manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. resideo
  6. •
  7. Security Sensor
  8. •
  9. resideo FlexGuard FG-1625R User manual

resideo FlexGuard FG-1625R User manual

FlexGuard® FG-1625R/FG-1625RT Glassbreak Detectector Installation Instructions

Mount the detector.
For location guidelines, refer to the Supplemental
Information on the back page.
Note: If you plan to use the wall tamper, locate the
wall tamper screw position before the mounting
screws position. Refer to the Supplemental Informa-
tion for instructions on using the wall tamper.
•Use a screwdriver to push down on the latch at the
side of the detector to remove the front cover.
Note: Do not remove the PCB from the protective
enclosure.
•For surface wiring, use the FG-SP2 spacer plate
provided.
•Secure the detector with #6 (3.5 mm) or #8 (4.2
mm) screws (not provided).

Wire the detector.
•Route the wire through the wire entry
hole in the PCB center. Cut and strip wire
ends 1/4 inch (6.0 mm).
•Wire the detector using 18-22 AWG
(0.64 mm to
1.02 mm). Reverse polarity connections will
not damage the detector. For proper wiring
methods, refer to the National Electrical
Code NFPA 70.
•After completing wiring, push excess
wire back into the wall and replace the front
cover.
Note: You can secure the cover with a #4
(2.9 mm) screw if required. The hole is
located on the intermediate cover near the
latch.
TIP: Temporarily mount the detector in the intended location and power it with a 9 V battery until testing
establishes effective range coverage. If the 9 V battery is low, both LEDs will flash.

Configure the detector.
The following tables show how to configure DIP
switch S4 to best suit the application. The
illustration shows you the default settings.
SENSITIVITY1
SENS1
SENS2
APPROX.
RANGE
Max
OFF
OFF
25’ (7.6 m)
Med
ON
OFF
15’ (4.6 m)
Low
OFF
ON
10’ (3 m)
SWITCH
OFF
ON
LATCH
Red Alarm LED lights for
5 seconds during alarm.
Red Alarm LED latches
ON when detector
goes into alarm.
2,3
LED
LEDs are disabled
except during power-up
and Test Mode. 4
LEDs are always enabled.
No effect in Remote LED
Enable/Disable Mode.
1Verify range with the FG-701.
2The timing of the alarm relay is not affected by the latched Alarm LED.
3Reset the Alarm LED by removing and restoring power, or by toggling the detector in
and out of test mode.
4LEDs can be enabled or disabled with the FG-701.

