Installation
Reliable Model F1FR80 QREC series sprinklers must be installed
in accordance with NFPA 13 and the requirements of all authorities
having jurisdiction using the Reliable sprinkler installation wrench
specied in this bulletin. Any other wrench may damage the
sprinkler. The Models W2 and W4 wrenches have two sets of
jaws. Use the smallest set of jaws that t on the wrench flats
of the sprinkler. A leak free 3/4” (R3/4) sprinkler joint can be
obtained with a torque of 14-20 lb-ft (19 - 27 N.m) after applying
a thread sealant to the male threads of the sprinkler. Do not
tighten sprinklers over the maximum recommended installation
torque. Exceeding the maximum recommended installation
torque may cause leakage or impairment of the sprinkler.
Glass bulb sprinklers have orange bulb protectors or protective
caps to minimize bulb damage during shipping, handling and
installation. Reliable sprinkler installation wrenches are designed
to install sprinklers with bulb protectors in place. Remove the
bulb protector at the time when the sprinkler system is placed in
service for re protection. Removal of the bulb protector before
this time may leave the bulb vulnerable to damage. Remove bulb
protectors by undoing the clasp by hand. Do not use tools to
remove bulb protectors.
Wrenches
Model W2 (non-recessed)
Model W4 (recessed, concealed)
Maintenance
Reliable Model F1FR80 QREC series sprinklers should be
inspected and the sprinkler system maintained in accordance
with NFPA 25, as well as the requirements of any Authorities
Having Jurisdiction.
Prior to installation, sprinklers should remain in the original
cartons and packaging until used. This will minimize the potential
for damage to sprinklers that could cause improper operation or
non-operation.
Do not clean sprinklers with soap and water, ammonia liquid or
any other cleaning fluids. Remove dust by gentle vacuuming
without touching the sprinkler.
Replace any sprinkler which has been painted (other than factory
applied). A stock of spare sprinklers should be maintained to
allow quick replacement of damaged or operated sprinklers.
Failure to properly maintain sprinklers may result in inadvertent
operation or non-operation during a re event.
Standard Finishes Special Application Finishes
Sprinkler F1 and F2
Escutcheons
CCP Cover
Plate(2) Sprinkler F1 and F2
Escutcheons
CCP Cover
Plate(2)
Bronze Brass Chrome Electroless Nickel PTFE(3)(4) Bright Brass Bright Brass
Chrome Chrome White Paint Bright Brass Satin Chrome Satin Chrome
White Polyester(3) White Polyester Satin Chrome Custom Color
Polyester
Custom Color
Paint
Custom Color Polyester(3)
Notes:
1. Paint or any other coating applied over the factory nish will void all approvals and warranties.
2. The CCP assembly consists of a bronze sprinkler mounted in a galvanized steel cup with a nished cover plate.
3. cULus Listed as corrosion resistant.
4. FM Approved as corrosion resistant.
Finishes(1) Table E
Bulletin 148
October 2022
Page 7 of 8
www.reliablesprinkler.com