3.4 Controller parameter and indication channels
3.5 Function description
Important notice:
By means of a internal locking mechanism, it is only possible
to adjust such pairs of values, for which the switch-on tem-
perature differential DE is at least by 0,5 K bigger than the
switch-off temperature differential DA.
The RESOL DeltaSol® KS controller controlls the tem-
perature diffence between the absorber and return flow
pool(S1 and S2) temperature and compares this difference
to a predetermined switch-on temperature differential ∆TON
(DE). The controller siwtches ON, if the measured tempera-
ture difference ∆T is bigger than or equals the value pread-
justed in the DE channel. Symbols and are displayed
and the operating control lamp flashes green (phase 0).
If the switch-off temperature differential ∆Toff (DA) between
the absorber and the return flow pool (S1 and S2) is under-
run, the R1 relay will remain switched on for the duration
of the preadjusted switch-on delay (VA). Symbols and
(flashing) are displayed and the operating control lamp
flashes green (phase 1).
If the temperature differential between the feed and return
flow (S3 and S2) of the pool after the preadjusted switch-off
temperature delay is bigger than the switch-off temperature
differential, relay R1 will remain switched on. Symbols
and are displayed and the operating control lamp flashes
green (phase 2).
Channel Indication Value group Min. Max. Factory setting Unit Specification
AB absorber temperature measured value - - - °C current absorber temperature
RL return flow temperature measured value - - - °C current return flow temperature
VL feed flow temperature measured value - - - °C current feed flow temperature
VZ delay time check value - - - min current active delay time, see also
page 8 (control phases)
PH control phase check value - - - - -
DE switch-on temperature
differential
set value 1.5 10.0 6.0 K If the preadjusted temperature
difference is exceeded, R1 is
switched on.
DA switch-off temperature
differential
set value 1.0 9.5 4.0 K If the preadjusted temperature
difference is underrun, R1 is
switched off.
MX pool maximum tempe-
rature
set value 10.0 40.0 30.0 °C If the preadjusted temperature is
exceeded, R1 is switched off.
VA switch-off delay set value 0.1 15.0 1.0 min switch-on follow-up time, see also
page 8 (control phases).
VE switch-on delay set value 0,1 15.0 1.0 min switch- on delay, see also page 8
(control phases).
TE thermostat switch-on
temperature
set value 0.0 95.0 40.0 °C see chapter 3.11
TA thermostat switch-off
temperature
set value 0.0 95.0 40.0 °C see chapter 3.11
PG program number indication -
VN version-number indication -
If the switch-off temperature differential between the feed
and return flow of the pool is underrun, relay R1 is swit-
ched off. The following switch-on delay (VE) prevents a too
frequent switch-on of the system (clocking) and enables a
sufficient re-heating of the absorber. Symbol (flashing)
is displayed and the operating control lamp flashes green
(phase 3).
The currently active control phase (PH) and the already
terminated appropriate delay time (VA, VE) will be displayed
as check values in channels PH and VZ .