Test the detector.
Note: Test the FG-1625R/RT at least once each
year.
Test the detector with the FG-701 Glassbreak
Simulator. The FG-700 can be used if set for
Tempered glass sound.
Activating Test Mode
1Position the simulator within 15’ (4.6 m) of the
FG-1625R/RT detector.
2Switch the FG-701 simulator to ACTIVATE
and MANual modes.
3Point the front speaker of the simulator at the
detector and press the red start button.
The simulator buzzes, and the green LED on
the FG-1625R/RT flashes about once per
second to indicate it is in Test Mode.
If an FG-701 is not available, or if for any reason
remote activation cannot be used, use a small
screwdriver to short the test pads on the PCB. This
activates Test Mode.
Make sure to replace the front cover of the unit before testing.
Testing the FG-1625R/RT
1Set the FG-701 switches to the TEST and FLEX positions.
2Position the FG-701 near the farthest point of the glass
and point the speaker directly at the FG-1625R/ RT. If window
coverings are present, close them fully and hold the FG-701
behind them.
3Press the red start button. The simulator “clicks” on and
starts an 8 second armed period.
4Generate a flex signal by carefully striking the glass with a
cushioned tool. The FG-701 responds by producing a burst of
glassbreak audio.
If the FG-1625R/RT properly receives both the simulator flex
and audio, the red alarm LED lights.
Note: Some environmental factors may reduce the detector activation
range. If after pressing the red start button you do not see the green LED
flashing, move closer to the detector and try again.
Testing the Audio Alone
You can also use the simulator in the MANual mode to test audio alone. The
green LED on the detector flickers when the detector properly receives the
simulator audio. (See the FG-701 Operating Instructions for additional
information.) Keep in mind this is not a complete test.
Exiting Test Mode
After testing, exit Test Mode using the same procedure for activating Test
Mode. The FG-1625R/RT automatically exits the Test Mode 5 minutes after the
last event is detected.
REMOTE LED ENABLE/DISABLE MODE
The detector’s Remote LED Enable/Disable Mode allows you to enable or
disable the detector’s LEDs with the FG-701 Glassbreak Simulator.
To enable or disable the LEDs with the FG-701:
1. Set LED switch, S4 position 4, to off.
2. Enter Test Mode, and then exit Test Mode.
3. Within two (2) seconds, enter Test Mode again; this changes LED
enable/disable status.
4. Exit Test Mode again.
5. Clap your hands to test the LEDs. If enabled, the green LED will flicker. If
disabled, the green LED will remain off.
LOCATION GUIDELINES
The FG-1625R/RT detects framed glass broken by an impact sufficient to make a hole.
Refer to the following guidelines when selecting a mounting location:
•The FG-1625R/RT can be mounted in corners, on walls, and on ceilings.
•Mount within 25’ (7.6 m) of the glass.
•There is no minimum range, but the detector must have a clear line-of-sight and a
clear view of the glass.
•The ideal location is on the wall or ceiling directly opposite the glass. The least
desirable location is on the same wall as the glass.
•When wall mounting, mount the detector a minimum of 6’ (1.8 m) high.
•Curtains, blinds and other window coverings absorb energy from breaking glass.
Heavy curtains, for example, effectively block the sound signal. In these cases,
mount the detector on the window frame behind the window covering or above the
window.
•Do not mount within 3’ (0.9 m) of forced air ducts, sirens, or bells measuring 2” (5
cm) or more in diameter.
•Minimize range to the glass. Do not install beyond the maximum specified range
even if testing indicates greater range.
•Adjust sensitivity for desired range; verify by testing with the FG-701.
•Mounting on freestanding posts and pillars is not recommended.
•Verify all installations back to the panel to be sure the protection loop is intact.
•Do not use outside.
•Avoid installing in rooms with high-level noise sources, such as air compressors,
bells, and power tools if those sources can be active when the detector can
signal analarm.
•Test false alarm immunity by activating any noise sources in the room.
Note: The FG-1625R/RT detects shattering of framed glass by a direct impact. It may
not consistently detect breakage by blows that only crack the glass, by high velocity
projectiles (such as bullets) or if the glass is broken without an impact.
USING THE CEILING/WALL TAMPER SWITCH (FG-1625RT ONLY)
The FG-1625RT has a combination normally-closed (NC) cover and wall tamper.
Each detector is shipped with the cover tamper operational and the ceiling/wall
tamper disabled.
•Use needle-nose pliers to break out the plastic tab on the back of the detector. The
tamper arm then extends through the hole.
•The tamper screw (not provided) should be a flat-head #8 (4.2 mm) or Tamper
#10 (4.8 mm) screw.
•Install the tamper screw so it will just make
contact with the bottom of the mounted
detector’s tamper cavity.
•After installing the tamper screw, position the
detector over it and mark
the locations for the mounting screws.
LED INDICATORS
The two LEDs on the front cover indicate the detector's operational status. The
following table summarizes the LED operation when the LEDs are enabled.
