cable Gland
2 x 3MTM Connectors
2 x 3MTM Connectors
2 x M6 x 175 mm Fixing
Studs (with ttings)
(Rada Mounting Plate 129 -
Optional Accessory)
1 x Rada Mounting Plate
1 x 2.5 mm Hexagon Wrench
2 x Screws M5 x 12 mm

10
3. Solenoid Valves
3.1 Rada SV1015 (HP) Solenoid Valve
1 x SV1015 Solenoid Valve
1 x Cable Gland
1 x Plug-in Connector
2 x Flat-faced Inserts
3.2 SV2022 Solenoid Valve
1 x SV2022 Solenoid Valve
1 x Cable Gland
1 x Plug-in Connector
1 x Electrical Connector
1 x Electrical Connector
2.4 Rada Pulse 124, 125, 126 Ceiling Sensor
1 x Plug-in
Connector
1 x Cable Gland
2 x Spade
Connectors
2 x M3 x 20 mm Screws (not illustrated)
2 x M3 x 50 mm Screws (not illustrated)
1 x Rada Pulse 124, 125 or 126 Ceiling
Sensor, complete with 3 metres of 2 core cable

11
3.4 SV3022 Solenoid Valve
1 x SV3022 Solenoid Valve
1 x Electrical Connector
3.3 SV2028 Solenoid Valve
1 x SV2028 Solenoid Valve
1 x Cable Gland
1 x Plug-in Connector
1 x Electrical Connector
1 x Cable Gland
1 x Plug-in Connector

12
DIMENSIONS
300 mm 117 mm
230 mm
1. Rada Pulse Control Box
84 mm
Diameter 6 mm
12 mm
68 mm
6 mm
22 mm
84 mm
2. Rada Pulse Sensors
2.1 Rada Pulse 120/122 Sensor
2.2 Rada Pulse 129 Sensor
68 mm 5 mm
84 mm
Diameter
52 mm Dia.
(Rada Mounting Plate 129
- Optional Accessory)

13
2.4 Rada Pulse 124, 125, 126 Sensor
2.3 Rada Pulse LR Sensor
55 mm
15 mm 78 mm dia
128 mm dia
9.5 mm to 25 mm
16 mm
Note! The M6 xing studs supplied allow the LR sensor to be attached through a
wall to a maximum thickness of 165 mm. If longer M6 xing studs are required, these
will have to be purchased through your local supplier.
Finished Wall
170 mm maximum
75 mm
75 mm

14
3.2 SV2022 Solenoid Valve
55 mm 75 mm
75 mm
3.3 SV2028 Solenoid Valve
72 mm 96 mm
85 mm
18 mm
20 mm
3. Solenoid Valves
3.1 SV1015 (HP) Solenoid Valve
127 mm
78 mm
14 mm

15
3.4 SV3022 Solenoid Valve
82 mm 75 mm
90 mm
18 mm

16
1. Rada Pulse Control Box
Material: Plastic sealed to IP54.
Voltage: 230 V AC, 50/60 Hz.
Transformer: 230 V AC/12 V AC.
Rating: 120 VA.
Main Fuse: T 2.5 A H 250 V
(Important! Use only Rada Approved Fuse, Part No. 422.84)
10 x Inputs suitable for Pulse Sensors.
10 x Solenoid Outputs, 12 V AC SELV (5 fuses) - fused at 2.5 A for each pair.
Door Switch Input (normally closed)
Disable Switch Input (normally open)
Disinfection Enable Input
3 x Auxiliary Outputs, 12V AC SELV (1 fuse) - fused at 400 mA, for connection to
Rada Pulse Relay Box:
Fan Output•
Light Output•
Pump Output•
1 x Disinfection Valve Output
Ambient Temperature Range: 0 - 40°C.
Maximum Humidity: 80% at 25°C.
Type of action: Type 1.
Suitable for continuous use.
Software/Firmware: Class A control function.
2. Rada Pulse Sensors
2.1 Rada Pulse 120/122 Sensors
Material: Plastic shell, Finish: Chrome plated.
3 m of 2 core sheathed cable with connections sealed into the sensor.
Operating voltage: 12 V AC. via the 2 core cable.
Fixing holes for 2 x 6 mm dome headed screws (supplied).
Protection: IP67.
Temperature range: 4 to 70°C.
Activation distance -120 sensor 0 to 50 mm.
-122 sensor 0 to 550 mm.
The distance is dependent on the reectivity of the detected object.
SPECIFICATIONS

17
2.2 Rada Pulse 129 Sensor
Material: Brass. Finish: Chrome plated.
3 m of 2 core sheathed cable with connections sealed into the sensor.
Operating voltage: 12 V AC. via the 2 core cable.
Fixing holes for 2 x 6 mm counter sunk screws (supplied).
Temperature range: 4 to 70°C.
Protection: IP65.
Activation distance: 0 mm to 50 mm depending on the reectivity of the detected
object.
(Rada Mounting Plate 129 - Optional Accessory)
Material: Brass. Finish: Chrome plated.
Fixing holes for 2 x 6 mm c/sk screws to wall/panel (Screws not supplied), and drilled
for 2 x 4 mm screws to secure to a junction box, if required.
Supplied with 2 x screws M5 x 12 mm (stainless steel) with hexagon slot and a
2.5 mm A/F hexagon wrench.
2.3 Rada Pulse LR Sensor
Material: Brass. Finish: Chrome plated.
3 m of 2 core sheathed cable with connections sealed into the sensor.
Operating voltage: 12 V AC. via the 2 core cable.
2 x M6 x 175 mm xing studs (rear xing)
Temperature range: 4 to 70°C.
Protection: IP65.
Activation distance: 0 mm to 50 mm depending on the reectivity of the detected
object.
2.4 Rada Pulse 124, 125 and 126 Ceiling Sensor
Rada 124 for washbasin
Rada 125 for single urinal
Rada 126 for group urinal
Material: Base and cover ABS.
Supply voltage: 12 V AC. via the 2 core cable.
Maximum humidity: 80% at 30°C.
Operating ambient temperature range: 0 - 35°C.

