REGULUS - R0BC Hot Water Storage Tanks - www.regulus.eu
6 - Installation and Commissioning
Installation must meet valid rules and may be done only by qualied staff. The tank shall be placed on the
oor, as close to the heat source as possible.
Warning: Defects caused by improper installation, use or handling are not covered by warranty.
6.1 - Connection to heat sources
Connect heating circuits to the inlet and outlet of the external heat exchanger*. The heat source for the tank -
external heat exchanger - connect with G 5/4” couplings to the two sleeves.
6.2 - Connection to a solar system
The tank can be used with a solar system. In such a case, the inlet for hot heat-carrying liquid coming from
the solar system shall be connected to the 2 lower sleeves (G 5/4”) via an external heat exchanger. The
lower G 5/4“ outlet connects to the return piping from the external solar heat exchanger, another G 5/4“outlet
connects to the inlet for hot heat-carrying liquid from the external heat exchanger (see section 5). Insulate all
the piping between the tank and the solar system.
6.3 - Heating rod installation
The G 6/4“ side sleeve is designed to accommodate an electric heating rod. Heating rods of output up to 12 kW
can be used (depending on the tank diameter and rod length), connected either directly to the mains (thermostat-
equipped rods), or to a heating system controller. The installation may be done by qualied staff only.
Warning: Electric heating elements shall be protected by a safety thermostat.
6.4 - Connection to water mains
DHW piping shall be done according to valid rules. G 6/4” threaded couplers are used to connect the tank
to a cold water inlet and hot water outlet (G 2” for volumes of 1000l and over). A 6bar safety valve shall
be installed at the cold water inlet. Installation of a reducing valve to the tank inlet is recommended. If the
pressure from water mains exceeds 6 bar, a reducing valve is necessary. In order to prevent water loss, an
expansion tank should be installed at the cold water inlet as well (8 l volume for R0BC 200, 12 l volume for
R0BC 300 18 l volume for R0BC 400, 24 l volume for R0BC 500, 35 l volume for R0BC 750, 50 l volume
for R0BC 1000, 60 l volume for R0BC 1500, 80 l volume for R0BC 2000, 100 l volume for R0BC 2500 l and
2×60 l volume for R0BC 3000).
Should the water be too hard, install a water softener before the tank. In case the water contains mechanical
impurities, install a strainer.
A suitable thermostatic mixing valve should be installed at the hot-water outlet from the tank, preventing too
hot water from entering the taps.
Install a drain valve to the lowest point of the tank.
Complete DHW piping shall be properly insulated.
6.5 - Electronic anode rod installation
A so called electronic anode rod can be used instead of the magnesium one. Its principle advantage is that
its proper function is signaled by an indication lamp while a magnesium anode rod needs to be taken out for
check. In such a case, just visual check of the indication lamp is sufcient.
A space equal to the anode length (see the table below) is needed between the tank top and ceiling to install/
exchange the electronic anode rod. In order to protect the tank properly and meet its warranty conditions,
select an anode from the table below.
* external heat exchangers are not included in the scope of supply of R0BC tanks.