Ross Controls DM2 C Series User manual

Product InformatIon
ROSS CONTROLS
Dm2® SerieS c
Safety exhauSt
douBle ValVeS

IMPORTANT NOTE: Please read carefully and thoroughly all of the CAUTIONS, WARNINGS on the inside back cover.
F2.11
Online Version
04/05/19
Cat. 4
PL e
Control Reliable Double Valves
with Dynamic Monitoring and Memory
These valves are not designed for controlling clutch/brake mechanisms on mechanical power presses,
see DM2® Series D double valves for mechanical power press applications.
Explosion proof valves available, see explosion proof valves.
Safety Exhaust (Dump)
DM2® Series C
Simplified Schematic
1
3
2
Basic Size 2, 4, 8, 12 and 30
Dynamic Monitoring With Complete Memory: Memory, monitoring, and air flow control functions are
simply integrated into two identical valve elements. Valves lock-out due to asynchronous movement of valve
elements during actuation or de-actuation, resulting in a residual outlet pressure of less than 1% of supply.
An Action is Required for Reset – cannot be reset by removing and re-applying supply pressure. Reset
can only be accomplished by the integrated electrical (solenoid) reset.
Basic 3/2 Normally Closed Valve Function: Dirt tolerant, wear compensating poppet design for quick
response and high flow capacity. PTFE back-up rings on pistons to enhance valve endurance – operates
with or without in-line lubrication.
Status Indicator: Includes a pressure switch with both normally open (NO) and normally closed (NC)
contacts to provide status feedback to the control system indicating whether the valve is in the lockout or
ready-to-run condition.
Silencers: All models include high flow, clog resistant silencers.
Mounting: Base mounted – with BSPP or NPT pipe threads. Inlet and outlet ports on both sides provide
for flexible piping (plugs for unused ports included). Captive valve-to-base mounting screws.
Basic Size 12 and 30
Intermediate Pilots: Increases pilot air flow for fast valve response, making it possible to use the same size
solenoids as valve sizes 2, 4 & 8, thereby reducing electrical power requirements for these larger valves.
DM2C N B 21 A 2 1
Solenoid
Reset Type
Voltage*
24 volts DC A
110 volts AC, 50 Hz
120 volts AC, 50/60 Hz B
* For other voltages consult ROSS.
ISO 13849-1
CAT 4, PL e
HSM 06008
Sicherheit seprüft
tested safety
√
Basic
Size
Inlet Port
Size
CVWeight
lb (Kg)
1-2 2-3
21/4 1.67 2.61 5.3 (2.4)
3/8 2.17 3.57 5.3 (2.4)
4 1/2 3.01 6.51 5.9 (2.6)
83/4 4.20 9.36 8.4 (3.7)
1 4.32 9.36 8.4 (3.7)
12 1 8.68 17.31 15.3 (3.7)
30
1
½20.11 55.10 34.7 (15.1)
# Valve and base assembly with status indicator.
Other OPTIONS
EN 175301-803 Form A*
(connector not included)
Leave
Blank
M12 (connector included) 005
Silicone Free with
EN 175301-803 Form A
(connector not included)
030
Silicone Free with M12
(connector included) 035
*See options for connectors
or wiring kits.
