
2.
General Description
The Reliable Model H 1½” (40mm) PrePaK is a completely self-
contained, supervised preaction system that can be readily installed
within a floor space of 4.5 square feet. Installation of the PrePaK (not
including exterior devices, i.e., detectors and alarm bells) requires
just three piping connections: a 1½” (40mm) supply line, a 1½”
(40mm) system line, and a ¾” (20mm) drain line. Reference loca-
tions of these piping connections are shown in Figure 1. Also, two
120 VAC (or 220 VAC) electrical supply connections are required.
The Reliable Model H 1½” (40mm) PrePaK contains the following
components within its 64” H x 24” W x 27” D (162.6cm H x 61cm W
x 68.6cm D) gauge 12 steel enclosure:
• One Reliable Model H 1½” (40mm) Deluge Riser Assembly
(See Reliable Bulletin 507).
• One Reliable Model A-2 Pressure Maintenance Device (See
Reliable Bulletin 251).
• One Reliable Model G 2½” (65mm) Right-Check Valve™ w/
Preaction Trim Kit (See Reliable Bulletin 806).
• One Gast Model1 1HAB-11T-M100X HP Tank-Mounted Air
Compressor with 2 Gallon (7.6 liter) tank (See Reliable Bulletin
700).
• One Potter Model PFC-4410-RC Releasing Control Panel (See
Potter Manual #5403550).
• All required fittings, gauges, electrical connectors, and electri-
cal devices to utilize the system in single interlock, single inter-
lock cross-zoned, double interlock, and double interlock cross-
zoned applications.
The Reliable Model H utilizes the Potter Model PFC-4410-RC Re-
leasing Control Panel. This fully programmable, microprocessor
based releasing panel is Underwriters Laboratories, Inc. Listed and
is in compliance with NFPA 13 and NFPA 72. Because the PFC-
4410-RC is totally zone and output programmable, the Reliable
Model H PrePaK can be utilized in four different preaction applica-
tions without having to rewire any of the factory installed devices.
Once the previously described connections are completed, the 24
VDC detectors, output devices, and relay contacts may be con-
nected to achieve the desired system implementation.
The Model H PrePaK can be used in both single and double in-
terlock applications. Reliable Single and Double Interlock Preaction
Systems are designed for water sensitive areas, which require pro-
tection from inadvertent water flow into the sprinkler system piping.
The major benefits of a single and/or double interlock preaction
system, when compared with a wet pipe system, are as follows:
A. A fire alarm sounds prior to the flow of water from a sprin-
kler, which may enable extinguishing the fire by handheld
means before the operation of any sprinkler head occurs.
B. An annunciator signals whenever the integrity of piping or
sprinklers is accidentally or intentionally disturbed; however,
no water flow or water damage will result at that time.
C. Speedy detection and an early fire alarm are provided by
fire detectors, without the delay associated with water de-
livery time in the event of a fire. Note that with a wet pipe
system, the fire alarm is delayed until after water has begun
flowing from an operated sprinkler head.
In single interlock applications, one electrical detector senses the
presence of fire, thereby causing the electrical releasing control pan-
el to activate fire alarm devices and latch the solenoid releasing valve
in the open position. Note that arranging detectors in a cross-zoned
pattern will require operation of two detectors before the solenoid
valve can open (Note: Cross-zoned detection systems are not per-
mitted in New York City and are not Factory Mutual Approved). The
solenoid valve, when closed, is preserving supply water pressure in
the inlet of the Reliable Model H Deluge Riser Assembly. Actuating
the solenoid valve releases that water pressure, allowing water flow
into the sprinkler system in readiness for the subsequent operation
of a sprinkler.
To fully operate a single interlock system with cross-zoned detec-
tion, two separate electrical detection systems must activate and a
sprinkler must open. During the early stages of a fire, smoke or heat
activates the first detector, which causes the control panel to pro-
duce a local alarm and an alarm at the main fire alarm panel. Elec-
trical relays inside the releasing control panel can be used to shut
down air moving equipment or activate security doors and other
electrical devices when the panel goes into this first alarm condition.
Subsequent activation of a second, nearby or adjacent detector, on
a separate detection system, will cause the panel to energize the
solenoid valve open and release water into the sprinkler piping. Wa-
ter flowing into the sprinkler piping will simultaneously produce water
pressure that causes the transfer of contacts in the pressure switch
mounted in the riser assembly, thereby activating a water flow alarm
device. The flow of water into the sprinkler piping effectively converts
the dry system into a wet pipe system. In the event the fire subse-
quently produces sufficient heat to operate a sprinkler head, water
will flow from that sprinkler, controlling the fire.
To flow water into a double interlock preaction system, two events
must take place. A fire detection device must operate, and a pres-
sure switch must be operated by the loss of system pressure (sprin-
kler operation). These two signals, both an electric signal and a
pneumatic signal, must coexist at the releasing control panel, which
only then will energize the solenoid releasing valve, causing water
flow into the system and out of the open sprinkler(s).
In the event that the system piping is ruptured or a sprinkler head
is accidentally opened, the system pressure switch will operate and
an alarm will sound. The riser assembly, however, will not release
water since the solenoid valve remains closed due to only one input
into the control panel.
When using the Reliable Model H PrePaK in either single or dou-
ble interlock applications, the sprinkler system is pressurized (super-
vised) with air provided by the HP tank-mounted air compressor
and is monitored by the system pressure switch.
A hydraulic manual emergency releasing station is standard
equipment in the Model H PrePaK. It is identified by a nameplate
attached above the releasing valve.
Preaction trim provides a by-pass drain line and the air supply re-
quired to supervise the preaction system at 10 psi (0,7 bar). This trim
includes a UL Listed Reliable Model G Right-Checkä Valve installed
with rigid grooved pipe couplings.
Approvals
The Reliable Model H 1½” (40mm) PrePaK Preaction System
is Underwriters Laboratories Inc. (UL) Listed and UL Certified for
Canada*, as an assembled unit, in the “Special System Water
Control Valves Assembled Units” category (VKYL). New York City
Approved, MEA 258-93-E, when installed in accordance with the
following guidlines and limitations:
For Single Interlock Preaction Systems:
1. Cross-zoning of preaction system detectors is prohibited, ex-
cept where used as a secondary system to a gaseous sup-
pression system.