Note: Each MPPT has power limitation, it's recommended to
sharing the DC input of the 4 x MPPT.
Note: After connecting the 485 communication line, fix the cable on
the tie bridge to avoid loosening and falling off the communication
line.
3.3.2 Connect the PV wire to the positive PV and negative PV terminals
accordingly.
4.Running Setting
Check all connections again before
starting the inverter. To start the
inverter, please switch on AC breaker
first, then switch on the DC switch (If
there) on inverter. If all connections
are correct and PV configurations are
correct, LCD will be on, "WAIT" LED
will be on, inverter will be standby for
Grid-tied connecting.
4.1 Working Mode Setting
Default working mode of inverter is independent. If the PV
connections are not independent, mode settings required. On LCD,
please press "ESC" to enter main menu interface, select "Setting",
then press "ENTER" to confirm to enter password interface. Enter
"00000 " and press "ENTER" to confirm. Select " INPUT MODE ",
press"ENTER" to confirm, move the cursor to choose the correct
mode and press "ENTER " to confirm. After the setting, restart the
inverter, the setting will be valid. (Note: before the setting, please
switch off AC breaker, DC connected, inverter will give alarm, the
setting should be carried out during this. "ESC" for quit, "UP",
"DOWN" for moving cursor, "ENTER" for confirming).
4.2 Safety Standard Setting
Default working mode of inverter is independent. If the PV
connections are not independent, mode settings required. On LCD,
please press "ESC" to enter main menu interface, select "Setting",
then press "ENTER" to confirm to enter password interface. Enter
"00000 " and press "ENTER" to confirm. Select " INPUT MODE ",
press"ENTER" to confirm, move the cursor to choose the correct
mode and press "ENTER " to confirm. After the setting, restart the
inverter, the setting will be valid. (Note: before the setting, please
switch off AC breaker, DC connected, inverter will give alarm, the
setting should be carried out during this. "ESC" for quit, "UP",
"DOWN" for moving cursor, "ENTER" for confirming).
4.3 Grid-tied Dc Voltage Setting
Grid-tied DC voltage can be set on the inverter when in error
conditions (inverter factory default is 350Vdc), normally there is no
to need. If needed, setting can be finished in the panel through the
button, the steps are as follows:
Press "ESC" key to enter the main menu interface, select the first
option "settings", press "ENTER " to confirm, enter password
"00000" and confirm, enter the setup menu, select the fourth option
"operation parameters ", press " ENTER " to confirm, enter the menu
and select f i r st opti o n " power v o l t age” ac c o r d i n g to t h e
requirements, setting will be valid after restarting.
4.4 Rs485 Address Setting
Rs485 address can be set when the inverter is grid- connected or
giving alarm (default address is 1). It's no need to set it if there is
single inverter in communication. To set it, please press "ESC" to
enter the main menu, select "setting" and press "ENTER" to confirm,
enter password"00000" and press "ENTER", select"485 address",
press” ENTER" to confirm and enter desired address (max is 32),
press “ENTER" to confirm. Setting will be valid after restarting.
3.3 PV Input Connection
3.3.1 Installation instructions of PV terminal connection & disconnection
(Terminal has polarity, pay attention to the "+" "-" logo on the body).
d.Lock nut operation.
█ Attention: you can do the connection and disconnection operation when connectors
are unloaded.
█ Input pv cable standard: inner diameter 12AWG (4mm²), external diameter
Ø6mm(Recommend)
a. Using a cable clamp to stripp off the wire skin 7±0.5mm, be careful not to damage the
copper core.
b. Using a special wire crimper tool which have amphenol certification, put the stripping
cable into the wire crimper jaw, correspond to the correct locator hole position,please
make sure no any damage to the locating wings.
c. Insert the pressed wire terminal into the backside of the connector, you will hear a
sound of “drop” when the plug in right position, the terminal will not be pulled out
again.( be careful not to make any mistake for the connection between terminal and
connectors)
locating wings
Female Connector
Male Connector
1 2 3 4
+ + - -
Pin NO.
1
2
3
4
RS485
(A)R/T+
(A)R/T+
(B)R/T-
(B)R/T-
Inverter1 485
Pin NO.
1
2
3
4
RS485
(A)R/T+
(A)R/T+
(B)R/T-
(B)R/T-
Pin NO.
1
2
3
4
RS485
(A)R/T+
(A)R/T+
(B)R/T-
(B)R/T-
...
485 PortRS232/RS485 Converter
Pin NO.
1
2
3
4
RS485
(A)R/T+
(A)R/T+
(B)R/T-
(B)R/T-
Pin NO.
1
2
3
4
RS485
R/ T +
R/ T -
VC C
GN D
3.4 Communication Connection
3.4.1Local communication connection of RS485:
3.4.2 Share 485 BUS for direct connection in multi inverters
Inverter2 485 InverterN 485
3.4.3 Inverter WLAN/GPRS port.
Note: When the network communication is for more than two (including)
inverters, for last inverter, the 2P dial switch next to RS485 terminal can
be switched to "ON", equivalent to add a 120Ω communication terminal
resistance between the R/T+ and R/T-.
The inverter is equipped with standard RS232, RS485,WLAN/GPRS and dry
contact (optional) communication ports, and the RS232 communication port
is mainly used for the software upgrade, RS485 communication port is for
inverter cable monitoring, WLAN/GPRS communication port is for inverter
wireless monitoring.
1- VCC
2- GND
3- 485A
4- 485B
RS485
DC Input Communication Port AC Output