manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Regin
  6. •
  7. Thermostat
  8. •
  9. Regin RU-DFO User manual

Regin RU-DFO User manual

Other Regin Thermostat manuals

Regin MTIS Series User manual

Regin

Regin MTIS Series User manual

Regin RCF-230CD User manual

Regin

Regin RCF-230CD User manual

Regin PULSER User manual

Regin

Regin PULSER User manual

Regin AL230A User manual

Regin

Regin AL230A User manual

Regin TM1-50 User manual

Regin

Regin TM1-50 User manual

Regin MTIB User manual

Regin

Regin MTIB User manual

Regin RCF-230D User manual

Regin

Regin RCF-230D User manual

Regin TM1-P User manual

Regin

Regin TM1-P User manual

Regin RCFD-230C User manual

Regin

Regin RCFD-230C User manual

Regin TM1-P User manual

Regin

Regin TM1-P User manual

Regin DTTH User manual

Regin

Regin DTTH User manual

Regin TH-RV468 User manual

Regin

Regin TH-RV468 User manual

Regin RCFM-230D User manual

Regin

Regin RCFM-230D User manual

Regin MTIBL90H User manual

Regin

Regin MTIBL90H User manual

Regin REGIO RC-DFO User manual

Regin

Regin REGIO RC-DFO User manual

Regin MTIR30S User manual

Regin

Regin MTIR30S User manual

Regin RCF-230D User manual

Regin

Regin RCF-230D User manual

Regin REGIO RC-O User manual

Regin

Regin REGIO RC-O User manual

Regin RRT025A User manual

Regin

Regin RRT025A User manual

Regin Regio Mini Series User manual

Regin

Regin Regio Mini Series User manual

Regin Floorigo FL1TP User manual

Regin

Regin Floorigo FL1TP User manual

Regin RCFD-230C User manual

Regin

Regin RCFD-230C User manual

Regin ED-T43L-V User manual

Regin

Regin ED-T43L-V User manual

Regin REGIO RC-TO User manual

Regin

Regin REGIO RC-TO User manual

Popular Thermostat manuals by other brands

Full Gauge TIC-17C product manual

Full Gauge

Full Gauge TIC-17C product manual

Imit Chronomix S manual

Imit

Imit Chronomix S manual

ChiliTec ST-35 ana instruction manual

ChiliTec

ChiliTec ST-35 ana instruction manual

Salus VS05 Installer's/user's manual

Salus

Salus VS05 Installer's/user's manual

Azel D-500 user guide

Azel

Azel D-500 user guide

Honeywell Chronotherm III owner's manual

Honeywell

Honeywell Chronotherm III owner's manual

Charmeg MP-R user manual

Charmeg

Charmeg MP-R user manual

dixell WING XW40LS Installing and operating instructions

dixell

dixell WING XW40LS Installing and operating instructions

Network Thermostat NetX X7C-WIFI Installation and programming manual

Network Thermostat

Network Thermostat NetX X7C-WIFI Installation and programming manual

Radio Thermostat CT80 Operation guide

Radio Thermostat

Radio Thermostat CT80 Operation guide

HAI Omnistat RC-120 installation manual

HAI

HAI Omnistat RC-120 installation manual

Lennox iComfort E30 Installation and setup guide

Lennox

Lennox iComfort E30 Installation and setup guide

Lux Products PSD011Ba Installation and operating instructions

Lux Products

Lux Products PSD011Ba Installation and operating instructions

Computherm Q20 operating instructions

Computherm

Computherm Q20 operating instructions

Heatmiser neoStat user manual

Heatmiser

Heatmiser neoStat user manual

Mars HEAT CONTROLLER IR Wireless Thermostat user manual

Mars

Mars HEAT CONTROLLER IR Wireless Thermostat user manual

LUX LP0511D user manual

LUX

LUX LP0511D user manual

Saswell SAS920XWHB-7-S-RF User manual and warranty card

Saswell

Saswell SAS920XWHB-7-S-RF User manual and warranty card

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

HEAD OFFICE SWEDEN
Phone: +46 31 720 02 00
Web: www.regincontrols.com
E-Mail: [email protected]
Revision 2019-05-27
— 1 —
RU-DFO
RU-DFO
Room unit with display and fan button
for use with RCP
RU-DFO is a room unit intended for use together
with Regio Maxi controllers. 9Simple installation
9Built-in temperature sensor
9Backlit display
9Cable for connection between the room
unit and the RCP controller is available as
accessory
Function
RU-DFO is a room unit from the Regio series with display
and fan button for controlling a three-speed fan (fan coil).
It should be connected to one of the Regio Maxi control-
lers RCP100F, RCP100FT, RCP200F or RCP200FT.
Regio
Regio is a wide series of controllers which handle heating
and cooling.
The controllers are divided into three different series,
Mini, Midi and Maxi. Mini are pre-programmed,
stand-alone controllers. The Midi controllers are pre-
programmed with communication. The Maxi group, to
which RU-DFO belongs, consists of freely programmable
controllers with communication.
Applications
The Regio controllers are suitable in buildings where you
want optimal comfort and low energy consumption, for
example offices, schools, shopping centres, airports, hotels
and hospitals etc.
Sensor
The room unit has a built-in sensor.
Easy to install
The modular design with a separate bottom plate for
wiring makes the whole Regio series easy to install and
commission. The bottom plate can be put into place be-
