VR8204A,M INTERMITTENT PILOT COMBINATION GAS CONTROL
69-0423—04 2
Fire or Explosion Hazard
Can cause property damage, severe injury, or
death.
Follow these warnings exactly:
1. Disconnect power supply before wiring to
prevent electrical shock or equipment damage.
2. To avoid dangerous accumulation of fuel gas,
turn off gas supply at the appliance service
valve before starting installation, and perform
Gas Leak Test after completion of installation.
3. Do not bend pilot tubing at control or pilot after
compression nut has been tightened, or gas
leakage at the connection may result.
4. Always install sediment trap in gas supply line
to prevent contamination of gas control.
5. Do not force the gas control knob. Use only
your hand to turn the gas control knob. Never
use any tools. If the gas control knob will not
operate by hand, call a qualified service
technician to replace the gas control. Force or
attempted repair can result in fire or explosion.
Never apply a jumper across or short the valve
coil terminals. This may burn out the heat
anticipator in the thermostat or damage the
electronic intermittent pilot (IP) module.
IMPORTANT:
These gas controls are shipped with protective
seals over inlet and outlet tappings. Do not
remove seals until ready to connect piping.
Follow the appliance manufacturer’s instructions if
available; otherwise, use the instructions provided on
page 2 as a guide.
Converting Control from Natural Gas to LP
Gas Application (or LP Gas to Natural Gas
Application)
Fire or Explosion Hazard
Can cause property damage, severe injury, or
death.
Always change the main and pilot burner orifices
when converting from natural to LP gas or from
LP to natural gas. Follow appliance
manufacturer’s specifications and instructions.
Controls are factory-set for natural (and manufactured)
or LP gas. Do not attempt to use a control set for natural
(manufactured) gas on LP gas, or a control set for LP on
natural (manufactured) gas.
Controls with standard regulators can be converted from
one gas to the other with a conversion kit (order
separately). Order Part No. 393691 to convert from
natural (manufactured) to LP gas; order Part No. 394588
to convert from LP to natural (manufactured) gas.
Install Adapters to Gas Control
If adapters are to be installed on the gas control, mount
them as follows:
Flanges
1. Choose the appropriate flange for your application.
2. Remove seal over control inlet or outlet.
3. Check to ensure that the O-ring is fitted in the
groove of the flange. If the O-ring is not attached or
missing, do not use flange.
4. With O-ring facing control, line up the screw holes
on the control with the holes in the flange. Insert
and tighten the screws provided with the flange.
See Fig. 1. Tighten the screws to 25 inch pounds of
torque to provide a gas-tight seal.
Bushings
1. Remove seal over gas control inlet or outlet.
2. Apply moderate amount of good quality pipe com-
pound to bushing, leaving two end threads bare. On
LP installations, use compound resistant to LP
gas. Do NOT use Teflon tape.
3. Insert bushings in control and thread pipe carefully
into bushing until tight.
Fig. 1. Fasten flange to valve firmly, but do not
overtighten screws.
Complete installation below for piping, installing control,
connecting pilot tubing and wiring. Make certain the leak
test you perform on the control after completing the
installation includes leak testing the adapters and
screws. If you use a wrench on the valve after flanges are
installed, use the wrench only on the flange, not the
control.
Location
Do not locate the combination gas control where adverse
environments such as steam cleaning, high humidity or
dripping water, corrosive chemicals, dust or grease
accumulation, or excessive heat are prevalent.
To ensure proper operation, follow these guidelines:
• Locate in a well ventilated area.
• Mount high enough above the cabinet bottom to avoid
exposure to flooding or splashing water.
• Ensure that the ambient temperature does not exceed
the ambient temperature ratings for each component.
• Cover if appliance is cleaned with water, steam, or
chemicals or to avoid dust and grease accumulation.
• Avoid locating where exposure to corrosive chemical
fumes or dripping water is likely.
Mount the combination gas control in the appliance
vestibule on the gas manifold. If this is a replacement
application, mount the control in same location as old
control.