Basic
Size
Port Size
Inlet Outlet
2
1/4
3/8
1/4
3/8
20
21
Valve Only (No Base)
2X
4
1/2
1/2 42
Valve Only (No Base)
4X
8
3/4
1
3/4
1
54
55
Valve Only (No Base)
5X
12
1 1
66
Valve Only (No Base)
6X
30 1
½
2
88
Valve Only (No Base)
8X
Series
STANDARD SPECIFICATIONS (for valves on this page):
Construction Design Dual Poppet
Mounting Type: Base
Orientation: Vertically with pilot solenoids on top
Solenoids According to VDE 0580. Enclosure rating according to DIN
400 50 IP 65. Three solenoids, rated for continuous duty
Voltage/Power Consumption
(each solenoid)
Basic Size 2, 4, 12 & 30
Primary and Reset Solenoids:
24 volts DC; 110 volts AC, 50 Hz; 120 volts AC, 50/60 Hz
5.8 watts nominal on AC and DC; 6.5 watts maximum on
AC and DC
Basic Size 8
Primary Solenoids:
15 watts on DC; 36 VA inrush and 24.6 VA holding on AC
Reset Solenoids:
6.0 watts on DC; 15.8 VA inrush and 10.4 VA holding on AC
Enclosure Rating IP65, IEC 60529
Electrical Connection EN 175301-803 Form A, or M12
Temperature Ambient: 15° to 122°F (-10° to 50°C)
Media: 40° to 175°F (4° to 80°C)
Flow Media Filtered, lubricated or unlubricated (mineral oils according to
DIN 51519, viscosity classes 32-46)
Operating Pressure Basic Size 2: 45 to 150 psig (3.1 to 10.3 bar).
Basic Size 4, 8, 12, 30: 30 to 120 psig (2.1 to 8.3 bar)
Pressure Switch (Status
Indicator) Rating Contacts - 5 amps at 250 volts AC, or 5 amps at 30 volts DC
Monitoring
Dynamically, cyclically, internally during each actuating and
de-actuating movement. Monitoring function has memory and
requires an overt act to reset unit after lockout
Minimum Operation Frequency Once per month, to ensure proper function
Construction Material
Valve Body: Cast Aluminum
Poppet: Acetal and Stainless Steel
Seals: Buna-N
Functional Safety Data:
Category 4, PL e; B10D: 20,000,000; PFHD: 7.71x10-9; MTTFD: 301.9 (nop: 662400)
Certifications: CE Marked for applicable directives, DGUV Test, CSA/UL, TSSA for
appropriately tested valves.
Vibration/Impact Resistance: Tested to BS EN 60068-2-27.
F
F2
Choose your options (in red) to configure your model number.
SIL 3
Functional Safety
Thread
GD
NPT N
Valve Only (No Base)
X
Revision Level
Basic Size
4, 8, 12, 30 A
2BStatus Indicator*
Yes 1
No/Valve Only (N/A) X
*Installed in the base.

© ROSS CONTROLS®. All Rights Reserved.F2.12 Online Version
04/05/19
Control Reliable Double Valves
with Dynamic Monitoring and Memory
DM2® Series C
Valve Technical Data
Main
Solenoids Status Indicator
0.97
(24.6)
1.32 (33.5)
1.24
(31.5)
1/2 NPT
Outlet Port
(Each Side)
1/2 NPT
Inlet Port
(Each Side)
Solenoid
Reset
6.33 (160.8)
9.97
(253.2) 12.00
(304.8)
4.34 (110.2) View X
(Base mounting hole pattern)
Valve envelope
(Based in overall hole
dimensions at left.)
0.65
(16.6)
0.27 (6.9)
(4 places)
2.74
(69.6)
4.00 (101.6)
0.16
(4.06)
4.34
(110.2)
3.68 (93.5)
12.73
(323.3)
5.41 (137.4)
1.43
(36.3)
1.92 (48.8)
1.90 (48.3)
7.48 (190)
0.34 (8.6)
(4 places)
Valve envelope
(Based in overall hole
dimensions at left.)
View X
(Base mounting hole pattern)
4.60(116.8)
2.68
(68.1)
4.28 (108.7) 0.86
(21.9)
6.23
(158.2)
0.16
(4.1)
3/4 or 1 NPT
Outlet Port
(Each Side)
3/4 or 1 NPT
Inlet Port
(Each Side)
Status
Indicator
Solenoid
Reset
Main
Solenoids
6.74 (117.2)
13.23
(336.1)
13.71
(348.2)
9.42 (239.3)
1.67
(42.4)
2.36 (59.9)
2.07 (52.6)
View X
(Base mounting hole pattern)
Valve envelope
(Based in overall hole
dimensions at left.)
