Reliable G5-56 Manual

The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Bulletin 034 Rev. B
Bulletin 034 Rev. B
Model G5-56, Model G5-42,
Model G5-28
Quick Response Concealed
Automatic Sprinkler
UL Quick Response
FM Standard Response
Concealed Sprinkler With a
3/4” (19mm) Adjustment
Features
1. Cover plate attachment (Plain or Perforated) with
¾” (19mm) assembly adjustment.
2. Smooth aesthetic ceiling profile.
3. Factory installed protective cap.
4. Available in Chrome and White as Standard Finish-
es. Special Application Finishes are also available.
5. Ordinary and Intermediate temperature rating.
For additional Sprinklers refer to Bulletin 154 for
Technical Specification and Approvals
Approvals & Listings
1. Underwriters Laboratories Inc. and cULus -
Quick Response
• G5-56 - Light Hazard and Ordinary Hazard
Occupancies
• G5-42 - Light Hazard Occupancies
• G5-28 - Light Hazard Occupancies
2. Factory Mutual Research Corp. (FM) -
Standard Response (See Page 3)
• See the most recent FM Global Property
Loss Prevention Data Sheets for installation
and use guidelines.
3. Loss Prevention Council (LPCB, UK) -
Standard Response
• G5-56 - Light Hazard and Ordinary Hazard
Occupancies
4. VdS Schadenverhütung GmbH -
Standard Response
5. EC-Certificate of Conformity 0832-CPD-2062
U.S. Patent number 6,554,077.
Application
The Reliable Model G5-56, G5-42 and G5-28 are the most
versatile quick response concealed sprinklers available. It
provides the best form of fire protection while offering an at-
tractive appearance and 3/4” (19mm) of cover adjustment for
ease of installation. The small diameter cover plate assem-
bly is easily attached and blends into the ceiling, concealing
the most dependable fire protection available, an automatic
sprinkler system.
The Model G5-56, G5-42 and G5-28 are designed for use
where aesthetic appearance is important. Offices, hospitals,
motels and restaurants are but a few of the applications where
it can be used.
The Model G5-56, G5-42 and G5-28 are UL Listed Quick
Response Concealed sprinklers intended for use in accor-
dance with NFPA 13. FM Approves the G5-56 and the G5-28
sprinkler as a standard response concealed sprinkler intended
for use in accordance with FM Loss Prevention Data Sheet 2.0.
Product Description
The Reliable Model G5-56, G5-42 and G5-28 uses a proven
quick response fusible element in a standard style sprinkler
frame with a drop-down deflector. This assembly is recessed
into the ceiling and concealed by a flat cover plate assem-
bly. The threaded engagement provides ¾” (19mm) of cover
adjustment. The flat cover plate is attached to the skirt using
either 135°F (57°C) or 165°F (74°C) ordinary temperature clas-
sification solder.
When the ceiling temperature rises, the solder holding the
flat cover plate melts, the flat cover plate released thus expos-
ing the sprinkler inside to the rising ambient temperature.
The subsequent fusing of the element opens the waterway
and causes the deflector to distribute the water. Any secure
engagement between the cover plate and cup will assure that
the drop-down deflector is properly located below the ceiling.
Plain Cover Plate
Perforated Cover Plate
Installation
Do not install the G5-56, G5-42 and G5-28 in ceilings which
have positive pressure in the space above.
• Cut a 25
/
8” inch (67mm) diameter hole is cut in the ceiling, the
sprinkler is easily installed with the Model FC Wrench. The
wrench has a socket drive which is inserted into the body of
the sprinkler. When installing a sprinkler the wrench is first
positioned into the sprinkler/cup assembly until the wrench
socket engages the body of the sprinkler. The sprinkler is
then tightened into the pipe fitting. When inserting or remov-
ing the wrench from the sprinkler/cup assembly, care should
be taken to prevent damage to the sprinkler. DO NOT
WRENCH ON ANY OTHER PART OF THE SPRINKLER/
CUP ASSEMBLY. Install the cover plate by hand turning the
cover in the clockwise direction until it is tight against the ceil-
ing.
A protective cap is provided to protect the drop-down sprinkler
deflector from damage which could occur during construction
before the cover plate is installed. The cap is factory installed
