Display channels
Channel Description Connection terminal Page
INIT x* ODB initialisation active - 23
FLL x* ODB lling time active - 23
STAB x* ODB stabilisation in progress - 23
COL x Temperature collector S1 24
TSTB x Temperature store 1 base S2 24
TSTT x Temperature store 1 top S3 24
TDIS s* Thermal disinfection temperature (thermal disinfection) S3 24
S4 x Temperature sensor 4 S4 24
TFL x* Temperature ow sensor S1 / S4 / VFD 24
TR x* Temperature return sensor S4 / VFD 24
VFD x* Temperature Grundfos Direct Sensor™ VFD 24
L/h x* Flow rate Grundfos Direct Sensor™ VFD 25
n1 % x Speed R1 R1 25
h P1 x Operating hours R1 R1 26
h P2 x Operating hours R2 R2 26
kWh x* Heat quantity in kWh - 25
MWh x* Heat quantity in MWh - 25
CDIS s* Countdown of monitoring period (thermal disinfection) - 25
SDIS s* Starting time display (thermal disinfection) - 25
DDIS s* Heating period display (thermal disinfection) - 25
TIME x Time - 26
Adjustment channels
Channel Description Factory setting Page
Arr x System 2 26
DT O x Switch-on temperature difference R1 6.0 K [12.0 °Ra] 27
DT F x Switch-off temperature difference R1 4.0 K [8.0 °Ra] 27
DT S x Set temperature difference R1 10.0 K [20.0 °Ra] 27
RIS x Rise R1 2 K [4 °Ra] 27
PUM1 x Pump control type R1 PSOL 28
n1MN x Minimum speed R1 30 % 28
n1MX x Maximum speed R1 100 % 28
S MX x Maximum store temperature 60 °C [140 °F] 28
OSEM x Store emergency shutdown option OFF 29
EM x Collector emergency temperature 130 °C [270 °F] 29
Collector emergency temperature if ODB is activated: 95 °C [200 °F] 29
OCC x Collector cooling option OFF 29
CMX x* Maximum collector temperature 110 °C [230 °F] 29
OSYC x System cooling option OFF 30
DTCO x* Switch-on temperature difference cooling 20.0 K [40.0 °Ra] 30
DTCF x* Switch-off temperature difference cooling 15.0 K [30.0 °Ra] 30
OSTC x Store cooling option OFF 30
OHOL x* Holiday cooling option OFF 30
THOL x* Holiday cooling temperature 40 °C [110 °F] 30