5.86 (148.8)
0.42 (10.7)
(4 places)
7.47
(189.7)
0.57
(14.5)
1.59
(40.4)
1.61 (40.9)
4.72 (119.9)
Main
Solenoids Status
Indicator
1 NPT
Outlet Port
(Each Side)
1 NPT
Inlet Port
(Each Side)
Solenoid Reset
9.85 (250.2)
16.87
(428.5)
11.82 (300.3)
1.95
(49.5)
3.34 (84.8)
2.54 (64.5)
View X
(Base mounting hole pattern)
Valve envelope
(Based in overall hole
dimensions at left.)
8.46 (214.9)
0.50 (12.7)
(4 places)
1.16
(29.5) 9.73
(247.1)
1.73
(44)
6.14 (156)
2.42 (61.5)
Main
Solenoids
Status Indicator
Solenoid Reset
2 NPT
Outlet Port
(Each Side)
1-1/2 NPT Inlet Port
(Each Side)
Basic Size 30
Basic Size 12
Basic Size 8
Basic Size 4
Status
Indicator
Solenoid
Reset
Pressure
Switch
Reset
Port
Pilot booster on
Size 12 & 30
only
1
Schematic - Valve de-actuated
Valve Dimensions – inches (mm)
Basic Size 2 Main
Solenoids
Status Indicator
1/4 or 3/8 NPT
Outlet Port
(Each Side)
1/4 or 3/8 NPT
Inlet Port
(Each Side)
4.74 (120.4)
4.50 (114.3)
2.99
(75.9)
7.90
(200.8)
10.89
(276.7)
0.82
(20.9)
1.19
(30.2)
2.99
(75.9)
View X
(Base mounting hole pattern)
Valve envelope
(Based in overall
hole dimnsions at
left.)
0.22 (5.6)
(4 places)
4.00
(101.6)
4.00 (101.6)
0.25
(6.4)
2.04
(51.9)
0.57 (14.5)
10.32
(262.2)
Solenoid
Reset
F
F2

F2.13
Online Version
04/05/19
ACCessories & options
High-Flow, High Reduction Silencer Kits A
B
C
Port
Size
Kit Number*Flow
scfm
Dimensions inches (mm)
NPT Threads G Threads AB (NPT) B (G) C
42324H77 2329H77 800 (378) 4.34 (110.2) 19.06 (484.1) 21.40 (543.6) 7.27 (184.7)
82325H77 2329H77 800 (378) 5.41 (137.4) 21.18 (538.0) 23.52 (597.4) 8.41 (213.6)
12 2326H77 2330H77 2080 (982) 6.74 (117.2) 25.85 (656.6) 28.20 (716.3) 10.66 (270.8)
30 2327H77 2331H77 7200 (3398) 9.85 (250.2) 41.55 (1055.4) 41.55 (1055.4) 13.47 (342.1)
*Kits include all plumbing required for installation. Pressure Range: 125 psig (8.6 bar) maximum.
Designed to improve equipment performance and reduce the Exponentially Perceived Noise (EPNdB) in the 35–40 dB range.
Valve Locked-out: Whenever the valve elements operate in a sufficiently asynchronous manner, either on actuation or de-actuation,
the valve will move to a locked-out position. In the locked-out position, one crossover and its related timing chamber will be exhausted,
and the other crossover and its related timing chamber will be fully pressurized.
The valve element (side B) that is partially actuated has pilot air available to fully actuate it, but no air pressure on the return piston to
fully de-actuate the valve element. Air pressure in the crossover acts on the differential of side B stem diameters creating a latching
force. Side A is in a fully closed position, and has no pilot air available to actuate, but has full pressure on the inlet poppet and return
piston to hold the element in the fully closed position. Inlet air flow on side A into its crossover is restricted, and flows through the open
inlet poppet on side B, through the outlet into the exhaust port, and from the exhaust port to atmosphere. Residual pressure in the outlet
is less than 1% of inlet pressure. The return springs are limited in travel, and can only return the valve elements to the intermediate
(locked-out) position. Sufficient air pressure acting on the return pistons is needed to return the valve elements to a fully closed position.