inside the sprinkler cup. Remove cap to install sprinkler, then re-
install cap until the cover plate is installed.
Maintenance
The Model G5-56, G5-42 and G5-28 should be inspected
quarterly and the sprinkler system maintained in accordance
with NFPA 25. Do not clean sprinklers with soap and water, am-
monia or any other cleaning fluids. Remove any sprinkler that
has been painted (other than factory applied) or damaged in
any way. Concealed sprinklers cover plates can not be painted
in the field, after installation or have any other coating applied
other than the factory finish. A stock of spare sprinklers should
be maintained to allow quick replacement of damaged or oper-
ated sprinklers. Prior to installation, sprinklers should be main-
tained in the original cartons and packaging to minimize the
potential for damage to sprinklers that would cause improper
operation or non-operation.
UL Listing Category
Sprinklers, Automatic and
Open
Quick Response Sprinkler
UL Guide Number
VNIV
Maximum Working Pressure
175 psi (12 bar)
100% Factory tested Hydrostatically to 500 psi (34.5 bar)
Temperature Rating
Classification Sprinkler Cover
Plate
Max. Ambient
Temp.
Ordinary 165°F/74°C 135°F/57°C 100°F/38°C
Intermediate 212°F/100°C 165°F/74°C 150°F/66°C
Model FC Sprinkler Wrench
Ordering Information
1. Sprinkler Model
2. Nominal Orifice
3. Flat Cover Plate
Plain or Perforated
4. Flat Cover Plate
Assembly Finish
5. Inlet Type
Cover Plate Finishes(1)
Standard Finishes
Chrome
White Paint
Special Application
Finishes(2)
Bright Brass
Finished Bronze
Black Plating
Black Paint
Off White
Satin Chrome
(1) Other finishes and colors are
available on special order.
Consult factory for details.
Coverplate custom paint is
semi-gloss, unless specified
otherwise.
(2) For the perforated style cover-
plate, consult factory for avail-
ability on these and other cus-
tom finishes.
2.
Technical Data
Sprinkler
Model Sprinkler Inlet Total
Adjustment
Nominal
Orifice
Nominal
K Factor Thread Approvals Sprinkler
Identification (SIN)
US Metric
G5-56 Non Adjustable ¾” (19mm) ½” (15mm) 5.6 80 ½” NPT (R½) 1,2,3,4,5 RA3415
G5-42 Non Adjustable ¾” (19mm) 7
/
16” (10mm) 4.2 60 ½” NPT (R½) 1 RA3413
G5-28 Non Adjustable ¾” (19mm) 3
/
8” (10mm) 2.8 40 ½” NPT (R½) 1,2 RA3411
For VdS Approval, temperature rating sprinkler 165°F/74°c and cover plate 135°F/57°C only!
Notice
FOR USE AS A REPLACEMENT OF MODEL G4A SPRINKLERS
NOTE:
1. Testing has shown that use of a “nipple extension” will not affect the listing of the sprinkler.
2. For RETROFIT installations, per NFPA 13 (2010) section 8.15.19.4, “which allows the use of nipples as the same pipe
thread size as the existing outlet when revamping existing systems”.
3. Do not exceed 8-18 ft-lbs of torque during installation.
3.
The Reliable Automatic Sprinkler Co., Inc.
(800) 431-1588 Sales Offices
(800) 848-6051 Sales Fax
(914) 829-2042 Corporate Offices
www.reliablesprinkler.com Internet Address
Manufactured by
Recycled
Paper
Revision lines indicate updated or new data.
EG. Printed in U.S.A. 11/12 P/N 9999970421
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory
Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly
qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.
• Automatic sprinklers
• Flush automatic sprinklers
• Recessed automatic sprinklers
• Concealed automatic sprinklers
• Adjustable automatic sprinklers
• Dry automatic sprinklers
• Intermediate level sprinklers
• Open sprinklers
• Spray nozzles
• Alarm valves
• Retarding chambers
• Dry pipe valves
• Accelerators for dry pipe valves
• Mechanical sprinkler alarms
• Electrical sprinkler alarm switches
• Water flow detectors
• Deluge valves
• Detector check valves
• Check valves
• Electrical system
• Sprinkler emergency cabinets
• Sprinkler wrenches
• Sprinkler escutcheons and guards
• Inspectors test connections
• Sight drains
• Ball drips and drum drips
• Control valve seals
• Air maintenance devices
• Air compressors
• Pressure gauges
• Identification signs
• Fire department connection
Reliable offers a wide selection of sprinkler components. Following are some of the many
precision-made Reliable products that guard life and property from fire around the clock.
Reliable...For Complete Protection

