
VR4200
69-0682—02 2
FAILURE TO FOLLOW THESE WARNINGS COULD
RESULT IN A FIRE OR EXPLOSION WITH
PROPERTY DAMAGE, PERSONAL INJURY OR
LOSS OF LIFE.
1. Disconnect power supply before wiring to
prevent electrical shock or equipment damage.
2. To avoid dangerous accumulation of fuel gas,
turn off gas supply at the appliance service
valve before starting installation, and perform
Gas Leak Test after completion of installation.
3. Do not bend pilot tubing at control or pilot after
compression nut has been tightened, or gas
leakage at the connection can result.
4. Always install sediment trap in gas supply line
to prevent contamination of gas control.
5. Do not force the gas control knob. Use only
your hand to push down the reset button or
turn the gas control knob. Never use any tools.
If the knob or reset button will not operate by
hand, replace the control using a qualified
service technician. Force or attempted repair
may result in fire or explosion.
1. Never apply a jumper across or short the valve
coil terminals. This may burn out the heat
anticipator in the thermostat.
2. When a gas control is installed external to the
appliance, a conduit cover must be installed.
IMPORTANT
1. These gas controls are shipped with protective
seals over inlet and outlet tappings. Do not
remove seals until ready to connect piping.
2. When a gas control is installed external to the
appliance, a conduit cover MUST be installed.
Make sure that the conduit cover is placed over
the flange before rotating the conduit cover into
position.
Follow the appliance manufacturer’s instructions if
available; otherwise, use the instructions provided below
as a guide.
CONVERTING CONTROL FROM NATURAL GAS TO LP GAS
APPLICATION (OR LP GAS TO NATURAL GAS
APPLICATION)
FIRE OR EXPLOSION HAZARD CAN CAUSE
PROPERTY DAMAGE, SEVERE INJURY OR DEATH
Always change the main and pilot burner orifices
when converting from natural gas to LP gas or
from LP gas to natural gas. Follow appliance
manufacturer’s specifications and instructions.
Controls with standard or slow opening
regulators can be converted from one gas to the
other with a conversion kit (order separately).
Order part no. 393691 to convert from natural
(manufactured) to LP gas; order part no. 394588
to convert from LP to natural (manufactured) gas.
Controls with step opening regulators cannot be
converted.
INSTALL ADAPTERS TO CONTROL
If adapters are to be installed on the gas control, mount
them as follows:
Flanges
1. Choose the appropriate flange for your application.
NOTE: A right angle inlet flange cannot be used with
ECO connected.
2. Remove seal over control inlet or outlet.
3. Check to assure that the O-ring is fitted in the
groove of flange. If the O-ring is not attached or is
missing, do not use the flange.
4. With O-ring facing valve, align the screw holes on
the control with the holes in the flange. Insert and
tighten the screws provided with the flange. See
Fig. 1. Tighten the screws to 25 inch pounds of
torque to provide a gas-tight seal.
Bushings
1. Remove seal over control inlet or outlet.
2. Apply moderate amount of good quality pipe
compound to bushing, leaving two end threads
bare. On LP installation, use compound resistant to
LP gas. Do not use Teflon tape.
3. Insert bushing in control and carefully thread pipe
into bushing until tight.
Complete instructions below for piping, installing control,
connecting pilot tubing, thermocouple and wiring. Make
certain the leak test you perform on the control after
completing the installation includes leak testing the
adapters and screws. If you use a wrench on the valve
after flanges are installed, use the wrench only on the
flange, not on the control.
Fig. 1. Fasten flange to valve firmly, but do not
overtighten screws.
LOCATION
The combination gas control is mounted in the appliance
vestible on the gas manifold. If this is a replacement
application, mount the gas control in the same location
as the old control.
Do not locate the gas control where it may be affected by
steam cleaning, high humidity, dripping water, corrosive
chemicals, dust or grease accumulation, or excessive
heat. To assure proper operation, follow these guidelines:
• Locate gas control in a well-ventilated area.
• Mount gas control high enough above the cabinet
bottom to avoid exposure to flooding or splashing
water.
• Assure the ambient temperature does not exceed the
ambient temperature ratings for each component.
• Cover the gas control if appliance is cleaned with
water, steam, or chemicals to avoid dust and grease
accumulation.
• Avoid locating gas control where exposure to
corrosive chemical fumes or dripping water is
possible.
M3081A
VALVE OUTLET
FLANGE
9/64 INCH HEX SCREWS (4)
CONDUIT
COVER
6/32 INCH ROUND
SCREWS (1)