Protected glass:
Minimum size for all types is 11 inches (28 cm) square. Glass must be framed in the wall of the
room or mounted in a barrier of 36 inches (0.9 m) minimum width.
1 Protected only if both glass plates are broken.
2 Coated glass with security films up to 0.35mm (14 mils) thick (including films for solar
protection) may be used. Evaluated with these products: 3M® SCOTCHSHIELD®
SH14CLARL – 0.35mm
(14 mils), 4 ply film; Film Technologies International, Inc.’s GLASS-GARD® GGLL 1200 –
0.3mm
(12 mils), 3 ply film by Underwriters Laboratories, Inc., at Resideo’s request.
3 In compliance with Underwriters Laboratories of Canada’s Standard for Intrusion
Detection Units (CAN/ULC-S306-M89)
a ULC recognizes a maximum range of 6m (20 ft.) for protecting 2mm (3/32”) plate and and
3mm (1/8”)laminated.
b ULC recognizes a maximum range for protecting 3mm (1/8”) sealed insulating glass and
all coated glass of 4m (12.5 ft.).
4 UL recognizes a maximum range for protecting 3mm (1/8”) sealed insulating glass of 6m (20
ft.) with sensitivity set at maximum.
IMPORTANT: The FG-1625R/RT must be connected to a UL listed power
supply or UL listed control unit capable of providing a minimum of four hours
of standby power.
2 Corporate Center Drive, Suite 100
P.O. Box 9040, Melville, NY 11747
2020 Resideo Technologies, Inc.
www.resideo.com
SPECIFICATIONS
Range: Operating temperature:
25 feet (7.6m) maximum 14° F to 131°F (-10° C to 55°C)
No minimum range UL: 14° F to 122°F (-10° C to 50°C)
Alarm relay: (Indoor useenvironment)
FG-1625R Form A Storage: -4° F to 131° F (-20° C to 55° C)
FG-1625RT Form C -4° F to 122° F (-20° C to 50° C)
100 mA maximum ESD immunity:
25 VDC maximum 10 kV, Discharges of either polarity to exposed
ON/closed 22ʌ±6ʌsurfaces
OFF/open >1MʌDimensions:
Alarm duration: 4.25” OD x 0.88” THK 5
seconds (unaffected by alarm LED (108 mm x 22.4 mm)
latching) Weight:
Tamper switch: (FG-1625RT only) 4.5 oz., (128 g)
Combination cover and wall tamper Packaged product: 7.5 oz., (213 g) 25
mA maximum Accessories:
24 VDC maximum FG-701 Glassbreak Simulator
Power requirements: FG-SP2 Spacer Plate
8 - 16 VDC; 12 mA typical at Approvals/Listings:
12 VDC, 22 mA max.; FCC and IC Verified
AC Ripple: 4 Volts peak-to-peak UL Listed
at nominal12 VDC ULC Listed
RFI immunity: CE
30 V/m, 10 MHz - 1000 MHz FG-1625RT only:
ESD immunity: EN 50131-1, Grade 2, Class II
10 kV, Discharges of either polarity to Suitable for connection to an EN 60950 Class II
exposed surfaces Limited Power Source
Responsible Party / Issuer of Supplier’s Declaration of Conformity: Ademco Inc., a subsidiary
of Resideo Technologies, Inc., 2 Corporate Center Drive., Melville, NY 11747, Ph: 516-577-
2000
For any additional information regarding the compliance of this product to any EU specific requirements,
please contact:
Sécurité Communication
1198, Avenue du Docteur Maurice Donat
BP 1219 - 06254 MOUGINS CEDEX, FRANCE
Tel.: +33 (0)4 92 94 29 50
fax: +33 (0)4 92 94 29 60.
NOTICES
FCC NOTICE: This equipment has been tested and found to comply with the limits for a Class
B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference in a residential installation. This equipment
generates, uses, and can radiate radio frequency energy and, if not installed and used in
accordance with the instructions, may cause harmful interference to radio communications.
However, there is no guarantee that interference will not occur in a particular installation. If
this equipment does cause harmful interference to radio or television reception, which can be
determined by turning the equipment off and on, the user is encouraged to try to correct the
interference by one or more of the following measures: 1) Reorient or relocate the receiving
antenna, 2) Increase the separation between the equipment and receiver, 3) Connect the
equipment into an outlet on a circuit different from that to which the receiver is connected,
4) Consult the dealer or an experienced radio/television technician for help.
The user is cautioned that changes or modifications not expressly approved by Resideo
could void the user’s authority to operate this equipment.
IC Notice: This Class B digital device apparatus complies with the Canadian standard
ICES-003. Cet appareil numérique de la Classe B est conforme à la norme NMB-003
du Canada.
Ê5-051-738-00F*Š
This product is manufactured by Resideo and its affiliates.
For the latest U.S. warranty information, please go to: www.resideo.com or Please contact your local
authorized Resideo representative for product warranty information. 5-051-738-00F 7/14 Rev. F
Condition Green LED Red LED
Normal
OFF
OFF
Normal, event detected Flicker OFF
Normal, break detected OFF ON 5 seconds
Normal, alarm latched OFF ON continuously
Power up ON 1 second ON 1 second
Low voltage Flash ON/OFF Flash ON/OFF
Test Mode Flash once per second OFF
Test Mode, event detected Flicker OFF
Test Mode, alarm Flash once per second ON 5 seconds
Type
Thickness
Minimum
Maximum
Plate 3a,4
3/32” (2 mm)
3/8” (10 mm)
Tempered
1/8” (3 mm)
3/8” (10 mm)
Laminated 1,3a
1/8” (3 mm)
9/16” (14 mm)
Wired 3a
1/4” (6 mm)
1/4” (6 mm)
Coated 2,3b
1/8” (3 mm)
1/4” (6 mm)
Sealed Insulating 1,3b,4
1/8” (3 mm)
1/4” (6 mm)
[1/2” (13 mm overall)]
[3/4” (19 mm overall)]

