
www.rosscontrols.com 9
CC4 Series Valves Integration Guide
Using EXTERNAL Pilot Supply (Optional configuration):
When operating the CC4 valve with EXTERNAL pilot pressure (supplied externally from a separate source through the X port), a loss
of supply pressure in supply port 1, but not in external pilot supply port X, will allow the valves to remain actuated; thus, potentially
causing unexpected cylinder movement. This fault where both valves remain actuated while the main supply pressure is lost can
be detected through the addition of an upstream pressure switch or transducer in the main supply line to port 1. This additional
pressure switch or transducer must be monitored by the safety monitoring system to detect a fault where supply pressure in port 1
is too low. This condition should be registered as a valve fault by the safety control monitoring system, which should remove power
from all solenoids on the CC4 valve. Thus, stopping any further cylinder movement.
WARNING: When utilizing EXTERNAL pilot supply from a source that is independent of the main valve supply, loss of pressure
in the main valve supply could cause unexpected cylinder movement.
NOTE: No ladder logic example provided for additional equipment.
No Supply Pressure Applied Before Actuation
Monitoring of supply pressure may also be utilized if deemed beneficial for the application but is not required (unless using external
pilot supply). If you choose to detect this condition it would require the addition of an upstream pressure switch or transducer in
the main supply line to port 1. The condition of the pressure switch or transducer should be monitored to prevent actuation of the
valve when supply pressure is insufficient. However, this becomes essential when external pilot pressure is being used.
See above information on Loss of Supply Pressure While Actuated.
NOTE: No sample ladder logic provided for additional equipment.
Valve Fault & Safety System Reset
Any detected fault in the valve system should cause the safety control system to de-actuate the valve by removing power from all
solenoids. Any fault should be latched in by the safety monitoring system until a reset is performed. A reset of the safety control
system should only be possible after the valve sensors indicate that both valves in the CC4 are in the center, de-actuated position
(both sensors switched on).
Safety System Reset Ladder Logic Example
< >
Reset Button Extend Signal Sensor A Sensor BRetract Signal Reset
Limitations of Load Holding Due to System Leakage
Leakage in a safe cylinder stop/load holding application has the potential to create unexpected motion regardless of whether the
leakage occurs in the valve, hoses, connections or the cylinder. The CC4 series valves are equipped with valve position sensors for
external monitoring to meet diagnostic coverage requirements. However, position sensing does not detect leakage. The CC4 series
valves are designed to have redundant valve elements that are interconnected in such a manner that any single point of leakage within
the valve will not cause unexpected movement. Therefore, periodic leakage testing of the system may be necessary depending on
the risk assessment specific to the machine or application. If leakage is discovered, measures should be taken to eliminate the leak.
WARNING: Continued operation of the system without periodic leakage inspections can lead to unexpected movement.
Refer to steps 1 - 9 below to help identify valve/system leakage.
Step # Fault Conditions Procedures Sol
12A
Sol
12B
Sol
14A
Sol
14B
Outlet Pressure Sensor Condition Expected
Cylinder
Action
Notes Results
Port 2 Port 4 Sensor A Sensor B
NOTE: Prior to step 1 the cylinder needs to be positioned near mid-stroke.
1Momentarily energize
solenoids 12A & 12B
On then
off
On then
off Off Off Line Line Off then
On
Off then
On
Partial
retract
Energize only long enough
for a partial stroke.
2 Energize solenoid 12A On Off Off Off Line Line Off On None Fault
3 De-energize solenoid 12A Off Off Off Off Line Line On On None No fault
4 Energize solenoid 12B Off On Off Off Line Line On Off None Fault
5 De-energize solenoid 12B Off Off Off Off Line Line On On None No fault
6 Energize solenoid 14A Off Off On Off Line Line Off On None Fault
7 De-energize solenoid 14A Off Off Off Off Line Line On On None No fault
8 Energize solenoid 14B Off Off Off On Line Line On Off None Fault
9 De-energize solenoid 14B Off Off Off Off Line Line On On None No fault
Valve/System Leakage Test Procedure
Operation & Monitoring – Loss of Supply Pressure While Actuated (continued)