Valve Actuated: Energizing the pilot valves
simultaneously applies pressure to both pistons,
forcing the internal parts to move to their actuated
(open) position, where inlet air flow to crossover
passages is fully open, inlet poppets are fully open
and exhaust poppets are fully closed. The outlet is
then quickly pressurized, and pressure in the inlet,
crossovers, outlet, and timing chambers are quickly
equalized. De-energizing thepilots quicklycauses the
valve elements to return to the ready-to-run position.
Valve De-actuated (ready-to-run): The flow of inlet
air pressure into the crossover passages is restricted
by the size of the passage between the stem and
the valve body opening. Flow is sufficient to quickly
pressurize pilot supply/timing chambers A and B. The
inlet poppets prevent air flow from crossover passages
into the outlet chamber. Air pressure acting on the
inlet poppets and return pistons securely hold the valve
elements in the closed position.(Air passages shown
out of position and reset adapter omitted for clarity.)
Control Reliable Double Valves
with Dynamic Monitoring and Memory
DM2® Series C
Valve Operation & Options
Resetting the Valve: The valve will remain in the locked-out
position, even if the inlet air supply is removed and re-applied.
A remote reset signal must be applied to reset the valve. Reset
is accomplished by momentarily pressurizing the reset port.
Actuation of the reset piston physically pushes the main valve
elements to their closed position. Inlet air fully pressurizes the
crossovers and holds the inlet poppets on seat. Actuation of
the reset piston opens the reset poppet, thereby, immediately
exhausting pilot supply air, thus, preventing valve operation
during reset (Resetadapter added toillustration.). De-actuation
of reset pistons causes the reset poppets to close and pilot
supply to fully pressurize. Reset pressure can be applied by a remote 3/2 normally
closed valve, or from an optional 3/2 normally closed solenoid mounted on the reset
adapter. De-actuation of reset pistons causes the reset poppets to close and pilot
supply to fully pressurize.Reset air pressure can be applied by a remote 3/2 normally
closed valve, or from an optional 3/2 normally closed solenoid, or a manual push
button mounted on the reset adapter.
Status Indicator: The status indicator
pressure switch will actuate when the main
valve is operatingnormally, andwill de-actuate
when the main valve is in the locked-out
position or inlet pressure is removed. This
device is not part of the valve lockout function,
but, rather, only reports the status of the
main valve.
Basic Size 12 and 30 valves require relatively large
pilots to actuate and de-actuate the main valve
elements. In order to achieve extremely quick valve
response for such large pilots, a 2-stage solenoid
pilot system is incorporated into the design. This
keeps the required electrical current to operate
the pilots to a minimum.
Status indicator in normal
ready-to-run position.
Basic Size 12 & 30 pilots
EXHAUST
INLET
OUTLET
EXHAUST
OUTLET
INLET
AB
EXHAUST
INLET
OUTLET
EXHAUST
OUTLET
INLET
AB
EXHAUST
OUTLET
INLET
AB
EXHAUST
INLET
OUTLET
EXHAUST
OUTLET
INLET
AB
AB
• May be installed downstream on all double valves
• Provides a redundant means to verify the release
of downstream pressure to next obstruction
• Factory preset, 5 psi (0.3 bar) - falling
Downstream Pressure Monitoring Redundant
Downstream
Feedback Switch
Model Number Port Threads
RC026-13 3/8 NPT
Pressure Switches
Connection Type Model Number Port
Threads
EN 175301-803 Form A 586A86 1/8 NPT
M12 1153A30 1/8 NPT
*
Pressure switch closes on falling pressure of 5 psig (0.34 bar).