This manual suits for next models

2

Other Reliable Irrigation System manuals

Reliable F156 Series User manual

Reliable

Reliable F156 Series User manual

Reliable G5 Series User manual

Reliable

Reliable G5 Series User manual

Reliable F1FR-SS Series User manual

Reliable

Reliable F1FR-SS Series User manual

Reliable F4FR-NF Manual

Reliable

Reliable F4FR-NF Manual

Reliable G5 Series User manual

Reliable

Reliable G5 Series User manual

Reliable RFC43 LL User guide

Reliable

Reliable RFC43 LL User guide

Reliable RFC43 User manual

Reliable

Reliable RFC43 User manual

Reliable GFR Series User manual

Reliable

Reliable GFR Series User manual

Reliable F1FR – 300 User manual

Reliable

Reliable F1FR – 300 User manual

Reliable RFC30 LL User manual

Reliable

Reliable RFC30 LL User manual

Reliable F3QR56 User manual

Reliable

Reliable F3QR56 User manual

Reliable DH56 HSW-PL User manual

Reliable

Reliable DH56 HSW-PL User manual

Reliable F1FR User manual

Reliable

Reliable F1FR User manual

Reliable RFC30 User manual

Reliable

Reliable RFC30 User manual

Reliable F3-80 Series Manual

Reliable

Reliable F3-80 Series Manual

Reliable JL-17 User manual

Reliable

Reliable JL-17 User manual

Reliable RFS42 User guide

Reliable

Reliable RFS42 User guide

Reliable G User manual

Reliable

Reliable G User manual

Reliable F1FR56 User manual

Reliable

Reliable F1FR56 User manual

Reliable MBEC-14 Manual

Reliable

Reliable MBEC-14 Manual

Reliable F1FR40 Manual

Reliable

Reliable F1FR40 Manual

Reliable F156 Series Manual

Reliable

Reliable F156 Series Manual

Reliable F1FR56-300 QREC Series User manual

Reliable

Reliable F1FR56-300 QREC Series User manual

Reliable SWC Manual

Reliable

Reliable SWC Manual

Popular Irrigation System manuals by other brands

Netafim NETBEAT user manual

Netafim

Netafim NETBEAT user manual

Nelson PC-S3000 quick start guide

Nelson

Nelson PC-S3000 quick start guide

Tyco ESFR-1 General description

Tyco

Tyco ESFR-1 General description

Tyco Fire Product Star SG300 instruction manual

Tyco Fire Product

Tyco Fire Product Star SG300 instruction manual

Netafim MegaNet 15D user manual

Netafim

Netafim MegaNet 15D user manual

Toro 570Z PRX Series Specifications

Toro

Toro 570Z PRX Series Specifications

Nelson Traveling Sprinkler Assembly and operating instructions

Nelson

Nelson Traveling Sprinkler Assembly and operating instructions

Tyco Fire Product Star Pulsar S160QR instruction manual

Tyco Fire Product

Tyco Fire Product Star Pulsar S160QR instruction manual

Eden 94150EDAMZ manual

Eden

Eden 94150EDAMZ manual

Ebinger LEADER 25 Instruction booklet

Ebinger

Ebinger LEADER 25 Instruction booklet

GÜDE MP 120/5A/GJ manual

GÜDE

GÜDE MP 120/5A/GJ manual

MiniMax MS-1 Technical data sheet

MiniMax

MiniMax MS-1 Technical data sheet

Viking VK960 Technical data

Viking

Viking VK960 Technical data

IrriGreen Irrigreen2 Guide

IrriGreen

IrriGreen Irrigreen2 Guide

Motorola IRRInet-M DC owner's manual

Motorola

Motorola IRRInet-M DC owner's manual

Tyco TY-FRB Series Installation and operation manual

Tyco

Tyco TY-FRB Series Installation and operation manual

Rain Bird SR3003 manual

Rain Bird

Rain Bird SR3003 manual

Tyco TY-FRL Series Operation instructions

Tyco

Tyco TY-FRL Series Operation instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.