This manual suits for next models

1

Other resideo Security Sensor manuals

resideo CHW3610W User manual

resideo

resideo CHW3610W User manual

resideo Lyric RCHW3610WF User manual

resideo

resideo Lyric RCHW3610WF User manual

resideo Honeywell Home SiXOCC User manual

resideo

resideo Honeywell Home SiXOCC User manual

resideo 5800COV User manual

resideo

resideo 5800COV User manual

resideo C554A Operation manual

resideo

resideo C554A Operation manual

resideo FlexGuard FG-730 User manual

resideo

resideo FlexGuard FG-730 User manual

resideo Honeywell Home PROA7 Series User manual

resideo

resideo Honeywell Home PROA7 Series User manual

resideo L1 User manual

resideo

resideo L1 User manual

resideo 5800CMBOV User manual

resideo

resideo 5800CMBOV User manual

resideo 5800PIR-OD2 Assembly instructions

resideo

resideo 5800PIR-OD2 Assembly instructions

resideo Honeywell Home PROOUTMV Assembly instructions

resideo

resideo Honeywell Home PROOUTMV Assembly instructions

resideo TWLD3005-001 User manual

resideo

resideo TWLD3005-001 User manual

resideo DT8035V User manual

resideo

resideo DT8035V User manual

Popular Security Sensor manuals by other brands

RKI Instruments CT-7 Series Operator's manual

RKI Instruments

RKI Instruments CT-7 Series Operator's manual

Rielta Pyrone-4RK installation guide

Rielta

Rielta Pyrone-4RK installation guide

Agni AGNI-203 quick start guide

Agni

Agni AGNI-203 quick start guide

Bosch TriTech DS950 Series installation instructions

Bosch

Bosch TriTech DS950 Series installation instructions

Simtronics GD1 operating manual

Simtronics

Simtronics GD1 operating manual

Baumer UNCK 09G8914 quick start guide

Baumer

Baumer UNCK 09G8914 quick start guide

Omron WS02-CFSC1-E Operation manual

Omron

Omron WS02-CFSC1-E Operation manual

Bradley S19-310JJ installation manual

Bradley

Bradley S19-310JJ installation manual

RKI Instruments 35-3010RKA-08 manual

RKI Instruments

RKI Instruments 35-3010RKA-08 manual

Teledata SWF1000 quick start guide

Teledata

Teledata SWF1000 quick start guide

Siemens CEREBRUS PYROTRONICS AD-3XRI Installation/Wiring Instructions

Siemens

Siemens CEREBRUS PYROTRONICS AD-3XRI Installation/Wiring Instructions

SICK WEU26-3 operating instructions

SICK

SICK WEU26-3 operating instructions

SubSurface Instruments PL-VF10 user manual

SubSurface Instruments

SubSurface Instruments PL-VF10 user manual

Triplett ET330 user manual

Triplett

Triplett ET330 user manual

steute Ex RC Si 56-3G/D Mounting and wiring instructions

steute

steute Ex RC Si 56-3G/D Mounting and wiring instructions

Siemens FDL241-9 Commissioning

Siemens

Siemens FDL241-9 Commissioning

Campbell SurfaceVue 10 product manual

Campbell

Campbell SurfaceVue 10 product manual

Vivax Metrotech vLoc3 Series user guide

Vivax Metrotech

Vivax Metrotech vLoc3 Series user guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.