Electrical
Connectors
Electrical
Connector
Form
Electrical Connector Type Cord Length
meters (feet)
Cord
Diameter
Electrical Connector Model Number
Without
Light
Lighted Connector
24 Volts DC 120 Volts AC
EN 175301-803
Form A
Prewired Connector (18 gauge) 2 (6½) 6-mm 721K77 720K77-W 720K77-Z
Prewired Connector (18 gauge) 2 (6½) 10-mm 371K77 383K77-W 383K77-Z
Connector for threaded conduit
(1/2 inch electrical conduit fittings) – – 723K77 724K77-W 724K77-Z
Connector Only – – 937K87 936K87-W 936K87-Z
CAUTIONS: Do not use electrical connectors with surge suppressors, as this may increase valve response time when de-actuating the solenoids.
3
1
2
Normally
Closed
Normally Open
Ground
Common
EN Connector Pinout
Pin 1
Common
Pin 3
Not Used
Pin 2
Normally
Closed
Pin 4
Normally
Open
M12 Connector Pinout
F
F2

F2.14 © ROSS CONTROLS®. All Rights Reserved.
IMPORTANT NOTE: Please read carefully and thoroughly all of the CAUTIONS, WARNINGS on the inside back cover.
Online Version
04/05/19
Wiring Kits with J-Box
BRN
GRY
GRN/YEL
GROUND
BLK
1
BRN
3 BLK
2
GRY
1
2
3
Status Indicator
Cable with EN Connector
4
BLACK
3
BLUE
2
3
1
4
3
BLUE 4
BLACK
Solenoid Cables
with M12 Connector
5
A J-Box is a junction box with a 10-pin MINI connector for connecting to the user’s control
system and (4) 5-pin M12 ports for connecting to the 3 solenoids and the status indicator
on the DM2® Series valve. The J-Box kits include the J-Box as described above and
(4) 1-meter cables for connecting to the valve. These cables have a connector on each
end. The status indicator cable and the (3) solenoid cables have an M12 connector on
one end and a EN connector on the other end (M12-DIN).
Standard valves come with DIN type
solenoid connections, but could be
bought with M12 type connections as
well. Therefore we also offer a kit that
provides solenoid cables with an M12
connector on each end (M12-M12). 3.9 (100)
2.90 (73.6)
dia.
0.18
[4.5]
2.0
(51)
1.41
(35.9)
1.125 - 16UN2A
1.85 (46.9)
1
2
10
3
4
5
9
8
7
6
10 Pin
Pin # Port 2
Pin # Port 3
Pin # Port 4
Pin #
Port 1
Pin #
1
2
3
4
5
6
78
9
10
(V+) 1
(V-) 2
3
4
5
6
7
8
9
10
1111
3 3 3 3
2
2
2
2
4
4
4
4
1111
2222
3333
5555
4444
J-Box Wiring
Connector Types Kit Number*Length meters (feet)
M12 - DIN 2249H77 1 (3.3)
M12 - M12 2250H77 1 (3.3)
*24 volts DC only.
Wire Colors:
Orange
Blue
White w/Black
Red w/Black
Green w/Black
PIN #
1 +24 volts DC
2 Common volts DC
3 -
4 Solenoid A
5 Solenoid B
PIN #
6 -
7 Remote Reset
8 -
9 Remote Valve Fault Light
10 Remote System OK Light
Wire Colors:
Orange w/Black
Red
Green/Yellow
Black
White
1
21096
543
78
10 PIN MINI Cable These cables have a 10-pin MINI connector for connecting the J-Box kits above to the user’s control
system. Kits include one cable with connector and cord grip. Cable conductors are 18-gauge wire.
Kit Number Length meters (feet)
2253H77 3.66 (12)
2254H77 6.1 (20)
2255H77 9.1 (30)
2256H77 15.2 (50)
Some customers prefer to monitor downstream
pressure in addition to using the DM2® or DM1Series
valve. A convenient way to do this is to install a pressure
switch in the extra outlet port that is provided on the
valve. The Outlet Port Pressure Monitoring kit can be
used with one of the J-Box kits above to split one of the M12 ports on the J-Box so that a pressure switch
can be wired in as well. These kits consist of one port splitter (a Tee with three M12 connectors) and one
M12-DIN cable (1 meter).