fore the electronics are installed. Mounting is directly on
the wall or on an electrical connection box.
Connection to RCP
The room unit is connected to the RCP-unit with an
RJ12-cable, max length 30 m. Regin has two cables as
accessories, RU-CBL3 (length 3 m) and RU-CBL10
(length 10 m).
HEAD OFFICE SWEDEN
Phone: +46 31 720 02 00
Web: www.regincontrols.com
E-Mail: [email protected] — 2 —
RU-DFO
Display handling
The display has the following indications:
Occupancy
indication
Open window
Indoor /
outdoor
temp.
Setpoint
Forced ventilation
Changeable value
Current room
temperature
in °C to one
decimal point
COOL/HEAT:
Shows if the unit controls
according to the heating
or cooling setpoint
OFF: Unoc-
cupied (also
shows tem-
perature) or
O󰀨
indication
(only OFF)
STANDBY:
Standby indication
SERVICE:
Parameter setting
Fan
Auto/Man.
indication
for the fan
Current
fan speed
(0, 1, 2, 3)
It is possible to set different parameter values in a para-
meter menu in the display, using the buttons on the con-
troller. You change parameter values with the INCREASE
and DECREASE buttons and confirm changes with the
Occupancy button.
INCREASE
DECREASE
Occupancy button
The Occupancy button
If you press the Occupancy button for less than 5 seconds
when the controller is in the preset operating mode
(Occupied or Stand-by), the controller changes to opera-
ting mode Bypass. It will automatically return to the pre-
set operating mode after a configurable time (FS=2 hours).
If you press the button for less than 5 seconds when the
controller is in Bypass, it changes operating mode to the
preset operating mode.
When the Occupancy button is held depressed for more
than 5 seconds, the controller changes operating mode to
”Shutdown” (Off/Unoccupied), regardless of the current
operating mode. Via the display, you can configure which
operating mode, Off or Unoccupied, should be activated
on ”Shutdown” (FS=Unoccupied). If you press the
Occupancy button for less than 5 seconds in Shutdown,
the controller returns to Bypass.
Forced ventilation
Regio has a built-in function for forced ventilation. A
short press on the Occupancy button activates the output
that has been configured for forced ventilation, for exam-
ple for a damper.
Setpoint
In Occupied mode, the controller operates from a heating
setpoint (FS=22°C) or a cooling setpoint (FS=24°C) that
can be changed using the INCREASE and DECREASE
buttons.
Pressing on INCREASE increases the current setpoint by
0.5°C with each press up to the max. limit (FS = +3°C).
Pressing on DECREASE decreases the current setpoint by
0.5°C with each press down to the min. limit (FS = -3°C).
Switching between heating and cooling setpoints is done
automatically in the controller depending on the heating
and cooling requirement.
Fan control
RU-DFO has a fan button. When you press the button,
a symbol is shown in the display for 10 seconds. During
this time, it is possible to change the fan speed using the
INCREASE/DECREASE buttons.
The controller has the following positions:
Auto Automatic control of the fan speed to maintain
desired room temperature.
0Fan off.
IManual position with low speed.
II Manual position with medium speed.
III Manual position with high speed.
In operating modes Off and Unoccupied, the fan is
stopped, regardless of the setting in the display.
HEAD OFFICE SWEDEN
Phone: +46 31 720 02 00
Web: www.regincontrols.com
E-Mail: [email protected]
Revision 2019-05-27
HEAD OFFICE SWEDEN
Phone: +46 31 720 02 00
Web: www.regincontrols.com
E-Mail: [email protected] — 3 —
RU-DFO
— 3 —
RU-DFO
Technical data
Supply voltage Fed from RCP
Ambient temperature 0...50°C
Storage temperature -20...+70°C
Ambient humidity Max 90 % RH
Protection class IP20
Communication Same as RCP
Built-in temperature sensor NTC type, measuring range 0...50°C, accuracy ±0.5°C at 15...30°C
Material, casing Polycarbonate, PC
Weight 110g
Colour Signal white RAL 9003
Cables
Cable for connection between RU and RCP Type RJ12, max length 30 m
Cables that can be ordered from Regin RU-CBL3 (length 3 m)
RU-CBL10 (length 10 m)
CE
This product carries the CE mark. For more information, see www.regincontrols.com.
Inputs and outputs
In RCP
Terminal blocks in RCP So-called lift type for cable cross-section 2.1 mm2
Setpoint settings via Regio tool© or in the display
Basic heating setpoint 5...40°C
Basic cooling setpoint 5...50°C
Setpoint displacement ±0...10°C (FI=±3°C)
HEAD OFFICE SWEDEN
Phone: +46 31 720 02 00
Web: www.regincontrols.com
E-Mail: [email protected]
HEAD OFFICE SWEDEN
Phone: +46 31 720 02 00
Web: www.regincontrols.com
E-Mail: [email protected]
Revision 2019-05-27
— 4 —
RU-DFO
— 4 —
RU-DFO
Wiring
Terminal Designation Function
10-33 No function
40 +5 V +5 V supply voltage from RCP
41 N (0 V) 0 V supply voltage from RCP
42 A RU-Bus A
43 B RU-Bus B
Dimensions
Product documentation
The product documentation can be downloaded from www.regincontrols.com.
95
28
60 68
mm