18
Extension cable - Optional Accessory
3.0 metres of sheathed cable and two 3MTM connectors. Use to extend any Rada
Pulse sensor to a maximum of 6.0 metres.
3. Solenoid Valves
General
Operating voltage (see note) 10.2 to 13.5 Volts AC.
Note! Operation over the full range of pressure and operating voltage is guaranteed
for uid temperature up to 70°C.
Between 70°C and 90°C the following restrictions apply:
The installer must ensure that a minimum voltage of 12 V is present across the coil
to make sure that the valve will open over the full pressure range.
Maximum ambient temperature 40°C.
Maximum uid temperature for 100% full range operation 70°C.
Maximum combined uid and ambient temperature 130°C.
3.1 Rada SV1015 (HP) Solenoid Valve
Supply Voltage: 12 V AC, 50/60 Hz.
Rating: 5 VA.
Body Material: PA66 Reinforced Fibreglass
Connections: 15 mm compression connections.
1/2" BSP union connections (with at-faced inserts).
Min / Max Pressures: 20 to 1000 kPa (0.2 to 10 bar).
Inlet Isolating Valve: Brass ball valve (supplied).
Type: Servo assisted.
2.5 m
0.4 m 0.4 m
0.4 m
2.5 m
3.0 m
Sensor detection area for single
urinal applications (125 sensor)
Sensor detection area for group
urinal applications (126 sensor)
Sensor detection area for single
basin applications (124 sensor)
2.5 m Max
124, 125 and 126 Sensor Detection Area Diagrams

19
3.2 SV2022/SV2028 Solenoid Valve
Supply Voltage: 12 V AC, 50/60 Hz.
Rating: 8 VA.
Body Material: Brass.
Connections: SV2022 3/4" BSP female connections.
SV2028 1" BSP female connections.
Min / Max Pressures: 20 to 1000 kPa (0.2 to 10 bar).
Type: Servo assisted.
3.3 SV3022 Solenoid Valve
Note! A maximum of 5 SV3022 Solenoid Valves may be used on one Rada Pulse
control system.
Supply Voltage: 12 V AC, 50/60 Hz.
Rating: 13 VA.
Body Material: Brass.
Connections: 3/4" BSP female connections.
Min / Max Pressures: 0 - 800 kPa (0 - 8 bar).
Type: Lift assisted.
Maximum cable runs for solenoid connections are as follows:
SV1015
Cable Size mm2Max Length in Metres
0.50 27
0.75 40
1.0 53
2.0 104
SV2022
SV2028
SV3022
Cable Size mm2Max Length in Metres
0.50 7.5
0.75 10.5
1.0 14
2.0 28

20
INSTALLATION
General
The installation and maintenance of Rada Pulse products must be carried out in
accordance with the instructions and information given in this Product Manual, and
must be conducted by designated, qualied and competent personnel.
1. Before commencing installation refer to section: 'Specications'.
2. Care must be taken during installation to prevent any risk of injury or
damage.
3. In accordance with IEE regulations all electrical connections must be undertaken
by a competent person.
Important! Cross bond copper pipework to maintain earth continuity when
nylon housed solenoid valve SV1015 is tted.
4. Isolate mains voltage supply before removing cover.
5. The installations must comply with all current Building and Electrical Regulations
in force, and relevant Guidelines.
6. The products must not be subjected to extremes of moisture or temperature,
unauthorised tampering or wilful abuse.
7. Rada solenoid valves require a 12 V AC electrical supply, provided by the
transformer housed within the Rada Pulse Control Box.
Warning! Do not connect the solenoid valves to mains voltage.
Note! The Rada Pulse system control box can power a maximum of ve SV3022
solenoid valves. These must be controlled by alternate power outputs on the
Pulse system control box, (e.g. channel 1,3,5,7 and 9).
8. The plumbing must comply with the local requirements of the Water Authority
Undertaker.
9. Isolating valves are recommended to allow servicing of the solenoid valve.
These should be plumbed in so no user operation can occur (Note: no other
user operated control should be tted between the solenoid and the outlet
tting.
10. A thermostatic mixing valve should be installed to provide blended water to the
outlets. The mixing valve should be tted with isolating valves, check valves
and lters with a mesh not exceeding 0.3 mm aperture size.
11. Rada Pulse Solenoid Valves must be approved to EN 60730-2-8.
This manual suits for next models
7
Table of contents
Other rada Control Unit manuals
Popular Control Unit manuals by other brands

Watts
Watts LFU5B-Z3 installation guide

Johnson Controls
Johnson Controls Mercury 3 Series Hardware installation

ICP DAS USA
ICP DAS USA FR-32R user manual

Honeywell
Honeywell Hometronic HB 05 Mounting and operation instructions

Irritrol
Irritrol RD-600 Installation and programming guide

Draper
Draper LVC-IV Wiring instructions