(17)
0.7
(10)
0.4
(40) 1.6
(40)
1.6
M12x1
Female M12x1
Male
Ø0.6
Outlet Port Pressure Monitoring Wiring Kit
Kit Number Length meters (feet)
2251H77 1 (3.3)
Pressure switch available separately, see valve options.
3
4
5
FEMALE
A
5
1
2
3
4
51234
1
2
MALE
FEMALE
B
1
3
2
4
5
PORT SPLITTER
Preassembled Wiring Kits
for Safety Exhaust (Dump)
DM2® Series C
BLACK
PIN 2
GRN/YEL
GROUND
BLACK BLACK
GRN/YEL
BLACK
PIN 1
Solenoid Cables with
EN Connector
1
4
2
Status Indicator Cable
with M12 Connector
2
3
1
4
1
2
34
5
Preassembled Wiring Kits
Solenoid
Connector Type
Kit Number*Length
meters
(feet)
Connector
without Light
Lighted Connector
24 Volts DC 120 Volts AC
EN 175301-803
Form A
2283H77 2532H77-W 2532H77-Z 5 (16.4)
2284H77 2533H77-W 2533H77-Z 10 (32.8)
M12 2288H77 – – 5 (16.4)
2289H77 – – 10 (32.8)
* Each cable has one connector.
These kits include 1 cable for the status indicator, and 3 cables with
connector plus a cord grip for each.
F
F2

IMPORTANT NOTE: Please read carefully and thoroughly all of the CAUTIONS, WARNINGS on the inside back cover.
F2.25
Online Version
04/05/19
Air Entry Assemblies with DM2® Series C
Double Valves with Dynamic Monitoring and Memory
Safety Exhaust/Energy Isolation
M & RC Series
Custom designs available, consult ROSS.
MDM2® Series C Double Valves with Integrated Soft-Start, Manual Lockout L-O-X® Valves
with Integrated Filter/Regulators
Pre-engineered panel mountable design with air entry via a filter and regulator “FR”, or filter, regulator
and lubricator “FRL”
Includes M DM2® Series C Double Valve with Monitoring & Memory:
a) Self-contained dynamic monitoring system requires no further valve monitoring controls,
b) Dynamic memory of abnormal function prevents unintentional reset with removal of air or electricity
All necessary features for safety applications are included:
a) Electrical reset valve,
b) Status indicator switch for valve condition (ready-to-run) feedback
Pipe Size
1/2 NPTF 4
3/4 NPTF 5
1/2 G D
3/4 G E
Lockout Valve Type
*
Modular L-O-X®1
L-O-X®2
No L-O-X®
X
* Silencer included.
Filter-Regulator
(0-125 psi with 0-200 gauge)
5 Micron, Manual Drain, Metal Bowl 1
5 Micron, Auto Drain, Metal Bow 2
None X
Lubricator Fill Type
Fill Port 2
No lubricator X
Extra Ports
(Prior to MDM2
®
Exhaust Valve)
1/4 2
3/8 3
1/2
4
None X
M DM2
®
Valve
Without Transducer 1
With Transducer 3
Extra Ports
(Downstream of M DM2
®
)
1/4 2
3/8 3
1/2
4
None X
Downstram Pressure Switch
(includes 1/4” Extra Port)
586A86
1
None X
Cable Options
Yes 1
No
X
Cat. 4
PL e
DM2® Series C Double Valves, Manual Lockout L-O-X® Valves with Filter and Regulator
Pre-engineered panel-mounted design with air entry via a filter and regulator “FR”, or filter, regulator
and lubricator “FRL”
Includes DM2® Series C Double Valve with Monitoring & Memory:
a) Self-contained dynamic monitoring system requires no further valve monitoring controls,
b) Dynamic memory of abnormal function prevents unintentional reset with removal of air or electricity
All necessary features for safety applications are included:
a) Electrical reset valve,
b) Status indicator switch for valve condition (ready-to-run) feedback
Cat. 4
PL e
Air Entry
Assemblies
Port Size Model Number#Air Entry
Type
CVDimensions inches (mm)
1, 2 3NPT Threads 1-2 2-3 Length Width Depth
Cat-4 with DM2®Series C 1/2 1/2 RC408-06WFR 3 10 24.0 (610) 14.5 (369) 7.4 (187)
Cat-4 with DM2®Series C 1/2 1/2 RC408L-06WFRL 4.4 13 24.0 (610) 15.7 (399) 8.3 (211)
Cat-4 with DM2®Series C 3/4 3/4 RC412-06WFR 4.4 13 27.0 (686) 19.0 (483) 9.0 (229)
Cat-4 with DM2®Series C 3/4 3/4 RC412L-06WFRL 3 10 24.0 (610) 14.5 (369) 7.4 (187)
Cat-4 with DM2®Series C 1 1 RC416-06WFR 4.4 13 24.0 (610) 15.7 (399) 8.3 (211)
Cat-4 with DM2®Series C 1 1 RC416L-06WFRL 4.4 13 31.0 (788) 19.0 (483) 9.0 (229)
# Voltage: W=24 VDC; Z=110-120 VAC, 50/60 Hz, e.g., RC408-06Z.
M12 connectors available, consult ROSS.
Silencer included. Standard Air Entry Assemblies supplied with metal bowl and automatic drain.
Custom designs available, consult ROSS. Explosion proof solenoid pilot available, for more information consult ROSS.
NOTE: Per specications and regulations, lockout L-O-X® products are dened as energy isolation devices, NOT AS EMERGENCY STOP DEVICES.
These valve assemblies are not designed for controlling clutch/brake mechanisms on mechanical power presses.
F
F2
M5 1 1 X A2 1 2 1 1
Choose your options (in red) to configure your valve assembly model number.

3
Online Version
Rev. 07/30/18
CAUTIONS, WARNINGS and STANDARD WARRANTY
PRE-INSTALLATION or SERVICE
1. Before servicing a valve or other pneumatic component, be
sure that all sources of energy are turned off, the entire pneumatic
system is shut off and exhausted, and all power sources are locked
out (ref: OSHA 1910.147, EN 1037).
2. All ROSS products, including service kits and parts, should
be installed and/or serviced only by persons having training and
experience with pneumatic equipment. Because any installation
can be tampered with or need servicing after installation, persons
responsible for the safety of others or the care of equipment
must check every installation on a regular basis and perform all
necessary maintenance.
3. All applicable instructions should be read and complied with
before using any fluid power system in order to prevent harm to
persons or equipment. In addition, overhauled or serviced valves
must be functionally tested prior to installation and use. If you have
any questions, call your nearest ROSS location listed on the cover
of this document.
4. Each ROSS product should be used within its specification
limits. In addition, use only ROSS parts to repair ROSS products.
WARNING: Failure to follow these directions can adversely
affect the performance of the product or result
in the potential for human injury or damage to
property.
FILTRATION and LUBRICATION
5. Dirt, scale, moisture, etc. are present in virtually every air system.
Although some valves are more tolerant of these contaminants than
others, best performance will be realized if a filter is installed to
clean the air supply, thus preventing contaminants from interfering
with the proper performance of the equipment. ROSS recommends
a filter with a 5-micron rating for normal applications.
6. All standard ROSS filters and lubricators with polycarbonate
plastic bowls are designed for compressed air applications only.
Do not fail to use the metal bowl guard, where provided, to
minimize danger from high pressure fragmentation in the event of
bowl failure. Do not expose these products to certain fluids, such
as alcohol or liquefied petroleum gas, as they can cause bowls to
rupture, creating a combustible condition, hazardous leakage, and
the potential for human injury or damage to property. Immediately
replace a crazed, cracked, or deteriorated bowl. When bowl gets
dirty, replace it or wipe it with a clean dry cloth.
7. Only use lubricants which are compatible with materials
used in the valves and other components in the system.
Normally, compatible lubricants are petroleum based oils with
oxidation inhibitors, an aniline point between 180°F (82°C) and
220°F (104°C), and an ISO 32, or lighter, viscosity. Avoid oils
with phosphate type additives which can harm polyurethane
components, potentially leading to valve failure which risks human
injury, and/or damage to property.
AVOID INTAKE/EXHAUST RESTRICTION
8. Do not restrict the air flow in the supply line. To do so could
reduce the pressure of the supply air below the minimum
requirements for the valve and thereby cause erratic action.
9. Do not restrict a valve’s exhaust port as this can adversely
affect its operation. Exhaust silencers must be resistant to clogging
and must have flow capacities at least as great as the exhaust
capacities of the valves. Contamination of the silencer can result
in reduced flow and increased back pressure.
WARNING: ROSS expressly disclaims all warranties and
responsibility for any unsatisfactory performance
or injuries caused by the use of the wrong type,
wrong size, or an inadequately maintained silencer
installed with a ROSS product.
POWER PRESSES
10. Mechanical power presses and other potentially hazardous
machinery using a pneumatically controlled clutch and brake
mechanism must use a press control double valve with a monitoring
device. A double valve without a self-contained monitoring device
should be used only in conjunction with a control system which
assures monitoring of the valve. All double valve installations
involving hazardous applications should incorporate a monitoring
system which inhibits further operation of the valve and machine in
the event of a failure within the valve mechanism.
ENERGY ISOLATION/EMERGENCY STOP
11. Per specifications and regulations, ROSS L-O-X® and L-O-X®
with EEZ-ON® operation products are defined as energy isolation
devices, NOT AS EMERGENCY STOP DEVICES.
All products sold by ROSS CONTROLS are warranted for a one-year period
[with the exception of all Filters, Regulators and Lubricators (“FRLs”) which are
warranted for a period of seven years] from the date of purchase to be free of
defects in material and workmanship. ROSS’obligation under this warranty is
limited to repair or replacement of the product or refund of the purchase price paid solely at the discretion of ROSS and provided
such product is returned to ROSS freight prepaid and upon examination by ROSS is found to be defective.This warranty becomes
void in the event that product has been subject to misuse, misapplication, improper maintenance, modification or tampering.
THE WARRANTY EXPRESSED ABOVE IS IN LIEU OF AND EXCLUSIVE OF ALL OTHER WARRANTIES AND ROSS EXPRESSLY
DISCLAIMS ALL OTHER WARRANTIES EITHER EXPRESSED OR IMPLIED WITH RESPECT TO MERCHANTABILITY OR FITNESS
FOR A PARTICULAR PURPOSE. ROSS MAKES NO WARRANTY WITH RESPECT TO ITS PRODUCTS MEETING THE PROVISIONS
OF ANY GOVERNMENTAL OCCUPATIONAL SAFETY AND/OR HEALTH LAWS OR REGULATIONS.IN NO EVENT IS ROSS LIABLE TO
PURCHASER, USER, THEIR EMPLOYEES OR OTHERS FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES WHICH MAY RESULT
FROM A BREACH OF THE WARRANTY DESCRIBED ABOVE OR THE USE OR MISUSE OF THE PRODUCTS. NO STATEMENT OF
ANY REPRESENTATIVE OR EMPLOYEE OF ROSS MAY EXTEND THE LIABILITY OF ROSS AS SET FORTH HEREIN.
STANDARD WARRANTY
Table of contents
Other Ross Controls Control Unit manuals

Ross Controls
Ross Controls DM1 Series C User manual

Ross Controls
Ross Controls SAE Valves 80 Series User manual

Ross Controls
Ross Controls M DM2 C Series User manual

Ross Controls
Ross Controls Automatic Valve A04 Series Operating instructions

Ross Controls
Ross Controls CrossCheck CC4 Series Quick setup guide

Ross Controls
Ross Controls DM2C Series User manual

Ross Controls
Ross Controls Miniature Valves W14 Series User manual